Plan Review Details - Permit 11110130
Plan Review Stops For Permit 11110130
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-11-15 Cont ID  
Sent By wjolin Date 2011-11-15 Time 12:27 Rev Time 0.00
Received By wjolin Date 2011-11-15 Time 12:04 Sent To M
Notes
2011-11-15 12:27:47477 SOUTH ROSEMARY AVENUEN - SUITE #221
 PERMIT #11110130
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE CHANGE
 FROM RESIDENTIAL SPRINKLERS TO COMMERCIAL SPRINKLERS.
  
 SUBMIT CUT SHEETS FOR SPRINKLERS.
  
 FOR AREAS WITH EXPOSED STRUCTURE (NO CEILING) INDICATE
 IF THE SPACE IS OBSTRUCTED OR UNOBSTRUCTED CONSTRUCTION
 AND THE INDICATE THE DISTANCE SPRINKLERS ARE LOCATED
 BELOW THE STRUCTURE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-19 Cont ID  
Sent By hmoser Date 2011-11-19 Time 08:44 Rev Time 0.00
Received By hmoser Date 2011-11-14 Time 16:17 Sent To  
Notes
2011-11-14 16:17:46TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-11-19 Cont ID  
Sent By hmoser Date 2011-11-19 Time 08:44 Rev Time 0.00
Received By hmoser Date 2011-11-19 Time 08:44 Sent To  
Notes
***NONE***