Plan Review Details - Permit 11120544
Plan Review Stops For Permit 11120544
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2012-01-11 Cont ID  
Sent By jnguyen Date 2012-01-11 Time 12:01 Rev Time 0.00
Received By jnguyen Date 2012-01-09 Time 16:09 Sent To  
Notes
2012-01-11 12:01:11THE PRIMARY ADDRESS ON PCN# 74434321010050011 IS 105 S
 NARCISSUS AVE (DISPLAYED ONLY ON PAPA), BUT THERE WAS
 ALSO AN EXISTING SECONDARY ADDRESS OF 200 CLEMATIS ST
 (REFERENCED TO THE PRIOR RESTAURANT, CAFE
 MEDITERRANEO). I CHECKED THE SITE PLANS & ALSO WENT OUT
 TO INSPECT THE PHYSICAL LOCATION & CONFIRMED THAT THE
 MAIN ENTRANCE WAS INDEED OFF CLEMATIS ST (INSTEAD OF S
 NARCISSUS AVE). 200 CLEMATIS ST IS THE PROPER ADDRESS
 TO REFERENCE. THEREFORE, I HAVE RETURNED THE SITE PLANS
 & ASSOCIATED DOCUMENTS BACK TO THE C4 BOX.
  
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 PUBLIC UTILITIES DEPARTMENT
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-03-12 Cont ID  
Sent By jwitmer Date 2012-03-12 Time 16:29 Rev Time 1.50
Received By jwitmer Date 2012-03-12 Time 15:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-13 Cont ID  
Sent By jwitmer Date 2012-02-13 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2012-02-10 Time 16:00 Sent To  
Notes
2012-02-13 12:19:34BUILDING PLAN REVIEW
 PERMIT: 11120544
 ADD: 200 CLEMATIS ST
 CONT: TBD
 TEL: (269)599-1341
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 FEB. 13/2012
 2ND REVIEW
 ACTION: DENIED
  
 1) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS
 ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) COMPLIED. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
  
 5) COMPLIED. SHEET A1 THE BUILDING CODE ANYLSIS
 INDICATES THE WEST WALL BEING A 2 HR RATED WALL. THIS
 WALL SHOULD BE A 3 HOUR RATED WALL, 2007/09 FBC-B TABLE
 601, TABLE 602, < THAN 5'-0" FROM THE PROPERTY LINE.
  
 6) COMPLIED.
  
 7) COMPLIED. BASEMENT LEVEL. SHEET A1.1 2HR RATED EXIT
 STAIR WITH A 1 HOUR RATED SHAFT WALL CONSTRUCTION UNDER
 THE STAIR, PLEASE PROVIDE A DETAIL AND WHAT WILL BE THE
 USE OF THIS NEW AREA?
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) 2ND REQUEST, BASEMENT LEVEL. SHEET A1.1 INDICATES
 NEW GANGED RESTROOM STALLS FOR BOTH THE MENS AND LADIES
 RESTROOMS. 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. THIS IS CONSIDERED NEW WORK AND THE
 ACCESSIBLE TOILET STALL FOR NEW CONSTRUCTION IS TO BE
 DESIGNED TO THE 2007/09 FBC-B 11-4 .17.3 & FIGURE 30E.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW
 CONSTRUCTION (1) STANDARD ACCESSIBLE RESTROOM STALLS
 SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT.
  
 11) COMPLIED.
  
 12) SECOND REQUEST. SHEET A2, A5 & S-1 SHOW INFILL OF
 AN EXTERIOR BLOCK WALL. S1 ALSO INDICATES A CUT SECTION
 C/S3 NO SUCH DETAIL PROVIDING INFORMATION ON THE
 VERTICAL AND HORIZONTAL REINFORCEMENT FOR THE INFILL
 BLOCK. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 13) COMPLIED.
  
 14)COMPLIED.
  
 15) COMPLIED.
  
 16)COMPLIED.
  
