Plan Review Details - Permit 11110700
Plan Review Stops For Permit 11110700
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-23 Cont ID  
Sent By rbrown Date 2014-04-23 Time 12:40 Rev Time 0.00
Received By rbrown Date 2014-04-23 Time 12:40 Sent To  
Notes
2014-04-23 12:52:35BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 FLORIDA BUILDIING CODE 2010, SECTION 1604.2 - THE G.C.
 LETTER, DATED 4/21/14, THAT WAS SUBMITTED TO CERTIFY
 THE SHUTTER TRACK INSTALLATION IS NOT ACCEPTABLE UNLESS
 THE SHUTTER TRACKS ARE FULLY SUPPORTED AS INTENDED BY
 THE SHUTTER PRODUCT APPROVAL. THE REOMOVAL OF THE
 BALCONY FLOOR TILE HAS LEFT A GAP UNDERNEATH THE
 SHUTTER TRACKS. THE FASTENERS WILL BE SUBJECTED TO
 CANTILEVER BENDING, AND THE SHUTTER TRACKS WILL BE
 SUBJECTED TO TORSION, THAT WERE NOT CONTEMPLATED DURING
 THE ENGINEERING AND TESTING PERFORMED IN SUPPORT OF THE
 THE SHUTTER PRODUCT APPROVAL. PLEASE PROVIDE GROUT OR
 ALTERNATIVE PACKING UNDER THE SHUTTER TRACKS, OR
 PROVIDE ENGINEERING TO SHOW THAT REPEATED REVERSAL
 (POSITIVE AND NEGATIVE) OF THE DESIGN WIND LOAD WILL
 NOT CAUSE FAILURE OF THE SHUTTER TRACK OR THE
 FASTENERS, OR SPALLING OF THE CONCRETE AROUND THE
 FASTENERS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-12-01 Cont ID  
Sent By shill Date 2011-12-01 Time 08:59 Rev Time 0.00
Received By shill Date 2011-12-01 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-01 Cont ID  
Sent By shill Date 2011-12-01 Time 08:59 Rev Time 0.00
Received By shill Date 2011-11-30 Time 14:13 Sent To  
Notes
2011-11-30 14:14:22INCOMING SENT TO S. HILL DESK. JW