Plan Review Details - Permit 11120166
Plan Review Stops For Permit 11120166
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-12-09 Cont ID  
Sent By rlecky Date 2011-12-09 Time 15:27 Rev Time 0.00
Received By rlecky Date 2011-12-09 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-12-08 Cont ID  
Sent By rlecky Date 2011-12-08 Time 17:15 Rev Time 0.00
Received By rlecky Date 2011-12-08 Time 16:12 Sent To  
Notes
2011-12-08 17:15:49PROVIDE AN ELECTRICAL WIRING LAYOUT SHOWING THE NEW
 ELECTRICAL OUTLETS PROVIDED. SPECIFICALLY THE PLAN DOES
 NOT INCLUDE THE ELECTRICAL OUTLETS SERVING THE BAR.
 RECEPTACLES WITHIN 6 FEET OF ALL SINKS MUST BE
 PROTECTED BY GFCI'S. NEC 215.5, 210.8
  
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING 711.1
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-09 Cont ID  
Sent By rlecky Date 2011-12-09 Time 15:27 Rev Time 0.00
Received By rlecky Date 2011-12-09 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-08 Cont ID  
Sent By rlecky Date 2011-12-08 Time 17:17 Rev Time 0.00
Received By rlecky Date 2011-12-08 Time 08:17 Sent To  
Notes
2011-12-08 08:17:52INCOMING TO R. LECKY DESK. JW