 17) SEMI -COMPLIED. A6.1 & S-2 THE ELEVATOR DESIGN DOES
 NOT INDICATE WHAT TYPE OF SYSTEM IS TO DESIGNED AT THIS
 POINT, NOTE DIMINSION FOR SUMP SIZE NOT PROIDED, 3004.4
 NOR DOES THE PLANS INDICATE COMPLIANCE WITH 3007.1
 ELEVATOR ACCESSIBLITY REQUIREMENTS FOR THE PHYSICALLY
 HANDICAPPED. FBC-B 3007. IF NOT USING WHEEL CHAIR LIFT.
 2ND REVIEW COMMENT- THE REQUIREMENT FOR THE SUMP IS
 LOCATED WITHIN THE BLDG CODE, THE SIZING OF THE SUMP
 PIT IS LOCATED WITH IN THE PLUMBING CODE REQUIRING A 18
 INCH WIDE BY 24 INCH DEEP PIT. PLEASE BE AWARE THAT IF
 A HYDROLIC ELEVATOR IS INSTALLED, IF THERE IS A
 HYDROLIC LEAK IT MAY NOT GO TO SANITARY, PLEASE SEE
 PLUMBING COMMENTS.
  
 18) COMPLIED.
  
 19)COMPLIED.
  
 20) COMPLIED.
  
 NEW COMMENTS
  
 21) IN REGARDS TO THE 2ND FLOOR EXITING. 2007/09 EXIST
 BLDG CODE 601.2 ALLOWS FOR AN EXISTING BUILDING TO BE
 ALTERED OR PORTIONS THERE OF AND SHALL NOT BE ALTERED
 SUCH THAT THE BUILDING BECOMES LESS SAFE. PLEASE
 PROVIDE WHAT THTE OCCUPANT LOAD WOULD HAVE BEEN BEFORE
 THE REMOVAL OF THE 2ND STORY RESTROOMS. WITH THE
 RECONFIGURATION OF THE 2ND FLOOR IT WILL NEED TO BE
 EQUAL TO OR LESS THAN THE OCCUPANT LOAD FOR THE 2ND
 FLOOR BEFORE THE REMODELING TOOK PLACE.THE EXISTING
 BLDG CODE 705.3 NUMBER OF EXITS . THE NUMBER OF EXITS
 SHALL BE IN ACCORDANCE WITH THE APPROPRIATE SECTIONS OF
 THE FLORIDA FIRE PREVENTION CODE.
  
 22) THE NEW STAIRWWELL TO THE BASEMENT IS CONSIDERED
 NEW WORK AND WILL NEED TO MEET THE REQUIREMENTS FOR NEW
 CONSTRUCTION. 2007 EXISTING BUILDING CODE LEVEL II
 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING. 2007/09
 FBC-B 1020.1 VERTICAL SHAFT ENCLOSURES.
  
 23) OUTSWING KAWNEER STORE FRONT DOORS NOA 09-0129.01
 GLAZING TYPE NOT PROVIDED TYPE A & B DO NOT MEET
 PRESSURES CLASS C & D DO MEET PRESSURERS? PLEASE
 PROVIDE ADDITIONAL INFORMATION AS TO WHICH GLAZING
 SYSTEM TO BE INSTALLED.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-03 Cont ID  
Sent By jwitmer Date 2012-01-03 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2012-01-04 Time 11:09 Sent To  
Notes
2012-01-03 16:56:31BUILDING PLAN REVIEW
 PERMIT: 11120544
 ADD: 200 CLEMATIS ST
 CONT: TBD
 TEL: (269)599-1341
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS
 ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
  
 5) SHEET A1 THE BUILDING CODE ANYLSIS INDICATES THE
 WEST WALL BEING A 2 HR RATED WALL. THIS WALL SHOULD BE
 A 3 HOUR RATED WALL, 2007/09 FBC-B TABLE 601, TABLE
 602, < THAN 5'-0" FROM THE PROPERTY LINE.
  
 6) BASEMENT LEVEL. SHEET A1.1INDICATES NEW WALL
 CONSTRUCTION IN THE AREAS OF ROOM # 107 ELEVATOR
 EQUIPMENT ROOM & ROOM # 106 AN EXISTING MECHANICAL &
 ELECTRIC ROOM. THE DEMOLITION PLAN D1.1 DOES NOT
 INDICATE ANY REMOVAL OF ANY WALLS IN THIS AREA, ONLY
 THE REMOVAL OF A RAISED PLATFORM. THE FBC-B 1020.1.1
 OPENINGS AND PENETRATIONS INTO VERTICAL EXITS STAIRS,
 THE OBJECTIVE IS TO MINIMIZE THE POSSIBILITY OF FIRE
 SPREADING INTO THE EXIT ENCLOSURE AND ENDANGERING THE
 OCCUPANTS OR EVEN PREVENTING THE USE OF THE EXIT AT A
 POINT OF TIME WHEN IT IS NEEDED THE MOST. THE CODE
 COMMENTARY LIST SPACES THAT ARE NOT NORMALLY OCCUPIED
 INCLUDE, BUT NOT LIMITED TO,
 TOILET ROOMS, ELECTRICAL/ MECHANICAL ROOMS AND
 JANITORIAL CLOSETS.
  
