Plan Review Details - Permit 11110627
Plan Review Stops For Permit 11110627
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-05-24 Cont ID  
Sent By rmcdouga Date 2012-05-24 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2012-05-23 Time 07:49 Sent To  
Notes
2012-05-24 16:03:39THE SCOPE OF WORK WAS CHANGED FROM THE DEMOLISION AND
 REPLACEMENT OF BALCONY AND STAIRS TO REPAIRING THE
 EXISTING STAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-04-13 Cont ID  
Sent By rmcdouga Date 2012-04-13 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2012-04-12 Time 07:21 Sent To  
Notes
2012-04-13 10:02:222007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE LIVE LOAD FOR THE BALCONY IS REQUIRED TO BE 100
 PSF BY FBC TABLE 1607.1 (5) & (16). PLEASE REVISE SHEET
 A1 AND VERIFY DECK DESIGN FOR 100 PSF LIVE LOAD.
  
 2) FBC 1009.4 REQUIRES STAIRWAY LANDINGS TO HAVE A
 MINIMUM DIMENSION MEASURED IN THE DIRECTION OF TRAVEL
 EQUAL TO THE WIDTH OF THE STAIRWAY. PLEASE CORRECT.
  
 3) SHOW COMPLIANCE WITH FBC 1013.2 HEIGHT. GUARDS SHALL
 FORM A PROTECTIVE BARRIER NOT LESS THAN 42 INCHES (1067
 MM) HIGH, MEASURED VERTICALLY ABOVE THE LEADING EDGE OF
 THE TREAD, ADJACENT WALKING SURFACE OR ADJACENT
 SEATBOARD.
 NOTE: FBC 1012.2 HEIGHT. HANDRAIL HEIGHT, MEASURED
 ABOVE STAIR TREAD NOSINGS, OR FINISH SURFACE OF RAMP
 SLOPE SHALL BE UNIFORM, NOT LESS THAN 34 INCHES (864
 MM) AND NOT MORE THAN 38 INCHES (965 MM). EXCEPTION:
 HANDRAILS FOR STAIRS NOT REQUIRED TO BE ACCESSIBLE THAT
 FORM PART OF A GUARDRAIL MAY BE 42 INCHES (1067 MM)
 HIGH. BECAUSE THESE STAIRS ARE NOT REQUIRED TO COMPLY
 WITH ACCESSIBILITY, THE STAIR HANDRAILS CAN BE THE TOP
 OF THE GUARDS AT A HEIGHT OF 42". HOWEVER THE 36" SHOWN
 ON THE PLANS IS NOT ALLOWED. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-09 Cont ID  
Sent By rmcdouga Date 2012-01-09 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2012-01-09 Time 10:27 Sent To  
Notes
2012-01-09 10:33:392007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE USE, OCCUPANCY TYPE, NUMBER OF UNITS AND
 OCCUPANT LOAD ON THE PLANS. FBC 302
  
 2) SPECIFY THE CONSTRUCTION TYPE OF THE BUILDING THAT
 THE STAIRS ARE SERVING ON THE PLANS. SEE FBC 602 AND
 1009.5.
  
 3) SPECIFY THE 2007 FLORIDA BUILDING CODE AND THE
 DESIGN PARAMETERS ON THE PLANS PER FBC 1603.1. SPECIFY
 THE FLOOR LIVE LOAD FOR THE STAIRS, LANDING AND
 BALCONY, AS WELL AS THE WIND DESIGN DATA.
  
 4) SHOW COMPLIANCE WITH 1604.1 FOR STRUCTURAL DESIGN
 AND A CONTINUOUS LOAD PATH.
  
 5) SUBMIT TWO COPIES OF A SURVEY THAT INDICATES THE
 DISTANCE TO OTHER STRUCTURES LOCATED ON THE PROPERTY
 AND TO THE PROPERTY LINES. SEE FBC 701.
  
 6) SPECIFY THE STAIRWAY WIDTH ON THE PLANS. SHOW
 COMPLIANCE WITH FBC 1009.1.
  
 7) PLEASE CLARIFY THE NUMBER OF STAIR STRINGERS ON THE
 PLANS. IT IS SPECIFIED AS 2 IN ONE PLACE AND 3 IN
 ANOTHER.
  
 8) SPECIFY THE STAIR TREAD AND RISER DIMENSIONS ON THE
 PLANS. SHOW COMPLIANCE WITH FBC 1009.3.
  
 9) SPECIFY THE NUMBER OF STEPS AND THE TOTAL VERTICAL
 RISE OF THE STAIRS. SEE FBC 1009.6 VERTICAL RISE.
  
 10) SPECIFY THE STAIR LANDING DIMENSIONS ON THE PLANS,
 SHOWING THAT THEY COMPLY WITH FBC 1009.4.
  
