Plan Review Details - Permit 11120529
Plan Review Stops For Permit 11120529
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-11 Cont ID  
Sent By jgomez Date 2012-06-11 Time 13:20 Rev Time 0.00
Received By jgomez Date 2012-06-11 Time 13:20 Sent To  
Notes
2012-06-11 13:21:44RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF CHAPTER 13 FLORIDA RESIDENTIAL CODE. NONE
 SUBMITED..
  
 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOWS AS SHOWN ON PLANS. NONE SUBMITED.
  
 B) EXTERIOR DOORS AS SHOWN ON PLANS. NONE SUBMITTED.
  
 C) FLAT ROOF ASSEMBLY. AND, PLEASE SPECIFY WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. ALSO,
 PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. NOTE: IF THE PRODUCT
 APPROVAL SUBMITTED REQUIRES SIGNED AND SEALED
 CALCULATIONS, THEN THOSE CALCULATIONS NEED TO BE SIGNED
 AND SEALED. NONE SUBMITTED.
  
 D) CONCRETE TILE FOR NEW ADDITION. AND, POLYFOAM
 PRODUCT APPROVAL LISTED ON THE TILE PRODUCT APPROVAL,
 IF USING ADHESIVE. OTHERWISE, SPECIFY HOW ARE THE TILES
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.2.1.4.3. NONE SUBMITTED.
  
 E) HURRICANE SHUTTERS IF THE DOORS AND WINDOWS PRODUCT
 APPROVALS SUBMITTED DON'T HAVE IMPACT GLASS. AND,
 PROVIDE A COMPLETE SHUTTERS INSTALLATION SCHEDULE. NONE
 SUBMITTED.
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NONE SUBMITTED. SUBMITT ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE CONNECTOR.
 THIS APPLIES TO STRUCTURAL CONNECTORS ONLY.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- THERE ARE NEW PLANS SUBMITTED BY NEW ENGINEER AND
 REFERENCING THE 2010 FBC. PERMIT APPLICATION WAS
 SUBMITTED UNDER THE 2007 FBC. PLEASE REVISE PLANS AND
 REFERENCE THE 2007 FBC FOR THE DESIGN CRITERIA.
  
 5- ROOF FRAMING PLAN SUBMITTED SHOWS NEW RAFTERS
 CONSTRUCTION, NOT PREFABRICATED ROOF TRUSSES. PROVIDE
 COMPLETE FRAMING DETAILS SHOWING ATTACHMENT OF RAFTERS
 TO THE RIDGE AND HIP BEAMS. ATTACHMENT OF THE NEW (2)
 2X10 WOOD BEAM AT THE ENDS. SEC. 106.1.1 CITY
 AMENDMENTS TO FBC.
  
 6- SPECIFY THE CALCULATED DESIGN PRESSURES FOR THE NEW
 EXTERIOR DOOR AS REQUIRED BY SEC. R301.2.1.4.3 FLORIDA
 RESIDENTIAL CODE.
  
 7- SPECIFY EGRESS FROM THE EXISTING BEDROOM AS REQUIRED
 BY SEC. R310. SPECIFY TYPE AND SIZE OF EGRESS WINDOWS
 SHOWN ON THE CORNER.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE THE VALUE TO INCLUDE ALL MATERIALS, LABOR,
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS.
  
 9- PLANS NEED TO SHOW NEW SHOWER DIMENSIONS TO VERIFY
 COMPLIANCE WITH THE MIN. DIMENSIONS REQUIRED BY SEC.
 P2708 OF THE 2007 FLORIDA RESIDENTIAL CODE.
  
 10- NEED TO SPECIFY SAFETY GLASS FOR WINDOW LOCATED IN
 SHOWER AREA IF THE WINDOW HAS NOT IMPACT GLASS. SEC.
 308.4(5).
  
