Plan Review Details - Permit 11110598
Plan Review Stops For Permit 11110598
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-30 Cont ID  
Sent By shill Date 2011-12-30 Time 17:15 Rev Time 0.00
Received By shill Date 2011-12-30 Time 17:15 Sent To  
Notes
2012-01-05 18:13:20****PROVISOS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEPARATE PERMIT REQUIRED FOR ROOF. PRODUCT APPROVALS
 TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL, FBC106.3.3. THE ASSEMBLY PROPOSED IS TO BE
 INDICATED AND CALCULATIONS FOR ZONES 2 AND 3, IF
 REQUIRED, ARE TO BE SUBMITTED. PRESSURES TO COMPLY WITH
 MINIMUM REQUIREMENTS SPECIFIED BY EOR ON SHEET S302
 (ZONE 2 -71.7, ZONE 3 -107.9, ZONE 2 OH -61.5, ZONE 3
 OH -101.4).
  
 2. FBC 1008.1.9 AND 1008.1.8.3 ITEM 2, DOOR 103 AND
 REAR GATE TO INCLUDE REQUIRED PANIC HARDWARE; FRONT
 MAIN ENTRY TO EITHER INCLUDE PANIC HARDWARE OR IS TO
 COMPLY WITH EXCEPTION.
  
 3. BUILDING TYPE IIIB REQUIRES A 2 HOUR EXTERIOR
 BEARING WALL, SEE FBC TABLE 601. EITHER REVISE PLAN TO
 SHOW COMPLIANCE OR REVISE BUILDING TYPE EITHER WITH A
 REVISION OR A LETTER. PROPOSED CONSTRUCTION APPEARS TO
 COMPLY WITH TYPE VB.
  
 4. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.2.1
 PRIOR TO FOOTING INSPECTION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-07 Cont ID  
Sent By shill Date 2011-12-07 Time 13:47 Rev Time 0.00
Received By shill Date 2011-11-30 Time 17:38 Sent To  
Notes
2011-12-07 13:47:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. A000, LOCATION OF ACCESS AISLE COMPELS THE USER TO
 WALK OR WHEEL BEHIND PARKED CARS; COULD THE ACCESS
 AISLE BE RELOCATED ADJACENT TO THE SIDEWALK? FBC11
 4.6.2.
  
 2. IMPACT FEES ASSESSMENT REQUIRED. PLEASE CONTACT PALM
 BEACH COUNTY, 561 233 5025 FOR MORE INFORMATION. THE
 PLANS ARE TO BE STAMPED AND THE RECEIPT PROVIDED.
  
 3. THIS APPEARS TO BE A CHANGE OF OCCUPANCY. PLEASE
 REVISE LS100 AND INCLUDE IN DESIGN CRITERIA. CONFIRM
 COMPLIANCE WITH ALL REQUIREMENTS, SEE FBC EXISTING
 BUILDING.
  
 4. DINING AND BAR AREA REQUIRE TWO EXITS, FBC 1015.1,
 LS100. OCCUPANT LOAD IS OVER 50. PLEASE CONSIDER THE
 FOLLOWING WHEN REVISING THE PLAN TO SHOW TWO EXITS:
  
 IF DOOR 103 IS INTENDED FOR USE AS THE SECOND MEANS OF
 EGRESS, PLEASE SEE FBC 1024.1, EXIT DISCHARGE SHALL NOT
 REENTER A BUILDING, AND SEE COMMENT 5 REGARDING THE
 OUTDOOR WAITING AREA.
  
 PLEASE SEE FBC 1015.2, EXITS TO BE LOCATED IN A MANNER
 WHICH MAKES THEIR AVAILABILITY OBVIOUS. THE EXITING
 STRATEGY FOR THE SECOND DINING AND BAR EXIT IS NOT
 CLEAR. PLEASE REVISE PLAN TO SHOW TWO EXITS AND CLARIFY
 HOW THE AVAILABILITY IS OBVIOUS TO THE OCCUPANTS.
  
 PLEASE NOTE THAT EVEN IF THE OUTDOOR WAITING AREA IS
 CONSIDERED THE OUTDOORS AND NOT A PART OF THIS
 BUILDING, IT APPEARS THAT OCCUPANTS IN THE DINING AND
 BAR AREA, IF UNABLE TO EXIT THROUGH DOOR 100 DUE TO A
 HAZARD IN THAT ROOM, WOULD BE FORCED TO USE THE REAR
 EXIT WHICH HAS AN EXIT DISCHARGE ADJACENT TO THE
 HAZARD. AS THERE IS NO FIRE RATED ASSEMBLY (GLASS
 STOREFRONT), THERE WOULD BE NO PROTECTION FROM THE
 HAZARD. PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
 5. EXITS ARE TO BE REMOTELY LOCATED, FBC 1015.2.1.
 PROVIDE MORE INFORMATION REGARDING THE NATURE OF THE
 OUTDOOR WAITING AREA. BASED ON THE FLOOR PLAN LS100,
 SURVEY (APPEARS TO SHOW THIS AREA AS COVERED CONCRETE),
 ROOF PLAN, THIS APPEARS TO BE A PART OF THE BUILDING.
 THE PAGE LABELED SITE APPEARS TO SHOW A FENCE OR WALL
 ON THE WEST SIDE OF THE OUTDOOR WAITING AREA. IT IS NOT
 CLEAR WHICH DOOR OR GATE IS THE EXIT AS DEFINED IN FBC
 1002 AND, IF DOOR 103A IS THE EXIT AS SHOWN ON LS100.
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
 6. SEE FBC1024.4, EXIT DISCHARGE SHALL BE SUFFICIENTLY
 OPEN TO THE EXTERIOR SO AS TO MINIMIZE THE ACCUMULATION
 OF SMOKE AND GASES. PROVIDE MORE INFORMATION REGARDING
 THE OUTDOOR WAITING AREA IF THIS AREA IS TO BE USED AS
 EXIT DISCHARGE.
  
 7. FBC 1014.2(2), MEANS OF EGRESS SHALL NOT PASS
 THROUGH THE KITCHEN, SEE OFFICE LS100.
  
 8. PLAN STATES THAT THIS BUILDING IS FULLY SPRINKLERED.
 IF A SPRINKLER EXEMPTION IS TO BE USED, PLEASE PROVIDE
 A BASIC SPRINKLER HEAD LAYOUT PLAN. IF THIS BUILDING
 DOES NOT CURRENTLY HAVE SPRINKLERS INSTALLED, AND IF A
 SPRINKLER EXEMPTION IS USED FOR COMPLIANCE WITH FBC,
 HYDRAULIC CALCS MAY BE REQUIRED AT THIS TIME (PRIOR TO
 BUILDING PERMIT ISSUANCE) SUBJECT TO FIRE DEPARTMENT?S
 DISCRETION. COMPLETE PLANS, SPECS, HYDRAULIC CALCS WILL
 BE REQUIRED WITH THE SPRINKLER PERMIT APPLICATION.
 FBC*106.3.5.1.1(5), FS553.79 (2).
  
 9. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 ALL COMPONENTS AND CLADDING, FAC9N 3. PLEASE PROVIDE
 PRODUCT APPROVALS FOR THE DOORS AND STOREFRONT GLASS,
 ROOF, MECHANICAL EQUIPMENT STANDS.
  
 FOR THE ROOF, THE ASSEMBLY PROPOSED IS TO BE INDICATED
 AND CALCULATIONS FOR ZONES 2 AND 3, IF REQUIRED, ARE TO
 BE SUBMITTED. THIS CAN BE DONE EITHER WITH THE MASTER
 PERMIT OR WITH THE ROOF SUB PERMIT, SEPARATE REVIEW
 REQUIRED.
  
 10. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL, FBC 106.3.3.
  
 11. FBC 1008.1.9 AND 1008.1.8.3 ITEM 2, PLEASE CONFIRM
 THAT PRODUCT APPROVAL FOR THE DOORS INCLUDE REQUIRED
 PANIC HARDWARE AS APPLICABLE.
  
 12. FBC 1003.6, MEANS OF EGRESS CONTINUITY, PLEASE
 PROVIDE MORE INFORMATION REGARDING THE DOOR OR GATE
 SHOWN AT THE SOUTH END OF THE OUTDOOR WAITING AREA.
  
 13. PROVIDE AN OCCUPANT LOAD FOR THE OUTDOOR WAITING
 AREA, FBC 1004.
  
 14. LS100 STATES THIS BUILDING AS TYPE IIA
 CONSTRUCTION. PLEASE SEE FBC 602.2 AND FBC 603. S200
 SHOWS WOOD TRUSSES AND PLYWOOD SHEATHING (ONE EXAMPLE),
 NOT PERMITTED IN A TYPE II NON COMBUSTIBLE BUILDING
 EXCEPT AS PERMITTED BY FBC 603. EITHER REVISE BUILDING
 TYPE OR REVISE PLAN TO SHOW COMPLIANCE WITH TYPE IIA.
 NOTE THAT COMBUSTIBLES SUCH AS PVC ARE NOT PERMITTED IN
 A NON COMBUSTIBLE BUILDING.
  
 15. S100, WIND DESIGN CRITERIA STATES THAT THIS IS
 DESIGNED TO EXPOSURE B. PLEASE SEE
 FBC1609.4.2. EITHER REVISE TO EXPOSURE C OR PROVIDE
 RATIONAL ANALYSIS FOR REDUCED PRESSURES IN THE
 TRANSITION ZONE. ALSO REVISE PRESSURES ON A500, S302 AS
 NEEDED.
  
 16. SEE FBC1006 AND REVISE PLAN TO SHOW COMPLIANCE WITH
 MEANS OF EGRESS ILLUMINATION FOR THE OUTDOOR WAITING
 AREA.
  
 17. FBC 11-5.2, PROVIDE A DETAIL FOR THE BAR.
  
 18. FBC 11 5.1, SHOW HOW ACCESSIBLE SEATING WILL BE
 ADDRESSED FOR THE DINING, OUTDOOR WAITING, AND OUTDOOR
 DINING.
  
 19. DOOR 103A DOES NOT MEET THE MINIMUM WIDTH REQUIRED
 BY FBC 11-4.13.4.
  
 20. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.2.1.
  
 21. SHOW DISTANCE FROM RTUS TO ROOF EDGE, FBC 1013.5.
 PROVIDE A DETAIL FOR GUARD IF REQUIRED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-12-28 Cont ID  
Sent By rlecky Date 2011-12-28 Time 16:17 Rev Time 0.00
Received By rlecky Date 2011-12-28 Time 15:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-12-08 Cont ID  
Sent By rlecky Date 2011-12-08 Time 19:06 Rev Time 0.00
Received By rlecky Date 2011-12-08 Time 18:20 Sent To  
Notes
2011-12-08 18:57:21 
 PLEASE NOTE:
 A SEPARATE PERMIT WITH PLANS IS REQUIRED FOR THE
 ELECTRICAL SITE LIGHTING. LOW VOLTAGE, FIRE ALARM,
 AUDIO AND DATA SYSTEMS ARE PERMITTED SEPARATELY AS
 WELL.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-12-12 Cont ID  
Sent By mgonzale Date 2011-12-12 Time   Rev Time 0.25
Received By mgonzale Date 2011-12-12 Time   Sent To  
Notes
2011-12-12 10:38:49USE POLLUTION PREVENTION PLANS TO CONTAIN DEBRIS
 ON-SITE.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-01-05 Cont ID  
Sent By wjolin Date 2012-01-04 Time 15:26 Rev Time 0.00
Received By wjolin Date 2012-01-04 Time 14:28 Sent To  
Notes
2012-01-04 15:22:371700 SOUTH DIXIE HIGHWAY
 PERMIT #11110598
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 PROVIDE AN ARCHITECTURAL SEATING AND FURNITURE PLAN.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE
 DETAILS.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 PER CONVERSATION WITH ARCHITECT (1/5/12) OUTDOOR
 SEATING AREA DOES NOT HAVE A CEILING, ONLY A SMALL ROOF
 OVERHANG. NOTE: NO AWNING, CEILING, ROOF OR ANY OTHER
 STRUCTURE THAT WILL ALLOW SMOKE TO ACCUMULATE IS TO BE
 INSTALLED OVER THE OUTDOOR DINING AREA.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-12-08 Cont ID  
Sent By wjolin Date 2011-12-08 Time 14:41 Rev Time 0.00
Received By wjolin Date 2011-12-08 Time 08:49 Sent To  
Notes
2011-12-08 14:41:021700 SOUTH DIXIE HIGHWAY
 PERMIT #11110598
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND COLOR. ADDRESS TO FACE DIXIE
 HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 THE BENCH TYPE SEATING COUNT NEEDS TO BE FIGURED INTO
 THE OCCUPANT LOAD CALCULATIONS.
  