 7) BASEMENT LEVEL. SHEET A1.1 2HR RATED EXIT STAIR WITH
 A 1 HOUR RATED SHAFT WALL CONSTRUCTION UNDER THE STAIR,
 PLEASE PROVIDE A DETAIL AND WHAT WILL BE THE USE OF
 THIS NEW AREA?
  
 8) BASEMENT LEVEL. SHEET A1.1 THE PLANS INDICATE A TWO
 HOUR RATED STAIRWAY WITH THE NEW WALLS BEING A 1 HOUR
 CONSTRUCTION, THIS STAIRWAY IS LESS THAN 4 STORIES ONLY
 REQUIRING A 1 HOUR ENCLOSURE. WITHIN THIS STAIRWAY THE
 PLANS INDICATE THE USE OF A AREA OF RESCUE ASSISTANCE,
 THE PLANS DO NOT PROVIDE THE WIDTH OF THE EXISTING
 STAIR, NOR IF THERE IS A CENTER HANDRAIL EXISTING IN
 THIS STAIR. WHEN ADDING A AREA OF RESCUE ASSISTANCE
 PLEASE BE AWARE A MINUMUM CLEAR WIDTH OF 48 INCHES
 BETWEEN HANDRAILS.
 2007/09 FBC-B 11-4.3.11.3.
  
 9) BASEMENT LEVEL. SHEET A1 AND SHEET A1.1 BOTH
 INDICATE NEW WALK IN COOLERS AND FREEZERS, WILL REQUIRE
 SEPERATE PERMITS AND REVIEWS, AT TIME OF APPLICATION
 PLEASE PROVIDE DOCUMENTATION OF FBC-B 2603.4.1.2.
  
 10) BASEMENT LEVEL. SHEET A1.1 INDICATES NEW GANGED
 RESTROOM STALLS FOR BOTH THE MENS AND LADIES RESTROOMS.
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW
 CONSTRUCTION (1) STANDARD ACCESSIBLE RESTROOM STALLS
 SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT.
  
 11) SHEET A2 INDICATES THE USE OF LULA LIFTS OR WHEEL
 CHAIR PLATFORM LIFTS, PLEASE PROVIDE COMPLIANCE WITH
 11-4.11.2 ASME A17.1 .
  
 12) SHEET A2, A5 & S-1 SHOW INFILL OF AN EXTERIOR BLOCK
 WALL. S1 ALSO INDICATES A CUT SECTION C/S3 NO SUCH
 DETAIL PROVIDING INFORMATION ON THE VERTICAL AND
 HORIZONTAL REINFORCEMENT FOR THE INFILL BLOCK. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 13) A4.1 THE 2ND FLOOR INDICATES WHAT APPEARS TO BE A
 TV WALL MOUNTED SCREEN THAT BLOCKS THE EGRESS DOOR.
 11-4.4 PROTRUDING OBJECTS.
  
 14) SHEET A6 & A6.1 DECRATIVE WALL SCONCES IF ON AN
 ACCESSIBLE PATH PLEASE PROVIDE COMPLIANCE WWITH 11-4.4
 PROTRUDING OBJECTS, THIS WILL ALSO BE REVIEWED WITHIN
 THE STAIRS.
  
 15) SHEET A6 FURNISHINGS F4A BACK AND SEATS OF SEATS
 AND F41 CURTAINS, PLEASE PROVIDE THE FLAME SPREAD AND
 SMOKE DEVELOPMENT FOR THESE FINISHES. 2007/09
 FBC-B 803.1 & 803.5.
  
 16) A6.1 PLEASE PROVIDE THE CORRECT RISE AND RUN FOR
 THE NEW STAIRS, RISE IS SHOWN AS 11 1/2 INCHES.
 FBC-B1009.3.
  
