Plan Review Details - Permit 11110516
Plan Review Stops For Permit 11110516
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-12-19 Cont ID  
Sent By jwitmer Date 2011-12-19 Time 11:59 Rev Time 0.50
Received By jwitmer Date 2011-12-19 Time 11:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-28 Cont ID  
Sent By jwitmer Date 2011-11-28 Time 15:52 Rev Time 0.55
Received By jwitmer Date 2011-11-28 Time 15:36 Sent To  
Notes
2011-11-28 16:03:42BUILDING PLAN REVIEW
 PERMIT: 11110516
 ADD: 335 CLEMATIS ST
 CONT: RAYMOND NORDINE
 TEL: (561)252-1662
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007/09 FL EXST. BLDG CODE 706.1 BUILDINGS
 FACILITIES OR ELEMENTS THAT ARE ALTERED SHALL COMPLY
 WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE. SHEET A-2
 THE NEWLY RECONFIGURED RESTROOM WILL NEED TO SHOW
 COMPLIANCE WITH SECTION 11-4.22.2 DOORS. ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH SECTION
 11-4.13. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
  
 2) 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS
 SERVED AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN
 HEIGHT FOR CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR
 STANDING AT THE COUNTER, A PORTION OF THE MAIN COUNTER
 WHICH IS 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE
 PROVIDED IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE
 SHALL BE AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME
 AREA.
  
 3) THE DOLLAR VALUE ON THE PERMIT APPLICATION IS LOW
 FOR THE DESCRIPTION OF WORK COVERED WITHIN THE PLANS. W
 P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY. 108.3* BUILDING PERMIT
 VALUATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-12-20 Cont ID  
Sent By jleahy Date 2011-12-20 Time 16:35 Rev Time 0.00
Received By jleahy Date 2011-12-20 Time 16:25 Sent To  
Notes
2011-12-20 16:27:29PROVISO
  
 SEE PAGE A-3 AND A-5 OF PLANS FOR REQUIREMENTS PER
 CODE.
  
 J LEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-12-01 Cont ID  
Sent By rlecky Date 2011-12-01 Time 10:40 Rev Time 0.00
Received By rlecky Date 2011-12-01 Time 09:58 Sent To  
Notes
2011-12-01 10:41:1111110516
 333 CLEMATIS ST.
 INTERIOR RENOVATION
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE
 EQUIPMENT. NEC 110.9
 VERIFY THE EXISTING SERVICE RISER HAS ADEQUATE SIZE AND
 CLEARANCE. NEC 230.24
 INDICATE THE WIRE SIZE REQUIRED FOR THE SERVICE RISER.
 NEC 310.16
 VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN
 ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC
 230.72
 SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5
 PROVIDE A LIGHTING PLAN. SPECIFY ON THE PLANS HOW THE
 LIGHTING WILL BE CONTROLLED USING MOTION SENSORS OR
 SIMILAR TECHNIQUES AS REQUIRED BY THE FLORIDA BUILDING
 CODE. SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL
 CONTROLS 13-415.ABC.1.3, EXISTING BUILDING 711.1
 IF THERE ARE SHOW WINDOWS AT LEAST ONE RECEPTACLE
 OUTLET IS REQUIRED AT THE TOP OF THE SHOW WINDOWS FOR
 EACH 12 LINEAR FEET. NEC 210.63
 PROVIDE A SIGN CIRCUIT. NEC 660.5
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-12-12 Cont ID  
Sent By wjolin Date 2011-12-12 Time 12:58 Rev Time 0.00
Received By wjolin Date 2011-12-12 Time 12:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-30 Cont ID  
Sent By wjolin Date 2011-11-30 Time 11:02 Rev Time 0.00
Received By wjolin Date 2011-11-30 Time 10:31 Sent To  
Notes
2011-11-30 11:02:40333 CLEMATIS STREET
 PERMIT #11110516
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 PROVIDE ILLUMINATED MEANS OF EGRESS.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-20 Cont ID  
Sent By lmartine Date 2011-12-20 Time 16:39 Rev Time 0.00
Received By lmartine Date 2011-12-09 Time 17:47 Sent To  
Notes
2011-12-09 17:47:29C--9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-09 Cont ID  
Sent By lmartine Date 2011-12-09 Time 17:46 Rev Time 0.00
Received By lmartine Date 2011-11-21 Time 16:51 Sent To  
Notes
2011-11-21 16:51:23C7

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-12-02 Cont ID  
Sent By lwagner Date 2011-12-02 Time 14:41 Rev Time 0.00
Received By lwagner Date 2011-12-02 Time 14:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-12-08 Cont ID  
Sent By aaponte Date 2011-12-08 Time 10:54 Rev Time 0.00
Received By aaponte Date 2011-12-08 Time 10:54 Sent To  
Notes
2011-12-08 10:54:55SIGN NOT INCLUDED IN THIS PERMIT.