 BOTH THE INDOOR AND OUTDOOR AREAS EXCEED AN OCCUPANT
 LOAD OF 50 PERSONS AND WILL REQUIRE TO TWO SEPARATE,
 DISTINCT EXITS. THE EXIT DISCHARGE OF THE OUTDOOR
 DINING EXIT LEADS BACK TO THE MAIN BUILDING ENTRANCE
 AND CANNOT BE CONSIDERED A SEPARATE EXIT.
  
 PROVIDE THE ARCHITECTURAL SEATING PLAN THAT IS BEING
 UTILIZED IN THE ENGINEERING DRAWINGS.
  
 PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING
 OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE
 EXTINGUISHER COMPANY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 INDICATE THE HOURLY FIRE RATING OF THE FIRE DOORS. FIRE
 DOORS SHALL BE SELF CLOSING AND POSITIVE LATCHING.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE
 SURFACE.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM, KITCHEN EXHAUST HOOD, AND HOOD
 SUPPRESSION SYSTEM.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-11-28 Cont ID  
Sent By fmittner Date 2011-11-28 Time 12:06 Rev Time 0.00
Received By fmittner Date 2011-11-28 Time 12:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-05 Cont ID  
Sent By shill Date 2012-01-11 Time 18:13 Rev Time 0.00
Received By hmoser Date 2011-12-22 Time 15:16 Sent To  
Notes
2011-12-22 15:18:00*****************EXPEDITED*****************
 2ND RUN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-12 Cont ID  
Sent By shill Date 2011-12-12 Time 16:55 Rev Time 0.00
Received By shill Date 2011-11-28 Time 17:40 Sent To  
Notes
2011-11-30 10:15:58****************EXPEDITED******************
 C--25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-01-06 Cont ID  
Sent By shill Date 2012-01-06 Time 15:45 Rev Time 0.00
Received By shill Date 2012-01-06 Time 15:45 Sent To  
Notes
2012-01-06 15:45:54MU-2012-186

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-12-07 Cont ID  
Sent By shill Date 2011-12-07 Time 13:48 Rev Time 0.00
Received By shill Date 2011-12-07 Time 13:48 Sent To  
Notes
2011-12-07 13:51:44PLEASE CONTACT 561-233-5025, PALM BEACH COUNTY IMPACT
 FEES
 (SEE BUILDING COMMENTS)
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-12-30 Cont ID  
Sent By hmoser Date 2011-12-30 Time 07:55 Rev Time 0.00
Received By hmoser Date 2012-04-11 Time 15:03 Sent To  
Notes
2012-04-11 15:07:11PASS PROVISO
 REFER TO SECTION 308 CLEARANCE REDUCTION 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-12-08 Cont ID  
Sent By hmoser Date 2011-12-08 Time 08:10 Rev Time 0.00
Received By hmoser Date 2011-12-08 Time 08:10 Sent To  
Notes
2011-12-08 11:59:50****CORRECTIONS****
 11110598
  
 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR
 REFRIGERATION EQUIPMENT, HOOD.
  
 2. GUARDS REQUIRED WHERE MECHANICAL EQUIPMENT IS
 LOCATED LESS THAN 10FT FROM ROOF EDGE, FBC MECHANICAL
 304.10.
  
 3. FD (FIRE DAMPERS) SHOWN AT UNITS 3, 4, 5 BUT NO WALL
 IS IN THESE LOCATIONS.
  
 4. VOLUME DAMPERS REQUIRED, FBC MECHANICAL 603.1.7.
  
 5. DUCT SMOKE DETECTORS REQUIRED, FBC MECHANICAL 606.2.
  
 6. SUPERVISION REQUIRED FOR DUCT SMOKE DETECTORS, FBC
 MECHANICAL 606.4.1.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR
 561-805-6732
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-27 Cont ID  
Sent By lwagner Date 2011-12-27 Time 09:18 Rev Time 0.00
Received By lwagner Date 2011-12-27 Time 08:47 Sent To  
Notes
2011-12-27 09:18:38SEPARATE PLAN, APPLICATION, FEES, AND PERMIT REQUIRED
 FOR FUEL GAS

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-12-09 Cont ID  
Sent By lwagner Date 2011-12-09 Time 15:28 Rev Time 0.00
Received By lwagner Date 2011-12-09 Time 09:46 Sent To  
Notes
2011-12-09 15:28:04FBC 2007 PLUMBING REVIEW #1
 CORRECTIONS:
  
 1. ALL HOSE BIBBS WILL REQUIRE SHUT OFF VALVES.
 PLUMBING 606.2
  
 2. SHEET P200 SHOWS 1 1/4" WATER PIPE AT THE RESTROOM
 LOCATION BUT MUCH OF THE COLD WATER SIZING IS MISSING
 TO THAT POINT AND THE MAIN RISER IS MISSING.
  
