Plan Review Details - Permit 11120366
Plan Review Stops For Permit 11120366 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2012-03-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-03-05 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-03-05 |
Time |
11:57 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-01-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-01-09 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-01-09 |
Time |
16:02 |
Sent To |
|
|
Notes |
2012-01-09 16:05:22 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PROVIDE ENGINEERING WHICH SHOWS HOW PROPOSED | | GENERATOR WILL RESIST WIND LOADS, FBC1609. THE | | MANUFACTURER'S INTALLATION INSTRUCTIONS DO NOT INCLUDE | | A WIND DESING CRITERIA (140MPH, EXPOSURE C MINIMUM). | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2012-01-03 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2012-01-03 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2012-01-03 |
Time |
13:19 |
Sent To |
Z |
|
Notes |
2012-01-03 13:21:56 | APPROVED BY PHIL PETTY ON PLAN | 2012-01-03 13:20:41 | 702.7 SIGN REQUIRED |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2012-01-09 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-01-09 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-01-09 |
Time |
09:41 |
Sent To |
B |
|
Notes |
2012-01-09 10:25:27 | 5101 SOUTH DIXIE HIGHWAY | | PERMIT #11120366 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO***** | | | | GENERATOR SHALL BE LOCATED AT LEAST 5 FEET FROM | | ADJACENT BUILDINGS OR STRUCTURES. | | | | INDICATE IF THIS UNIT WILL BE FUELED BY NATURAL GAS OR | | LIQUIFIED PETROLEUM (LP). PROVIDE CONNECTION DETAIL. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-03-07 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2012-03-07 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2012-03-05 |
Time |
08:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-01-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-01-09 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2011-12-14 |
Time |
14:15 |
Sent To |
|
|
Notes |
2011-12-14 14:35:24 | IN ZONING BOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2012-03-07 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2012-03-07 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2012-03-07 |
Time |
08:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2011-12-29 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2011-12-29 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2011-12-29 |
Time |
15:28 |
Sent To |
E |
|
Notes |
2011-12-29 15:29:57 | 12/29/11- APPLICANT NEEDS TO PROVIDE INFORMAITON OF HOW | | PROPOSED GENERATOR WILL BE SCREENED.- AV | | | | ANGELLA VANN | | 561-822-1441 | | [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |