Plan Review Stops For Permit 11120277 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2011-12-27 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-12-27 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2011-12-27 |
Time |
11:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2011-12-16 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2011-12-16 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2011-12-16 |
Time |
13:11 |
Sent To |
E |
|
Notes |
2011-12-16 13:53:06 | 1507 BELVEDERE ROAD | | PERMIT #11120277 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | INDICATE DUCT SMOKE DETECTOR LOCATIONS. | | | | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND | | IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER | | LOCK FOR DEDICATED BRANCH CIRCUIT. | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2011-12-27 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-12-27 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2011-12-13 |
Time |
16:14 |
Sent To |
|
|
Notes |
2011-12-13 16:14:54 | SENT TO FIRE BOX |
|
|
|