 17) A6.1 & S-2 THE ELEVATOR DESIGN DOES NOT INDICATE
 WHAT TYPE OF SYSSTEM IS TO DESIGNED AT THIS POINT, NOTE
 DIMINSION FOR SUMP SIZE NOT PROIDED, 3004.4 NOR DOES
 THE PLANS INDICATE COMPLIANCE WITH 3007.1 ELEVATOR
 ACCESSIBLITY REQUIREMENTS FOR THE PHYSICALLY
 HANDICAPPED. FBC-B 3007. IF NOT USING WHEEL CHAIR LIFT.
  
 18) A7 DETAAIL A713 ACCESSBILE LAV, 11-19.2 HEIGHT MAX
 34 INCHES. PLEASE SEE DIMENSIONS TOTALING TO 35 INCHES
 VS 34 INCHES.
  
 19) SHEET A13 INDICATES THE USE OF WOOD BUCKS FOR
 WINDOW AAND DOOR ATTACHMENT, THE PRODUCT APPROVALS DO
 NOT PROVIDE A FASTENING SCHEDULE FOR WOOD SUB-BUCKS
 FBC 1609 . PLANS ARE NOT CLEAR IF THE USE OF WOOD BUCKS
 WILL BE ATTACHED TO THE STEEL TS 10"X6" HEADER? THE
 PRODUCT APPROVALS MAY NOT PROVIDE FASTENING OF THE
 PRODUCT TO THE 5/16 INCH TUBE STEEL, PLEASE PROVIDE
 TYPE OF FASTENERS FOR THIS APPLICATION. COMPONENTS &
 CLADDING.
  
 20) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS
 PROVIDE WIND DESIGN CRITERIA, SINCE THIS BUILDING IS
 OVER 60'-0" IN HEIGHT ASCE 7 AND EXPOSURE "C" WILL NEED
 TO BE CONSIDERED FOR THE DESIGN FACTORS. PLEASE PROVIDE
 THE POSITIVE ? NEGATIVE PRESSURES FOR THE INTERIOR AND
 END ZONES FOR THIS PROJECT. PRODUCT APPROVALS SUBMITTED
 CAN NOT BE CHECKED FOR COMPLIANCE UNTIL THE PRESSUES
 ARE PROVIDED AND TYPE OF GLAZING IS PROVIDED SINCE THE
 PRESSURES VARY WITH EACH GLAZING SYSTEM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-06 Cont ID  
Sent By rlecky Date 2012-02-06 Time 14:18 Rev Time 0.00
Received By rlecky Date 2012-02-06 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-09 Cont ID  
Sent By rlecky Date 2012-01-09 Time 11:25 Rev Time 0.00
Received By rlecky Date 2012-01-06 Time 16:17 Sent To  
Notes
2012-01-09 11:22:0311120544
 200 CLEMATIS STREET
 NEW RESTAURANT & BAR (BAR LOUIE)
  
 RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST BE
 GFCI PROTECTED. NEC 210.8
 A GFCI GENERAL PURPOSE RECEPTACLE MUST BE INSTALLED AT
 AN ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR
 CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC 210.63
 THE ELEVATOR EQUIPMENT ROOM REQUIRES A GFCI PROTECTED
 RECEPTACLE OUTLET. NEC 620.22, 620.85
 PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
 ALL DECORATIVE FIXTURES MUST BE LISTED BY AN APPROVED
 TESTING AGENCY. NEC 110.3
 PROVIDE A STRUCTURAL SUPPORT DETAIL FOR LIGHT FIXTURES
 AND LIGHTING ARRAYS WEIGHING MORE THAN 50 POUNDS. NEC
 410.36, 314.27
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOMS. NEC 110.22, 110.16, 701.9
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-03-09 Cont ID  
Sent By wjolin Date 2012-03-09 Time 11:33 Rev Time 0.00
Received By wjolin Date 2012-03-09 Time 10:27 Sent To  
Notes
2012-03-09 11:19:31200 CLEMATIS STREET
 PERMIT #11120544
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - THE USE OF THE EXISTING NON-CONFORMING
 OPEN STAIR BETWEEN THE 1ST AND 2ND FLOOR IS CONSIDERED
 TO BE APPROVED; HOWEVER, THE FOLLOWING FIRE PROTECTION
 FEATURES SHALL BE INSTALLED:
  
 PER NFPA 13, CLOSELY SPACED SPRINKLERS (6'-0" SPACING)
 AND 18" TALL NON-COMBUSTIBLE DRAFT CURTAINS WILL BE
 REQUIRED AROUND THE PERIMETER OF THE FLOOR/CEILING
 OPENING BETWEEN THE 1ST AND 2ND FLOOR.
  
