Plan Review Details - Permit 11110112
Plan Review Stops For Permit 11110112
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-01-05 Cont ID  
Sent By lmartine Date 2012-01-05 Time 16:47 Rev Time 0.00
Received By lmartine Date 2012-01-05 Time 16:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-12-19 Cont ID  
Sent By jgomez Date 2011-12-19 Time 11:46 Rev Time 0.00
Received By jgomez Date 2011-12-19 Time 11:38 Sent To  
Notes
2011-12-19 13:39:58ADDITION/ALTERATION (R3) BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9N-3
 FOR:
 A) 6'-8" FIBERGLASS DOORS AS SHOWN ON PLANS. DRAWING
 FL-11321.6 SUBMITTED IS FOR 8'-0" DOORS.
 B) WINDOW MULLIONS. NOA 10-0819.05 WAS SUPERSEDED BY
 MIAMI-DADE. NEED CURRENT NOA.
 C) MISSING EXTERIOR DOOR NOA 06-0406.11 SPECIFIED ON
 ENGINEER LETTER LISTING REVIEWED PRODUCT APPROVALS.
  
 ***NOTE: PLEASE HAVE HISTORIC APPROVAL PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS.
 UPDATE LETTER STATING ALL PRODUCT APPROVALS COVERED
 UNDER THIS REVISION/ADDITION INCLUDING THE ONES THAT
 WERE SUBMITTED ON FIRST SUBMITTAL.
  
 3- FLAT ROOF: PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION ON LAST PAGE OF NOA 09-0820.11 TO
 MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3.
  
 4- PROVIDE STORM SHUTTERS COMPLETE INSTALLATION
 SCHEDULE AND CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE
 USED. THIS APPLIES TO BOTH TYPES OF SHUTTERS SUBMITTED.
 FABRIC SHUTTERS AND STORM PANELS. SEE CITY POLICY FOR
 HURRICANE SHUTTERS REQUIRED INFORMATION.
  
 5- SPECIFY EMERGENCY OVERFLOW SCUPPERS AS REQUIRED BY
 SEC. R903.4.1.
  
 7- SPECIFY HOW THE ROOF GUTTERS WILL DISCHARGE THE RAIN
 WATER A LEAST ONE FOOT AWAY FROM THE STRUCTURE AS
 REQUIRED BY SEC. R320.7.
  
 8- ARCHITECT TO COORDINATE ROOF DRAINS WITH ENGINEER
 NOTE #1 ON DETAIL 1/S1. THERE ARE NOT INTERIOR ROOF
 DRAINS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-18 Cont ID  
Sent By jgomez Date 2011-11-18 Time 16:47 Rev Time 0.00
Received By jgomez Date 2011-11-18 Time 16:45 Sent To  
Notes
2011-11-18 17:04:16ADDITION/REVISION BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLEASE PROVIDE ENERGY CALCULATIONS AS REQUIRED BY
 SEC. N1100.3.
  
 2- PLEASE PROVIDE PRODUCT APPROVAL (2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR:
 A) CASEMENT WINDOWS AS SPECIFIED ON PLANS.
 B) SINGLE HUNG WINDOWS. NOA 11-0405.10 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE
 WEBSITE AND DOWNLOAD CURRENT NOA.
 C) FIBERGLASS EXTERIOR DOOR. FLORIDA PRODUCT APPROVAL
 FL-11321.6 SUBMITTED IS FOR 8'-0" DOORS. NEED ONE FOR
 6'-8" DOORS AS SPECIFIED ON PLANS.
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, SECTIONS AND UPLIFT CONNECTOR SCHEDULE. PLEASE,
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR.
 E) WINDOW MULLIONS AS SHOWN ON PLANS. AND CLEARLY
 INDICATE SIZE OF MULLION TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.2.1.4.3.
 F) FLAT ROOF. AND, CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED AND PROVIDE RAS 117
 CALCULATIONS. CALCULATIONS TO BE SIGNED AND SEALED IF
 THE PRODUCT APPROVAL SUBMITTED REQUIRES IT.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR
 TO SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC.
  
 4- PLEASE HAVE ALL THE REVISED PLANS AND PRODUCT
 APPROVALS REVIEWED BY HISTORIC FOR APPROVAL PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  
 5- PLEASE PROVIDE STORM SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. AND, CLEARLY MARK ON SHUTTERS DRAWINGS
 SPECIFIC WALL MOUNTING CONDITIONS (EX: WALL MOUNTED
 SECTION 1 OR WALL MOUNTED SECTION 2, ETC.), ANCHOR TYPE
 AND SPACING TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES BY SEC. R301.2.1.4.3.
  