 11- REVISE WALL SECTIONS:
 A) NEED TO SPECIFY 7/8" STUCCO THICKNESS AS REQUIRED BY
 TABLE R702.1(1).
 B) NEED TO SPECIFY TWO LAYERS OF WATER RESISTANT
 BARRIER AS REQUIRED BY SEC. R703.6.3.
 C) R-30 INSULATION DOESN'T FIT ON 2X6 RAFTERS.
 COORDINATE WITH THE ENERGY CALCULATIONS. SEC. 106.1.1
 CITY AMENDMENTS TO FBC.
 D) STUCCO CAN'T BE INSTALLED BELOW FINISHED GRADE. SEE
 SEC. R704.1 AND REVISE AS REQUIRED.
 E) CLEARLY SHOW LOCATION OF ATTIC VENTS ON THE ROOF
 FRAMING PLAN TO SHOW COMPLIANCE WITH SEC. R806.1 TO
 SHOW CROSS VENTILATION. AND, SHOW THE INSULATION
 CLEARANCE REQUIRED BY SEC. R806.3 SINCE ROOF SLOPE IS
 VERY LOW.
  
 12- CONNECTOR SCHEDULE ON SHEET A: CLARIFY WHERE ARE
 THE UPLIFT LOADS OF 985# SPECIFIED FOR THE H8 CONNECTOR
 TAKEN FROM. PROVIDE ENGINEERED CALCULATIONS. SEC.
 106.1.2 CITY AMENDMENTS.
  
 13- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-19 Cont ID  
Sent By jgomez Date 2012-01-19 Time 09:06 Rev Time 0.00
Received By jgomez Date 2012-01-18 Time 15:30 Sent To  
Notes
2012-01-19 09:17:15RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES
 ARE DUE. THEN, BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF CHAPTER 13 FLORIDA RESIDENTIAL CODE.
  
 3- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOWS AS SHOWN ON PLANS.
  
 B) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 C) FLAT ROOF ASSEMBLY. AND, PLEASE SPECIFY WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. ALSO,
 PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. NOTE: IF THE PRODUCT
 APPROVAL SUBMITTED REQUIRES SIGNED AND SEALED
 CALCULATIONS, THEN THOSE CALCULATIONS NEED TO BE SIGNED
 AND SEALED.
  
 D) HURRICANE SHUTTERS IF THE DOORS AND WINDOWS PRODUCT
 APPROVALS SUBMITTED DON'T HAVE IMPACT GLASS. AND,
 PROVIDE A COMPLETE SHUTTERS INSTALLATION SCHEDULE.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
  
 4- PROVIDE COMPLETE ROOF FRAMING PLAN. SHOW ALL FRAMING
 MEMBERS SIZES AND CONNECTORS. SPECIFY ATTACHMENT TO
 EXISTING ROOF. SPECIFY ROOF SLOPE. ETC. SEC. 106.1.1
 CITY AMENDMENTS TO FBC.
  
 5- SPECIFY THE CALCULATED DESIGN PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS AS REQUIRED BY SEC.
 R301.2.1.4.3 FLORIDA RESIDENTIAL CODE.
  
 6- SPECIFY EGRESS FROM THE EXISTING BEDROOM AS REQUIRED
 BY SEC. R310.
  
 7- SPECIFY SMOKE ALARMS AS REQUIRED BY SEC. R313.
  
 8- PROVIDE STRUCTURAL BUCK DETAILS FOR EXTERIOR DOORS
 AND WINDOWS AS REQUIRED BY SEC. R613.6.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE THE VALUE TO INCLUDE ALL MATERIALS, LABOR
 AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 108.3
 CITY AMENDMENTS.
  
