2011-12-21 08:17:13 | FBC 2007 FUEL GAS REVIEW #1 |
| DENIED: |
| |
| NOT ENOUGH INFORMATION FOR REVIEW. |
| GAS PERMIT APPLICATION REQUIREMENTS |
| EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL |
| BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING |
| IN THE CITY OF WEST PALM BEACH: |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| FBC-2007 FUEL GAS. |
| 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS |
| STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. |
| 3. TYPE OF GAS, (LP OR NATURAL). |
| 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ? |
| USE OF CAPACITY SECTION A.3.1(4) |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007 |
| FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| PSI. |
| 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER FBC-2007 FUEL GAS CODE |
| SEC. 502 THRU 505. |
| 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2007 FUEL GAS SEC. 402.2 |
| |