Plan Review Details - Permit 11110011
Plan Review Stops For Permit 11110011 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
N |
Date |
2011-12-21 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2011-12-21 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2011-11-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2011-11-21 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2011-11-21 |
Time |
11:43 |
Sent To |
|
|
Notes |
2011-11-21 13:20:40 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. A CBC HAS APPLIED FOR PERMIT, BUT NO BUILDING PLANS | | SUBMITTED. | | | | 2. NO STRUCTURAL WORK (SUCH AS CUTTING OF THE ROOF) CAN | | BE PERFORMED BY A CBC ON A FIVE STORY BUILDING, SEE | | FS489. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2011-12-21 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2011-12-21 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2011-12-15 |
Time |
10:26 |
Sent To |
|
|
Notes |
2011-12-20 10:31:02 | ROUTED APPLICATION TO PLANS | 2011-12-16 10:24:26 | SENT TO SAMANTHA'S DESK FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2011-11-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2011-11-21 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2011-11-02 |
Time |
10:48 |
Sent To |
|
|
Notes |
2011-11-02 10:48:24 | TO HM DESK | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2011-12-21 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2011-12-21 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2011-12-21 |
Time |
13:42 |
Sent To |
|
|
Notes |
2011-12-21 13:52:47 | PASS PROVISO | | REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER CONTROL . | | ( DAMPER FOR FRESH AIR) | | SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR | | HOOD. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2011-11-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2011-11-21 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2011-11-21 |
Time |
15:53 |
Sent To |
|
|
Notes |
2011-11-21 15:57:21 | 1. PLEASE REVISE AIR BALANCE DIAGRAM TO SHOW COMPLIANCE | | WITH FBC 13.409.AB.2 (BUILDING PRESSURES) AND FBC | | 13.409.AB.3.5 (EXHAUST HOODS). ALSO PLEASE NOTE THAT | | THE AIR BALANCE DIAGRAM SHOWS ONLY ONE BATHROOM EXHAUST | | (TWO REQUIRED AND TWO SHOWN ON FLOOR PLAN). | | | | 2. A MECHANICAL CONTRACTOR IS REQUIRED FOR THE | | MECHANICAL PERMIT. THE CONTRACTOR HAS BEEN CHANGED FROM | | KNOLYS JOHNSON (CBC) TO "TBD." | | | | 3. A SEPARATE PERMIT IS REQUIRED FOR THE HOOD. | | | | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR | | 561-805-6732 |
|
|
|