 REPLACE ANY STANDARD-RESPONSE TYPE SPRINKLERS WITH
 QUICK-RESPONSE TYPE SPRINKLERS.
  
 PROVIDE A COMPLETE SMOKE DETECTION SYSTEM (EXCLUDING
 KITCHEN AREA), COMPLIANT WITH NFPA 72, FOR THE
 BASEMENT, 1ST FLOOR AND 2ND FLOOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-02-14 Cont ID  
Sent By wjolin Date 2012-02-14 Time 13:49 Rev Time 0.00
Received By wjolin Date 2012-02-14 Time 10:37 Sent To  
Notes
2012-02-14 11:28:02200 CLEMATIS STREET
 PERMIT #11120544
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 I. GENERAL
 REPEAT: ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS
 ARE REQUIRED FOR THE MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 REPEAT: NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT
 WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A
 SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE, AND
 MAIN ENTRANCE ONLY, IS PERMITTED TO HAVE AN INTERIOR
 KEYED DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE
 SIGN STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1
 INCH IN HEIGHT. NOTE: SHEET A13 - FOUR DOORS INDICATE
 THE USE OF A KEYED DEADBOLT LOCK IN ADDITION TO THE
 PANIC HARDWARE.
  
 REPEAT: PENETRATIONS INTO THE PROTECTED STAIR
 ENCLOSURES ARE LIMITED TO EQUIPMENT ESSENTIAL TO THE
 FUNCTION OF THE STAIR. SHEET P3 INDICATES WATER LINES
 RUNNING THROUGH THE EXISTING STAIR ENCLOSURE.
  
 NEW: ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER'S EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1.
  
 NEW: SHEET M1 & M2 - DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO THE FIRE ALARM SYSTEM AND GENERATE A
 GENERAL ALARM CONDITION.
  
 II. BASEMENT
 NEW: THE LIFE SAFETY CODE REQUIRES TWO BASEMENT EXITS
 EVEN THOUGH THE FLORIDA BUILDING CODE MAY ONLY REQUIRE
 ONE EXIT.
  
 REPEAT: BASEMENT STAIR #113 DOOR SHOULD HAVE A 1-HOUR
 FIRE RATING IN LIEU OF 45-MINUTES PER TABLE 8.3.4.2
 (NFPA 101).
  
 NEW: BASEMENT STAIR #113 DOOR INDICATES IT IS HELD OPEN
 BY MAGNETS AND RELEASED BY THE FIRE ALARM SYSTEM. SMOKE
 DETECTORS LOCATED PER NFPA 72 SHALL ALSO AUTOMATICALLY
 CLOSE THE DOOR PER SECTION7.2.1.8.2 (NFPA 101).
  
 NEW: PROVIDE A ONE-HOUR FIRE SEPARATION BETWEEN
 EXISTING STAIR AND ELEVATOR EQUIPMENT ROOM. (ORIGINAL:
 OPENINGS INTO A STAIR ENCLOSURE ARE LIMITED TO NORMALLY
 OCCUPIED SPACES; HOWEVER, SECTION 7.1.3.2.1[8][B] (NFPA
 101) PERMITS MECHANICAL ROOMS PROVIDED THE SPACE DOES
 NOT CONTAIN FUEL-FIRE EQUIPMENT OR STORAGE OF
 COMBUSTIBLES. NO EXEMPTION IS MADE FOR ELECTRICAL
 ROOMS.)
  
 REPEAT: FOR STAIR #113, THE ENTIRE AREA ON THE LEVEL OF
 DISCHARGE SHALL BE SEPARATED FROM AREAS BELOW BY A
 1-HOUR FIRE RESISTANCE RATING PER SECTION 7.7.2.6 (NFPA
 101).
  