 3. SHEET P300 THE GREASE TRAP DETAIL IS MISSING THE
 INLET DROP TO 24" BELOW WATER LEVEL. PLUMBING 1003.5.3
  
 ****NOTE****
 NO GAS REVIEW AT THIS TIME AS NO GAS CONTRACTOR SIGNED
 ON. PLAN, APPLICATION, DRAWINGS, FEES REQUIRED. ALSO,
 SEE BELOW FOR PLAN REVIEW REQUIREMENTS:
  
 GAS PERMIT APPLICATION REQUIREMENTS
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2007 FUEL GAS CODE SEC. 304
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2007 FUEL GAS CODE
 SEC. 502 THRU 505.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2007 FUEL GAS SEC. 402.2
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO:
 CHIEF PLUMBING INSPECTOR (561) 805-6692
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 2 Status P Date 2011-12-22 Cont ID  
Sent By fmittner Date 2011-12-22 Time 13:53 Rev Time 0.00
Received By fmittner Date 2011-12-22 Time 13:53 Sent To  
Notes
2011-12-22 13:53:56SEPERATE PERMITS TO BE PULLED AS INDICATED ON FIRST
 ZONING REVIEW

Review Stop Z ZONING
Rev No 1 Status F Date 2011-12-12 Cont ID  
Sent By fmittner Date 2011-12-12 Time 16:08 Rev Time 0.00
Received By fmittner Date 2011-12-12 Time 14:24 Sent To  
Notes
2011-12-12 16:59:54SEPARATE PERMITS REQUIRED FOR:
 LIGHTING (PHOTOMETRIC PLAN TO REFLECT .5 FOOTCANDLE AT
 RESIDENTIAL PROPERTY LINE AND NO GLARE ON DIXIE, SHOW
 DETAILS OF FIXTURES, HEIGHT NOT TO EXCEED 15')
 LANDSCAPE ( NEED MORE TREES ALONG DIXIE AND BEHIND BLDG
 AT RESIDENTIAL PROPERTY LINE, PALMS NEED TO BE GROUPED
 IN 3S ONLY 50% SUBSTITUTE FOR TREES, NEED 40" HEDGE
 MATERIAL AT DIXIE )
 PARKING (REVISE PARKING CHART REFLECTING EXISTING,12"
 INSIDE TO INSIDE STRIPES, NORTH PARKING LOT NO BACK-UP
 NOTCH REQUIRED, REDUCE DRIVE AISLE IN SOUTH LOT TO
 INCREASE LANDSCAPING)
  
 ADDITIONAL PERMITS REQUIRED FOR:
 FLAG POLE (SHOW HEIGHT, US OR FL ONLY)
 DUMPSTER (SHOW DIMENSIONS, MATERIALS)
 SIGN
  
 MISC COMMENTS:
 INCLUDE DIMENSIONS AND MATERIALS ON CIVIL/SITE PLAN
 FENCE SETBACK TO BE REFLECTED ON ALL PLANS
 A/C AND MECHANICAL EQUIPTMENT AND
 SCREENING...ELEVATIONS AND DETAILS REQUIRED**** VERY
 IMPORTANT
 DEFINE SERVICE AREA MATERIAL AREA WITH CAN WASH
 INDICATE ACCESSIBLE ROUTE TO PUBLIC SIDEWALK
 SHOW DIMENSION OF ACCESS/CURB AT SOUTH PROPERTY
 LINE...ONE WAY OR 24'?
 PROVIDE FDOT PERMIT FOR CURB MODIFICATION
  
 QUESTIONS CONTACT FRIEDERIKE MITTNER: 822-1457
 FHM SPOKE TO ARCHITECT CAROLINE FOREST 12-12-11 4:15PM
 EXPLAINED COMMENTS, NEED FOR SEPERATE PERMITS, NEED FOR
 SCREENING OF A/C AND OTHER ROOFTOP MECHANICAL
 EQUIPTEMENT.
2011-12-07 15:35:38REVIEW IN PROGRESS...TO BE COMPLETED 12-12-11 FHM