Plan Review Details - Permit 11120521
Plan Review Stops For Permit 11120521
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-09 Cont ID  
Sent By jgomez Date 2012-04-09 Time 10:29 Rev Time 0.00
Received By jgomez Date 2012-04-06 Time 14:31 Sent To  
Notes
2012-04-06 14:31:39TO JG

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-06 Cont ID  
Sent By jgomez Date 2012-01-06 Time 16:52 Rev Time 0.00
Received By jgomez Date 2011-12-20 Time 08:33 Sent To  
Notes
2011-12-21 08:34:13SENT TO JULIO GOMEZ.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-04-09 Cont ID  
Sent By jgomez Date 2012-04-09 Time 10:29 Rev Time 0.00
Received By jgomez Date 2012-04-09 Time 10:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-06 Cont ID  
Sent By jgomez Date 2012-01-06 Time 16:37 Rev Time 0.00
Received By jgomez Date 2012-01-06 Time 16:36 Sent To  
Notes
2012-01-06 16:50:09REVISION MECHANICAL REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. N1107.AB.1. NO EQUIPMENT SIZING CALCULATIONS WERE
 SUBMITTED THIS TIME.
 ***NOTE: COORDINATE CALCULATIONS WITH THE ENERGY
 CALCULATIONS AND EQUIPMENT LISTED ON THE A/C PLANS.
  
 2- A/C CONTRACTOR TO PROVIDE HIS NAME AND SIGN THE A/C
 PLANS. BUILDING OFFICIAL ALLOWS A/C PLANS DRAWN BY THE
 A/C CONTRACTOR WHEN THE NAME, SIGNATURE AND LICENSE
 NUMBER IS ON THE PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712