 III. SECOND FLOOR
 THE REVISED FLOOR PLAN SENT IN THE EMAIL APPEARS TO BE
 AN ACCEPTABLE LAYOUT THAT SHOULD BE SUBMITTED FOR ALL
 PLAN REVIEWERS TO REVIEW.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-01-06 Cont ID  
Sent By wjolin Date 2012-01-06 Time 15:32 Rev Time 0.00
Received By wjolin Date 2012-01-05 Time 13:44 Sent To  
Notes
2012-01-05 14:14:31200 CLEMATIS STREET
 PERMIT #11120544
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 I. GENERAL
 IN ADDITION TO THE FLORIDA BUILDING CODE, THE FIRE
 PROTECTION AND LIFE SAFETY DESIGN SHALL CONFORM TO THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE (2009
 EDITION OF NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS).
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR THE MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE, AND MAIN ENTRANCE ONLY, IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE
 LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED
 LOCK.
  
 PENETRATIONS INTO THE PROTECTED STAIR ENCLOSURES ARE
 LIMITED TO EQUIPMENT ESSENTIAL TO THE FUNCTION OF THE
 STAIR. THE CURRENT MEP DRAWINGS SHOW DRAIN LINES, COLD
 WATER LINES, ELECTRICAL LINES ETC. THAT WILL NOT BE
 PERMITTED.
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 II. BASEMENT
 THE TWO BASEMENT STAIR DOORS SHOULD HAVE A 1-HOUR FIRE
 RATING IN LIEU OF 45-MINUTES PER TABLE 8.3.4.2 (NFPA
 101).
  
 OPENINGS INTO A STAIR ENCLOSURE ARE LIMITED TO NORMALLY
 OCCUPIED SPACES; HOWEVER, SECTION 7.1.3.2.1[8][B] (NFPA
 101) PERMITS MECHANICAL ROOMS PROVIDED THE SPACE DOES
 NOT CONTAIN FUEL-FIRE EQUIPMENT OR STORAGE OF
 COMBUSTIBLES. NO EXEMPTION IS MADE FOR ELECTRICAL
 ROOMS.
  
 FOR STAIR #113, THE ENTIRE AREA ON THE LEVEL OF
 DISCHARGE SHALL BE SEPARATED FROM AREAS BELOW BY A
 1-HOUR FIRE RESISTANCE RATING PER SECTION 7.7.2.6 (NFPA
 101).
  
 INDICATE THE SIGNAGE AND COMMUNCATION SYSTEM THAT WILL
 BE PROVIDED FOR THE AREA OF REFUGE.
  
 INDICATE THE REFRIGERANT AND THE NUMBER OF POUNDS
 ASSOCIATED WITH THE WALK-IN BEER COOLER.
  
 III. SECOND FLOOR
 THE SECOND FLOOR REQUIRES TWO FIRE-RATED EXIT
 ENCLOSURES. THE SECOND FLOOR IS TOO LARGE TO BE
 CONSIDERED A MEZZANINE WHEREBY AN OPEN EXIT ACCESS
 STAIR WOULD BE ACCEPTABLE. FOR STAIR #112, THE ENTIRE
 AREA ON THE LEVEL OF DISCHARGE SHALL BE SEPARATED FROM
 AREAS BELOW BY A 1-HOUR FIRE RESISTANCE RATING PER
 SECTION 7.7.2.6 (NFPA 101). INDICATE IF THE EXISTING
 STAIR (NIC) DISCHARGES TO THE EXTERIOR OR INTERIOR OF
 THE BUILDING.
  
