Plan Review Details - Permit 11100712
Plan Review Stops For Permit 11100712
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-11-03 Cont ID  
Sent By wjolin Date 2011-11-03 Time 08:45 Rev Time 0.00
Received By wjolin Date 2011-11-03 Time 08:39 Sent To  
Notes
2011-11-03 08:45:41900 SOUTH OLIVE AVENUE
 PERMIT #11100711
 REVIEW COMMENTS - FIRE DEPARTMENT
 UP - 11/4 OR 11/5 DN - 11/8
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-03 Cont ID  
Sent By wjolin Date 2011-11-03 Time 08:39 Rev Time 0.00
Received By wjolin Date 2011-11-01 Time 15:11 Sent To  
Notes
2011-11-01 15:12:08SENT TO TEMPORARY TENT SHELF FOR FIRE REVIEW. JG.


Account Summary | Usage Policy | Privacy Policy