2011-12-12 09:41:49 | PROVISO: | | | | THIS PERMIT IS LIMITED TO INTERIOR ELECTRIC PENDING THE | | ISSUANCE OF THE BUILDING PERMIT FOR INTERIOR | | IMPROVEMENTS (# 11110516) | | | | ALL MAIN ELECTRICAL DISCONNECTS MUST BE GROUPED IN ONE | | LOCATION (NEC 230.72) A REVISED ELECTRICAL SERVICE PLAN | | IS REQUIRED. | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|
|