 THE SOUTH WALL OF MAIN DINING #201 IS INDICATED AS A
 1-HOUR WALL. ALL THE OTHER WALLS AND FLOOR ARE RATED AT
 TWO-HOURS. INDICATE IF THE 1-HOUR WALL WILL BE UPGRADED
 TO A TWO-HOUR WALL.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-03-19 Cont ID  
Sent By hmoser Date 2012-03-19 Time 11:25 Rev Time 0.00
Received By hmoser Date 2012-02-29 Time 14:11 Sent To  
Notes
2012-02-29 14:11:573RD SUBMITTAL
 C--26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-28 Cont ID  
Sent By hmoser Date 2012-02-28 Time 13:59 Rev Time 0.00
Received By hmoser Date 2012-02-02 Time 17:42 Sent To  
Notes
2012-02-03 17:42:38SENT TO C26 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-20 Cont ID  
Sent By hmoser Date 2012-01-20 Time 14:05 Rev Time 0.00
Received By hmoser Date 2011-12-22 Time 11:12 Sent To  
Notes
2011-12-22 15:47:50PLANS WERE MOVED TO C--4, LM
2011-12-22 11:12:55INCOMING SENT TO C25. JW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-03-19 Cont ID  
Sent By hmoser Date 2012-03-19 Time 11:25 Rev Time 0.00
Received By hmoser Date 2012-03-19 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-02-28 Cont ID  
Sent By hmoser Date 2012-02-28 Time 13:48 Rev Time 0.00
Received By hmoser Date 2012-02-28 Time 10:51 Sent To  
Notes
2012-02-28 13:48:22PLANS DENIED
 1) MISSING FIRE SMOKE DAMPER FOR AHU # 1 IN DUCT SIZE
 20X10 AND 12X10 PAGE M2 OF THE PLANS.
 2) PROVIDE DUCT SIZE ON THE PLANS AHU # 1 PAGE M2
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-20 Cont ID  
Sent By hmoser Date 2012-01-20 Time 14:04 Rev Time 0.00
Received By hmoser Date 2012-01-18 Time 12:21 Sent To  
Notes
2012-01-20 14:04:44PLANS DENIED
 1) SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR
 HOOD AND COOLERS.
 2) PROVIDE FRESH AIR CALCULATION'S ON THE PLANS.
 3) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 A/C EQUIPMENT WITH THE PLANS.
 4) PROVIDE PRODUCT APPROVALS FOR OUTDOOR LOUVERS.
 5) REFER TO SECTION 606.2.1 SUPLY AIR AND SECTION 606.3
 INSTALLATION. 2007 FBC (M)
 6) REFER TO SECTION 606.4.1 SUPERVISION.2007 FBC (M)
 7) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M) .
 REFERRING TO PAGE A1.1
 ROOM'S 001 AND 005 ON THE PLANS.
 8) REFER TO NOTE # 10 ON PAGE M-2 THIS IS A TYPE ONE
 BUILDING CAN NOT USE PVC.
 9) PLEASE VERIFY THAT A/C UNIT # 6 IS IN STORAGE ROOM
 IN BASEMENT.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 NOMAD 5055 @WPB.ORG

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-03-05 Cont ID  
Sent By lwagner Date 2012-03-05 Time 13:26 Rev Time 0.00
Received By lwagner Date 2012-03-05 Time 12:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-02-15 Cont ID  
Sent By lwagner Date 2012-02-15 Time 10:58 Rev Time 0.00
Received By lwagner Date 2012-02-14 Time 15:27 Sent To  
Notes
2012-02-15 09:37:42 
 FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. NOT COMPLIED AT THIS TIME:
 THERE ARE NO PLUMBING FACILITIES FOR THE 2ND FLOOR
 WHICH IS MORE THAN ONE FLOOR LEVEL ABOVE THE BASEMENT.
 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES
 OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN
 COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET
 FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY
 ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH
 TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH
 FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET (152
 M).
  
 (IF THE RESTROOMS THAT ARE SHOWN ON THE EXITING PLAN -
 OPTION "B" ARE TO BE USED, PLEASE INCLUDE THE
 CALCULATIONS FOR THE OCCUPANT LOAD BASED ON THE SECOND
 FLOOR DINING AREA PLUS THE BUSINESS USE ON THAT FLOOR).
  
 2. OK
  
 3. BASEMENT LEVEL. SHEET A1.1 INDICATES
 NEW GANGED RESTROOM STALLS FOR BOTH THE MENS AND LADIES
 RESTROOMS. 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. THIS IS CONSIDERED NEW WORK AND THE
 ACCESSIBLE TOILET STALL FOR NEW CONSTRUCTION IS TO BE
 DESIGNED TO THE 2007/09 FBC-B 11-4 .17.3 & FIGURE 30E.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW
 CONSTRUCTION (1) :
  
 THE STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH
 LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] ...
  
 (FIGURE 30E SHOWS A CLEAR FLOOR SPACE OF 60" WIDE WITH
 THE LAVATORY OUTSIDE OF THAT SPACE. THE NOTES FOR
 FIGURE 30E ALSO STATE THAT THERE ARE MANY POSSIBLE
 LOCATIONS FOR THE LAVATORY WITHIN THE TOILET STALL).
  
