Plan Review Details - Permit 11120460
Plan Review Stops For Permit 11120460
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2012-01-26 Cont ID  
Sent By lwagner Date 2012-01-26 Time 09:09 Rev Time 0.00
Received By lwagner Date 2012-01-26 Time 09:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2011-12-21 Cont ID  
Sent By lwagner Date 2011-12-21 Time 08:17 Rev Time 0.00
Received By lwagner Date 2011-12-21 Time 08:10 Sent To  
Notes
2011-12-21 08:17:13FBC 2007 FUEL GAS REVIEW #1
 DENIED:
  
 NOT ENOUGH INFORMATION FOR REVIEW.
 GAS PERMIT APPLICATION REQUIREMENTS
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2007 FUEL GAS CODE
 SEC. 502 THRU 505.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2007 FUEL GAS SEC. 402.2
  
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO:
 CHIEF PLUMBING INSPECTOR (561) 805-6692
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-26 Cont ID  
Sent By lwagner Date 2012-01-26 Time 09:18 Rev Time 0.00
Received By lwagner Date 2012-01-26 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2011-12-21 Cont ID  
Sent By lwagner Date 2011-12-21 Time 08:17 Rev Time 0.00
Received By lwagner Date 2011-12-20 Time 10:25 Sent To  
Notes
2011-12-20 10:25:29TO PLUMBING < $5K