2012-01-05 13:21:36 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| 2007 FLORIDA RESIDENTIAL CODE W/ 2009 REVISIONS. |
| |
| |
| 1- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE |
| OF NOA 08-0410.09 SUBMITTED. PAGE 35 OF NOA SUBMITTED |
| IS GOOD FOR 60PSF. CORNER AND PERIMETER AREAS DESIGN |
| PRESSURES ARE HIGHER. NEED THE CALCULATIONS TO COMPLY |
| WITH THE DESIGN PRESSURES AS REQUIRED BY SEC. |
| R301.2.1.4.3. |
| |
| ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 |
| CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDOING |
| TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON |
| EXPOUSRE "C". |
| |
| 2- SPECIFY HOW IS THE CONCRETE TILE GOING TO BE |
| INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.2.1.4.3. IF USING SCREWS, THEN |
| SPECIFY NUMBER OF SCREWS. IF USING FOAM, THEN PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3. SEE TILE |
| NOA FOR LISTED FOAMS. |
| |
| 3- A) DESCRIPTION ON PERMIT APPLICATION DOESN'T SPECIFY |
| SKYLIGHTS. SPECIFY/CLARIFY IF INSTALLING NEW SKYLIGHTS |
| OR REPLACING EXISTING SKYLIGHTS AND SPECIFY HOW MANY. |
| |
| B) SPECIFY HOW MUCH SQUARE FEET IS FOR CONCRETE TILE, |
| HOW MUCH SQUARE FEET IS FOR FLAT ROOF AND HOW MANY |
| SKYLIGHTS ARE TO BE INSTALLED TO VERIFY TOTAL VALUE. |
| SEC. 108.3 CITY AMENDMENTS. |
| |
| 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC. |
| VALUE TO INCLUDE ALL SCOPE OF WORK INCLUDING CONCRETE |
| TILE ROOF, FLAT ROOF AND SKYLIGHTS. |
| |