 10- SHEET 1 OF 3 SUBMITTED:
 A) INFORMATION ON FLOOR PLAN SUBMITTED IS NOT CLEAR.
 (1) STEEL REINFORCING SPECIFICATIONS FOR CORNER COLUMNS
 ARE NOT CLEAR AND DON'T MATCH INFORMATION SHOWN ON THE
 FLOOR PLAN. (2) WHAT'S "NEW FRAME WALL LEADING TO BACK
 OF HOUSE" NOTE MEANS. IS THIS FRAME ADDITION OR
 CONCRETE BLOCK?. COORDINATE WITH WALL SECTION ON SHEET
 3 OF 3. (3) INFORMATION FOR NEW HALLWAY AND EXISTING
 UTILITY IS NOT CLEAR. DRAWING DON'T SHOW THE WALLS AND
 FRAMING AROUND DOORS IS NOT CLEAR. (4) SPECIFY VERTICAL
 REINFORCEMENT AT THE ENDS OF DOORS AND WINDOWS
 OPENINGS.
  
 B) REVISE GENERAL NOTES. (1) THERE IS NOT SBC. REFER TO
 THE 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
 (2) THERE IS NOT TABLE 1606.28. SEE 2007 FLORIDA
 RESIDENTIAL L CODE AND SPECIFY ALL THE DESIGN LOADS AS
 REQUIRED BY SEC. R301 AND TABLE R301.5. SPECIFY ALL THE
 LIVE AND DEAD LOADS, BUILDING EXPOSURE AND THE WIND
 SPEED.
  
 C) SPECIFY SIZE OF EXTERIOR DOORS AND WINDOWS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSRUES OS SEC.
 R301.2.1.4.3.
  
 11- SHEET 3 OF 3:
 A) REVISE WALL SECTIONS: (1) SPECIFY ALL STRUCTURAL
 CONNECTORS. SEC. 106.1.2 CITY AMENDMENTS. (2) PROVIDE
 ENGINEERING SHOWING REINFORCING FOR THE EXISTING ROOF
 TRUSSES TO BE CUT. SEC. 106.1.2 CITY AMENDMENTS. (3)
 COORDINATE VERTICAL REINFORCEMENT SHOWN ON THE TYPICAL
 WALL SECTION WITH REVISED INFORMATION ON PLANS.
 COORDINATE WITH ITEM #10(A) ABOVE.
  
 B) CLARIFY PLYWOOD NAILING NOTES. ARE THESE NOTES FOR
 ROOF SHEATHING OR WALL SHEATHING. ROOF SHEATHING
 REQUIRES MIN. 8D RING SHANK NAILS. SEE SEC. R803.2.3.1.
 AND ROOF ZONE #3 REQUIRES NAIL SPACING AT 4"O.C.
  
 C) REVISE SPECIFICATIONS FOR EXISTING ROOF TILE. 30#
 UNDERLAYMENT ALONE DOESN'T COMPLY WITH SEC. R905.3.3.
 ALSO, CLARIFY IF PERMIT INCLUDES RE-ROOFING EXISTING
 HOUSE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-05-29 Cont ID  
Sent By rlecky Date 2012-05-29 Time 11:04 Rev Time 0.00
Received By rlecky Date 2012-05-29 Time 10:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-19 Cont ID  
Sent By rlecky Date 2012-01-19 Time 16:47 Rev Time 0.00
Received By rlecky Date 2012-01-19 Time 16:22 Sent To  
Notes
2012-01-19 16:47:1611120529
 710 43RD ST.
 RESIDENTIAL BATH ADDITION
  
 SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED.
 PLEASE PROVIDE THE FOLLOWING:
  