 6- PLEASE BRING REVISED PLANS TO PALM BEACH COUNTY TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 7- PLEASE SPECIFY TYPE OF EXISTING BEDROOM WINDOWS TO
 BE REPLACED (EX: CASEMENT, SINGLE HUNG, ETC) TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. R310.
  
 8- ARCHITECT TO PROVIDE HIS LICENSE NUMBER ON THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004 FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
  
 9- VALUATION AND NUMBER OF SHEETS WERE UPDATED. OWES
 $692.85.
  
 10- SPECIFY ON PLANS CARBON MONOXIDE ALARMS IN ALL
 BEDROOMS AS REQUIRED BY SEC. R313.4.
  
 11- A) PLEASE SPECIFY OVERFLOW SCUPPERS AS REQUIRED BY
 SEC. R903.4.1.
  
 B) ROOF SCUPPERS SHOWN ON PLANS AND ELEVATIONS DON'T
 SHOW ANY DOWNSPOUTS. PLEASE PROVIDE SPECIFICATIONS
 SHOWING HOW PROTECTING THE BUILDING AS REQUIRED BY SEC.
 R320.7.
  
 C) PLEASE COORDINATE ROOF DRAINS AND SCUPPERS WITH
 ENGINEER NOTE #1 ON DETAIL 1/S1 ON SHEET S-1.
  
 12- PLEASE PROVIDE COMPLETE SPECIFICATIONS/DETAILS
 SHOWING COMPLIANCE WITH THE ROOF VENTILATION AS
 REQUIRED BY SEC. R806.
  
 13- SHEET A-0: PLEASE REVISE FRAMING NOTE #9. MAXIMUM
 RISER HEIGHT SHALL BE 7-3/4" NO 8". SEC. R311.5.3.1
  
 14- SHEET A-1: PLEASE COORDINATE NEW ENTRY STEPS WITH
 INFORMATION SHOWN ON FOUNDATION PLAN ON SHEET S-1. AND
 PROVIDE RISER AND TREAD DIMENSIONS TO VERIFY COMPLIANCE
 WITH SEC. R311.5.3.
 ALSO, PROVIDE DIMENSIONS FOR STEPS AND LANDING AT REAR
 DOOR BY THE KITCHEN AREA AND AT THE NEW LOGGIA.
  
 15- SHEET A-2: PLEASE CLARIFY ROOF SPECIFICATIONS ON
 DETAIL 1 AND DETAIL 2. INFORMATION PROVIDED IS
 CONFUSING THE UNDERLAYMENT WITH THE SHEATHING. CLEARLY
 IDENTIFY UNDERLAYMENT NAIL TYPE AND SPACING (SEE FLAT
 ROOF PRODUCT APPROVAL) AND ROOF SHEATHING NAIL TYPE AND
 SPACING. STRUCTURAL DRAWINGS ARE MISSING THE
 SPECIFICATIONS FOR THE ROOF SHEATHING AND THE TERRACE
 SHEATHING. **NOTE: SEC. R803.2.3.1 REQUIRES 8D RING
 SHANK NAILS AND ROOF ZONE 3 NEED TO BE AT 4"O.C..
 PLEASE PROVIDE COMPLETE SPECIFICATIONS, INCLUDING THE
 ROOF SHEATHING THICKNESS, NAIL SIZE AND SPACING IN THE
 STRUCTURAL DRAWINGS.
  
 16- SHEET S-1: A) THE SLOPE REQUIRED FOR ALL FLAT ROOFS
 IS 1/4" PER FOOT MINIMUM. SEC. R905.11.1. PLANS AND
 SECTIONS SHOW 2" SLOPE. THIS DOESN'T PROVIDE THE
 REQUIRED MINIMUM SLOPE. REVISE ALL SPECIFICATIONS ON
 PLANS AND DETAILS AS REQUIRED.
  
 B) DETAIL 1/S1 SPECIFIES 3/4" STUCCO. NEED TO PROVIDE
 7/8" MIN. AS REQUIRED BY TABLE R702.1(1). PLEASE REVISE
 AS REQUIRED.
  
 C) PLEASE PROVIDE SPECIFICATIONS FOR COLUMNS AND
 HEADERS ON THE WIDENED OPENING BY THE BUTLER'S PANTRY
 AND THE RELOCATED BACK DOOR IN THE KITCHEN AREA. SEC.
 R301.
  
 D) PLEASE REVISE NOTE #1 ON DETAIL 2/S1. SEE SEC.
 R319.1 FOR DISTANCE FROM GRADE AND REVISE AS REQUIRED.
  
 E) PLEASE REVISE NOTE #3 ON DETAIL 2/S1. SEE SEC. R408
 FOR MINIMUM REQUIREMENTS AND COORDINATE WITH
 ARCHITECTURAL PLANS ALSO.
  
