Plan Review Details - Permit 11120733
Plan Review Stops For Permit 11120733
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-01-05 Cont ID  
Sent By jgomez Date 2012-01-05 Time 14:27 Rev Time 0.00
Received By jgomez Date 2012-01-05 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-05 Cont ID  
Sent By jgomez Date 2012-01-05 Time 12:00 Rev Time 0.00
Received By jgomez Date 2012-01-05 Time 11:49 Sent To  
Notes
2012-01-05 13:21:36RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE W/ 2009 REVISIONS.
  
  
 1- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA 08-0410.09 SUBMITTED. PAGE 35 OF NOA SUBMITTED
 IS GOOD FOR 60PSF. CORNER AND PERIMETER AREAS DESIGN
 PRESSURES ARE HIGHER. NEED THE CALCULATIONS TO COMPLY
 WITH THE DESIGN PRESSURES AS REQUIRED BY SEC.
 R301.2.1.4.3.
  
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDOING
 TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON
 EXPOUSRE "C".
  
 2- SPECIFY HOW IS THE CONCRETE TILE GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3. IF USING SCREWS, THEN
 SPECIFY NUMBER OF SCREWS. IF USING FOAM, THEN PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3. SEE TILE
 NOA FOR LISTED FOAMS.
  
 3- A) DESCRIPTION ON PERMIT APPLICATION DOESN'T SPECIFY
 SKYLIGHTS. SPECIFY/CLARIFY IF INSTALLING NEW SKYLIGHTS
 OR REPLACING EXISTING SKYLIGHTS AND SPECIFY HOW MANY.
  
 B) SPECIFY HOW MUCH SQUARE FEET IS FOR CONCRETE TILE,
 HOW MUCH SQUARE FEET IS FOR FLAT ROOF AND HOW MANY
 SKYLIGHTS ARE TO BE INSTALLED TO VERIFY TOTAL VALUE.
 SEC. 108.3 CITY AMENDMENTS.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC.
 VALUE TO INCLUDE ALL SCOPE OF WORK INCLUDING CONCRETE
 TILE ROOF, FLAT ROOF AND SKYLIGHTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-05 Cont ID  
Sent By jgomez Date 2012-01-05 Time 14:27 Rev Time 0.00
Received By jgomez Date 2012-01-05 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-05 Cont ID  
Sent By jgomez Date 2012-01-05 Time 11:49 Rev Time 0.00
Received By jgomez Date 2012-01-05 Time 11:49 Sent To  
Notes
***NONE***