Plan Review Details - Permit 11110011
Plan Review Stops For Permit 11110011
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2011-12-21 Cont ID  
Sent By hmoser Date 2011-12-21 Time 13:52 Rev Time 0.00
Received By hmoser Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-21 Cont ID  
Sent By shill Date 2011-11-21 Time 11:43 Rev Time 0.00
Received By shill Date 2011-11-21 Time 11:43 Sent To  
Notes
2011-11-21 13:20:40****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. A CBC HAS APPLIED FOR PERMIT, BUT NO BUILDING PLANS
 SUBMITTED.
  
 2. NO STRUCTURAL WORK (SUCH AS CUTTING OF THE ROOF) CAN
 BE PERFORMED BY A CBC ON A FIVE STORY BUILDING, SEE
 FS489.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-21 Cont ID  
Sent By hmoser Date 2011-12-21 Time 13:53 Rev Time 0.00
Received By hmoser Date 2011-12-15 Time 10:26 Sent To  
Notes
2011-12-20 10:31:02ROUTED APPLICATION TO PLANS
2011-12-16 10:24:26SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-21 Cont ID  
Sent By shill Date 2011-11-21 Time 15:57 Rev Time 0.00
Received By shill Date 2011-11-02 Time 10:48 Sent To  
Notes
2011-11-02 10:48:24TO HM DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-12-21 Cont ID  
Sent By hmoser Date 2011-12-21 Time 13:42 Rev Time 0.00
Received By hmoser Date 2011-12-21 Time 13:42 Sent To  
Notes
2011-12-21 13:52:47PASS PROVISO
 REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER CONTROL .
 ( DAMPER FOR FRESH AIR)
 SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR
 HOOD.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-11-21 Cont ID  
Sent By shill Date 2011-11-21 Time 15:53 Rev Time 0.00
Received By shill Date 2011-11-21 Time 15:53 Sent To  
Notes
2011-11-21 15:57:211. PLEASE REVISE AIR BALANCE DIAGRAM TO SHOW COMPLIANCE
 WITH FBC 13.409.AB.2 (BUILDING PRESSURES) AND FBC
 13.409.AB.3.5 (EXHAUST HOODS). ALSO PLEASE NOTE THAT
 THE AIR BALANCE DIAGRAM SHOWS ONLY ONE BATHROOM EXHAUST
 (TWO REQUIRED AND TWO SHOWN ON FLOOR PLAN).
  
 2. A MECHANICAL CONTRACTOR IS REQUIRED FOR THE
 MECHANICAL PERMIT. THE CONTRACTOR HAS BEEN CHANGED FROM
 KNOLYS JOHNSON (CBC) TO "TBD."
  
 3. A SEPARATE PERMIT IS REQUIRED FOR THE HOOD.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR
 561-805-6732