 17- SHEET S-2: PLEASE REVISE ALL SPECIFICATIONS ON
 PLANS AND DETAILS THAT REFER TO THE ROOF SLOPE. SEE
 ITEM 16(A) ABOVE.
  
 18- SHEET S-3: SAME COMMENT AS #17 APPLIES.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-12-30 Cont ID  
Sent By lmartine Date 2011-12-30 Time 16:11 Rev Time 0.00
Received By lmartine Date 2011-12-30 Time 16:11 Sent To  
Notes
2011-12-30 16:11:49SEE PLANS FOR STAMP AND SIGNATURE FROM LECKY.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-11-30 Cont ID  
Sent By rlecky Date 2011-11-30 Time 11:09 Rev Time 0.00
Received By rlecky Date 2011-11-28 Time 16:11 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-12-29 Cont ID  
Sent By fmittner Date 2011-12-29 Time 15:40 Rev Time 0.00
Received By fmittner Date 2011-12-29 Time 15:40 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-11-04 Cont ID  
Sent By lmartine Date 2011-11-04 Time 14:43 Rev Time 0.00
Received By lmartine Date 2011-11-04 Time 14:43 Sent To  
Notes
2011-11-04 14:44:30SEE #11050043 FOR JILLIAN'S APPROVAL AND PROVISO.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-30 Cont ID  
Sent By lmartine Date 2011-12-30 Time 16:11 Rev Time 0.00
Received By lmartine Date 2011-12-15 Time 14:34 Sent To  
Notes
2011-12-16 14:38:34SENT TO R7 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-30 Cont ID  
Sent By rlecky Date 2011-11-30 Time 11:12 Rev Time 0.00
Received By rlecky Date 2011-11-09 Time 15:48 Sent To  
Notes
2011-11-09 15:48:42SENT TO R2 SHELF FOR REVIEW. JG.
2011-11-04 14:42:55GAVE TO JULIO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-12-19 Cont ID  
Sent By jgomez Date 2011-12-19 Time 15:40 Rev Time 0.00
Received By jgomez Date 2011-12-19 Time 15:34 Sent To  
Notes
2011-12-19 15:35:42PLANS WERE STAMPED BY PALM BEACH COUNTY, MU-2011-21261.
 TALKED TO WILLIE SWOOPE TO CONFIRM THAT FEES WERE PAID
 SINCE COPY OF PAID RECEIPT WAS NOT SUBMITTED. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-11-18 Cont ID  
Sent By jgomez Date 2011-11-18 Time 09:38 Rev Time 0.00
Received By jgomez Date 2011-11-18 Time 09:37 Sent To  
Notes
2011-11-18 09:39:22PLEASE TAKE PLANS TO PALM BEACH COUNTY BUILDING TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2011-12-20 Cont ID  
Sent By jgomez Date 2011-12-20 Time 10:36 Rev Time 0.00
Received By jgomez Date 2011-12-20 Time 10:36 Sent To  
Notes
2011-12-20 10:37:48PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-11-22 Cont ID  
Sent By jgomez Date 2011-11-22 Time 14:21 Rev Time 0.00
Received By jgomez Date 2011-11-22 Time 14:21 Sent To  
Notes
2011-11-22 14:30:14RESIDENTIAL (R3) ADDITION/REVISION MECHANICAL REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NO MECHANICAL PLANS AND EQUIPMENT SIZING
 CALCULATIONS WERE SUBMITTED WITH THIS
 ADDITION/REVISION. PLEASE, PROVIDE COMPLETE INFORMATION
 FOR REVIEW.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-12-20 Cont ID  
Sent By jgomez Date 2011-12-20 Time 10:33 Rev Time 0.00
Received By jgomez Date 2011-12-20 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-11-22 Cont ID  
Sent By jgomez Date 2011-11-22 Time 14:34 Rev Time 0.00
Received By jgomez Date 2011-11-22 Time 14:30 Sent To  
Notes
2011-11-22 14:40:26RESIDENTIAL (R3) ADDITION/REVISION PLUMBING REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLEASE CLARIFY KIND OF VENT SHOWN ON PLUMBING RISER
 DIAGRAM ON SHEET A-2. THERE ARE NO SPECIFICATIONS SHOWN
 ON THE PLUMBING RISER.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status P Date 2011-12-29 Cont ID  
Sent By fmitner Date 2011-12-29 Time 15:40 Rev Time 0.00
Received By fmittner Date 2011-12-29 Time 15:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-11-04 Cont ID  
Sent By lmartine Date 2011-11-04 Time 14:46 Rev Time 0.00
Received By lmartine Date 2011-11-04 Time 14:46 Sent To  
Notes
2011-11-04 14:46:49SEE PLANS FOR JILLIAN'S APPROVAL.