 INDICATE THE SIZE AND LOCATION OF THE EXISTING
 ELECTRICAL PANEL. PROVIDE A PANEL SCHEDULE AND LOAD
 CALCULATION. SHOW THE SERVICE LOCATION, FEEDER SIZE AND
 EXISTING MAIN BREAKER. IF THIS IS A NEW SERVICE
 ADDITIONAL INFORMATION IS NEEDED. NEC 215.5
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH CIRCUIT.
 NEC 210.11 (C) (3)
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-12 Cont ID  
Sent By jgomez Date 2012-06-12 Time 10:32 Rev Time 0.00
Received By jgomez Date 2012-05-29 Time 10:47 Sent To  
Notes
2012-05-29 11:07:42R06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-19 Cont ID  
Sent By rlecky Date 2012-01-19 Time 16:48 Rev Time 0.00
Received By rlecky Date 2011-12-22 Time 08:38 Sent To  
Notes
2011-12-22 08:39:57INCOMING SENT TO R-6. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-06-12 Cont ID  
Sent By jgomez Date 2012-06-12 Time 10:16 Rev Time 0.00
Received By jgomez Date 2012-06-12 Time 10:16 Sent To  
Notes
2012-06-12 10:18:05AFTER PLANS ARE REVISED, PLEASE BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES
 ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-06-12 Cont ID  
Sent By jgomez Date 2012-01-19 Time 09:21 Rev Time 0.00
Received By jgomez Date 2012-01-19 Time 09:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-12 Cont ID  
Sent By jgomez Date 2012-06-12 Time 10:29 Rev Time 0.00
Received By jgomez Date 2012-06-12 Time 10:29 Sent To  
Notes
2012-06-12 10:30:54REVIEW FOR BATHROOMS MECHANICAL VENTILATION ONLY. NO
 A/C INFORMATION WAS SUBMITTED FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-19 Cont ID  
Sent By jgomez Date 2012-01-19 Time 15:27 Rev Time 0.00
Received By jgomez Date 2012-01-19 Time 15:27 Sent To  
Notes
2012-01-19 15:34:30RESIDENTIAL ADDITION, MECHANICAL REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NO PLANS SUBMITTED, BUT OWNER BUILDER SIGNED OFF FOR
 MECHANICAL PERMIT. PLEASE CLARIFY SCOPE OF WORK TO BE
 DONE.
  
 2- BATHROOM WINDOW ON EXISTING BATHROOM WAS CLOSED TO
 ALLOW FOR NEW ADDITION. SPECIFY HOW GETTING THE
 MECHANICAL VENTILATION FOR THIS BATHROOM. SEC. M1507.
  
 3- SPECIFY SIZE OF WINDOW ON NEW BATHROOM TO VERIFY
 MECHANICAL VENTILATION SEC. M1507.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-12 Cont ID  
Sent By jgomez Date 2012-06-12 Time 10:32 Rev Time 0.00
Received By jgomez Date 2012-06-12 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-01-19 Cont ID  
Sent By jgomez Date 2012-01-19 Time 15:34 Rev Time 0.00
Received By jgomez Date 2012-01-19 Time 15:34 Sent To  
Notes
2012-01-19 15:40:57RESIDENTIAL ADDITION (R3) PLUMBING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLEASE PROVIDE CORRECT PLUMBING RISER DIAGRAM AS
 SPECIFIED ON PLUMBING NOTE #2. PLUMBING RISER DIAGRAM
 PROVIDED IS INCORRECT. LICENSED PLUMBING CONTRACTOR MAY
 DRAW PLUMBING RISER DIAGRAM. PROVIDE HIS/HER LICENSE #
 AND SIGN THE DIAGRAM. SEC. 106.3.5.4(9) OF CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status F Date 2012-06-06 Cont ID  
Sent By eschneid Date 2012-06-06 Time 11:08 Rev Time 0.50
Received By eschneid Date 2012-06-06 Time 11:08 Sent To  
Notes
2012-06-06 11:12:36FAILED
  
 1) REPEAT COMMENT - PLEASE PROVIDE TWO COPIES OF A
 RECENT SURVEY, LESS THAN ONE YEAR OLD, OF THE PROPERTY
 WHICH CLEARLY SHOWS THE SIDE AND REAR SETBACKS FOR THE
 HOUSE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-12-28 Cont ID  
Sent By eschneid Date 2011-12-28 Time 10:20 Rev Time 0.25
Received By eschneid Date 2011-12-28 Time 09:14 Sent To  
Notes
2011-12-28 10:21:42FAILED
  
 PLEASE PROVIDE A SURVEY OF THE PROPERTY WHICH CLEARLY
 SHOWS THE SIDE AND REAR SETBACKS FOR THE HOUSE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.