 4. OK
 GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE PLANS,
 APPLICATION, AND REVIEWS ARE REQUIRED.
  
 5. OK
  
 NEW NOTE: SOME METHOD OF KEEPING OIL OUT OF THE
 SANITARY SEWER WILL BE REQUIRED FOR THE ELEVATOR SUMP
 PUMP. THIS COULD BE ACCOMPLISHED WITH AN APPROVED OIL
 SENSING SUMP CONTROL SYSTEM.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-01-18 Cont ID  
Sent By lwagner Date 2012-01-18 Time 09:16 Rev Time 0.00
Received By lwagner Date 2012-01-12 Time 09:41 Sent To  
Notes
2012-01-12 11:28:24 
 FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. THERE ARE NO PLUMBING FACILITIES FOR THE 2ND FLOOR
 WHICH IS MORE THAN ONE FLOOR LEVEL ABOVE THE BASEMENT.
 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES
 OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN
 COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET
 FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY
 ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH
 TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH
 FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET (152
 M).
  
 2. THE MENS ROOM IN THE BASEMENT LEVEL HAS MORE
 FIXTURES THAN THE WOMENS ROOM. WHILE THE RESTAURANT IS
 LICENSED UNDER F.S. 509, PLEASE SEE THE EXCEPTION FOR
 403.1.1 POTTY PARITY. THE SAME NUMBER OF WATER CLOSETS
 IS REQUIRED FOR WOMEN AS THE COMBINED W.C AND URINALS
 FOR MEN:
  
 403.1.1 POTTY PARITY. IN ASSEMBLY OCCUPANCIES,
 RESTROOMS WHICH ARE OPEN TO THE PUBLIC MUST HAVE A
 RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE
 COMBINED TOTAL OF WATER CLOSETS AND URINALS PROVIDED
 FOR MEN, UNLESS THESE ARE TWO OR FEWER SUCH FIXTURES
 FOR MEN, IN ACCORDANCE WITH ?553.86, FLORIDA STATUTES.
  
 EXCEPTION: THIS SECTION DOES NOT APPLY TO
 ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA
 STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING
 OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150
 PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME
 NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS FOR MEN.
  
 3. THE ADA STALLS WILL REQUIRE A LAV INSTALLED IN THE
 STALL PER 11-4.17 EXCEPTION (1) SEE FIGURE 30(E)
  
 4. GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE PLANS,
 APPLICATION, AND REVIEWS ARE REQUIRED.
  
 5. SHEET P5 - HOSE BIBBS REQUIRE SEPARATE SHUT OFF
 VALVES:
 606.2 LOCATION OF SHUTOFF VALVES.
 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-02-27 Cont ID  
Sent By aaponte Date 2012-02-27 Time 09:37 Rev Time 0.00
Received By aaponte Date 2012-02-27 Time 09:37 Sent To  
Notes
2012-02-27 09:37:48AWNINGS NOT INCLUDED IN THIS PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-01-13 Cont ID  
Sent By aaponte Date 2012-01-13 Time 09:17 Rev Time 0.00
Received By aaponte Date 2012-01-13 Time 09:17 Sent To  
Notes
2012-01-13 09:27:121. SOUTHERN MOST OPENNING CAN NOT BE BLOCKED. IF NEEDED
 PLESE USE A FALSE WINDOW TO MAINTAIN THE CONSISTENCY ON
 THE FIRST FLOOR DESIGN.
 2. PROPOSED AWNINGS ARE NOT PERMITTED. AWNINGS SHALL BE
 LOCATED BETWEEN, RATHER THAN ACROSS, SIGNIFICANT
 VERTICAL ARCHITECTURAL FEATURES THAT MAKE UP THE
 COMPOSITION OF THE FACADE. NO POLES LANDING ON THE
 SIDEWALK PERMITTED. A SEPARATE AWNING PERMIT SHALL BE
 REQUESTED.
 3. GLASS SHALL NOT BE TINTED.
 4. A SIDEWALK CAFE PERMIT WILL BE REQUIRED FOR THE
 OUTDOOR SEATING. APPLICATION SHALL BE DONE AFTER
 RENOVATIONS COMPLETED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.