Plan Review Details - Permit 11120366
Plan Review Stops For Permit 11120366
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-05 Cont ID  
Sent By shill Date 2012-03-05 Time 11:57 Rev Time 0.00
Received By shill Date 2012-03-05 Time 11:57 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-09 Cont ID  
Sent By shill Date 2012-01-09 Time 16:02 Rev Time 0.00
Received By shill Date 2012-01-09 Time 16:02 Sent To  
Notes
2012-01-09 16:05:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE ENGINEERING WHICH SHOWS HOW PROPOSED
 GENERATOR WILL RESIST WIND LOADS, FBC1609. THE
 MANUFACTURER'S INTALLATION INSTRUCTIONS DO NOT INCLUDE
 A WIND DESING CRITERIA (140MPH, EXPOSURE C MINIMUM).
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-01-03 Cont ID  
Sent By lmartine Date 2012-01-03 Time 13:19 Rev Time 0.00
Received By lmartine Date 2012-01-03 Time 13:19 Sent To Z
Notes
2012-01-03 13:21:56APPROVED BY PHIL PETTY ON PLAN
2012-01-03 13:20:41702.7 SIGN REQUIRED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-01-09 Cont ID  
Sent By wjolin Date 2012-01-09 Time 10:25 Rev Time 0.00
Received By wjolin Date 2012-01-09 Time 09:41 Sent To B
Notes
2012-01-09 10:25:275101 SOUTH DIXIE HIGHWAY
 PERMIT #11120366
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 GENERATOR SHALL BE LOCATED AT LEAST 5 FEET FROM
 ADJACENT BUILDINGS OR STRUCTURES.
  
 INDICATE IF THIS UNIT WILL BE FUELED BY NATURAL GAS OR
 LIQUIFIED PETROLEUM (LP). PROVIDE CONNECTION DETAIL.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-07 Cont ID  
Sent By ajones Date 2012-03-07 Time 08:59 Rev Time 0.00
Received By ajones Date 2012-03-05 Time 08:31 Sent To  
Notes
2012-03-05 08:31:30SH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-09 Cont ID  
Sent By shill Date 2012-01-09 Time 16:05 Rev Time 0.00
Received By shill Date 2011-12-14 Time 14:15 Sent To  
Notes
2011-12-14 14:35:24IN ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-07 Cont ID  
Sent By ajones Date 2012-03-07 Time 08:59 Rev Time 0.00
Received By ajones Date 2012-03-07 Time 08:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-12-29 Cont ID  
Sent By ajones Date 2011-12-29 Time 15:28 Rev Time 0.00
Received By ajones Date 2011-12-29 Time 15:28 Sent To E
Notes
2011-12-29 15:29:5712/29/11- APPLICANT NEEDS TO PROVIDE INFORMAITON OF HOW
 PROPOSED GENERATOR WILL BE SCREENED.- AV
  
 ANGELLA VANN
 561-822-1441
 [email protected]