Plan Review Details - Permit 11120036
Plan Review Stops For Permit 11120036
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-12-13 Cont ID  
Sent By jgomez Date 2011-12-13 Time 16:08 Rev Time 0.00
Received By jgomez Date 2011-12-13 Time 16:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-12-09 Cont ID  
Sent By jgomez Date 2011-12-09 Time 08:35 Rev Time 0.00
Received By jgomez Date 2011-12-09 Time 08:29 Sent To  
Notes
2011-12-09 08:38:28RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- FLAT ROOF: NEW NOA WAS PROVIDED BUT THE REQUESTED
 RAS 117 CALCULATIONS WERE NOT SUBMITTED. PROVIDE RAS
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA SUBMITTED. NEED THE NAIL ENHANCING TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. WHEN
 DOING THE CALCULATIONS PLEASE TAKE INTO CONSIDERATION
 THAT ACCORDING TO THE 2009 REVISIONS THIS BUILDING IS
 LOCATED IN EXPOSURE "C". SEE SEC. R301.2.1.4.3.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-01 Cont ID  
Sent By jgomez Date 2011-12-01 Time 16:48 Rev Time 0.00
Received By jgomez Date 2011-12-01 Time 16:41 Sent To  
Notes
2011-12-01 16:49:14RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- FLAT ROOF:
 A) NOA 07-0730.03 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE WEBSITE
 DOWNLOAD CURRENT NOA AND PROVIDE 2 NEW COPIES.
  
 B) PLEASE CLARIFY WHICH APPROVED FLAT ROOF ASSEMBLY IS
 GOING TO BE INSTALLED. TWO DIFFERENT APPROVED
 ASSEMBLIES WERE SUBMITTED. ONE SHOWN ON PAGE 6 OF 18 IS
 FOR AN INSULATED ASSEMBLY. AND, THE OTHER ASSEMBLY
 SHOWN ON PAGE 17 OF 18 IS FOR A NON-INSULATED ASSEMBLY.
 PLEASE SELECT ONLY ONE ASSEMBLY TAKE INTO CONSIDERATION
 IF INSTALLING INSULATION AND TYPE OF FASTENINGS TO BE
 USED.
  
 C) PROVIDE RAS CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. NEED THE
 NAIL ENHANCING TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1.4.3. WHEN DOING THE CALCULATIONS PLEASE
 TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009
 REVISIONS THIS BUILDING IS LOCATED IN EXPOSURE "C". SEE
 SEC. R301.2.1.4.3.
  
 2- SHINGLES: NOA 07-1120.14 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE WEBSITE
 DOWNLOAD CURRENT NOA AND PROVIDE TWO NEW COPIES.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-12-13 Cont ID  
Sent By jgomez Date 2011-12-13 Time 16:08 Rev Time 0.00
Received By jgomez Date 2011-12-13 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-09 Cont ID  
Sent By jgomez Date 2011-12-09 Time 08:38 Rev Time 0.00
Received By jgomez Date 2011-12-09 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-01 Cont ID  
Sent By jgomez Date 2011-12-01 Time 16:42 Rev Time 0.00
Received By jgomez Date 2011-12-01 Time 16:42 Sent To  
Notes
***NONE***