 11) SHOW COMPLIANCE WITH FBC 1013 FOR THE REQUIRED
 GUARDS AT THE BALCONY, LANDING AND STAIRS. SHOW
 COMPLIANCE FOR HEIGHT, OPENING LIMITATIONS AND
 STRENGTH.
  
 12) SHOW COMPLIANCE WITH FBC 1009.10 FOR THE REQUIRED
 HANDRAILS.
  
 13) SHOW COMPLIANCE WITH FBC 1012 FOR HEIGHT AND
 GRASPABILITY AND FBC 1607.7 FOR STRENGTH AND ATTACHMENT
 REQUIREMENTS.
  
 14) SHOW COMPLIANCE WITH FBC 1012.5 FOR HANDRAIL
 EXTENSIONS WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN
 FLIGHTS.
  
 15) IF REQUIRED TO BE ACCESSIBLE, HANDRAILS SHALL
 COMPLY WITH FBC 11-4.26.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2012-05-29 Cont ID  
Sent By wjolin Date 2012-05-29 Time 10:45 Rev Time 0.00
Received By wjolin Date 2012-05-29 Time 10:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-03-08 Cont ID  
Sent By wjolin Date 2012-03-08 Time 11:14 Rev Time 0.00
Received By wjolin Date 2012-03-08 Time 09:57 Sent To  
Notes
2012-03-08 11:08:451021 14TH STREET
 PERMIT #11110627
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TO ENSURE CONTINUOUS GRASPABILITY OF THE HANDRAIL, A
 MINIMUM GAP OF 1-1/2" NEEDS TO BE PROVIDED BETWEEN THE
 HANDRAIL AND THE 3" NEWEL POST DESIGNATED AS C2 ON THE
 PLANS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-12-28 Cont ID  
Sent By wjolin Date 2011-12-28 Time 11:22 Rev Time 0.00
Received By wjolin Date 2011-12-28 Time 10:35 Sent To  
Notes
2011-12-28 11:22:311021 14TH STREET
 PERMIT #11110627
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS DOES NOT MATCH THE
 ADDRESS PROVIDED ON THE PERMIT APPLICATION.
  
 INDICATE WHERE THIS STAIR WILL TERMINATE IN RELATION TO
 THE ADJACENT EXTERIOR STAIR.
  
 PROVIDE SCALABLE OR DIMENSIONED STAIR, HANDRAIL AND
 GUARD DETAILS.
  
 HANDRAILS AND GUARDRAILS ARE REQUIRED ON BOTH SIDES OF
 THE STAIR. HANDRAIL ENDS SHALL BE RETURNED TO THE WALL
 OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS.
  
 HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT
 LESS THAN 1.25-INCHES AND NOT MORE THAN 2-INCHES AND
 SHALL BE CONTINUOUSLY GRASPABLE.
  
 STAIRS SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD
 DEPTH OF 11-INCHES AND PREVENT THE ACCUMULATION OF
 WATER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-06-01 Cont ID  
Sent By rmcdouga Date 2012-06-01 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2012-04-17 Time 17:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-13 Cont ID  
Sent By rmcdouga Date 2012-04-13 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2012-03-05 Time 08:47 Sent To  
Notes
2012-03-05 08:48:19SENT TO B15 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-09 Cont ID  
Sent By rmcdouga Date 2012-01-09 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2012-01-09 Time 15:25 Sent To  
Notes
2011-11-30 14:16:22IN ZONING BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2012-05-01 Cont ID  
Sent By aaponte Date 2012-05-01 Time 10:36 Rev Time 0.00
Received By aaponte Date 2012-05-01 Time 10:36 Sent To  
Notes
2012-05-01 10:36:50ONLY REPAIRS TO EXISTING PORCH.

Review Stop Z ZONING
Rev No 2 Status F Date 2012-03-19 Cont ID  
Sent By aaponte Date 2012-03-19 Time 15:17 Rev Time 0.00
Received By aaponte Date 2012-03-19 Time 15:05 Sent To  
Notes
2012-03-19 15:24:59EXISTING COVERED PORCH AND STAIR ENCROACHES INTO THE
 REQUIRED FRONT SETBACK. IF DEMOLISHED NEW PORCH AND
 STAIR SHALL MEET MINIMUM FRONT SETBACK (25').
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439

Review Stop Z ZONING
Rev No 1 Status F Date 2011-12-14 Cont ID  
Sent By astelly Date 2011-12-14 Time 11:55 Rev Time 0.00
Received By astelly Date 2011-12-14 Time 11:55 Sent To  
Notes
2011-12-14 11:56:54AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 SCOPE OF WORK.