2011-10-28 13:59:58 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- PROVIDE ALL THE INFORMATION REQUIRED BY THE CITY |
| POLICY FOR RE-ROOFING PERMITS: |
| A) SPECIFY HOW MUCH ROOF AREA IS FOR FLAT ROOF AND HOW |
| MUCH AREA IS FOR SHINGLES. |
| |
| B) SPECIFY ROOF MEAN ROOF HEIGHT. |
| |
| C) SPECIFY ROOF PITCH. |
| |
| 2- FLAT ROOF PRODUCT APPROVALS SUBMITTED: |
| |
| A) PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND THE |
| FIRST PAGES SHOWN THE GENERAL NOTES THAT APPLY. ALSO, |
| PROVIDE PAGE SHOWING THE SPECIFIC ASSEMBLY TO BE |
| INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.2.1.4.3. INFORMATION SUBMITTED |
| IS INCOMPLETE AND MIS-MATCHING UNDERLAYMENT PRODUCT |
| APPROVAL WITH FLAT ROOF ASSEMBLIES PRODUCT APPROVAL. |
| |
| B) PAGE 9 OF 30 OF FLORIDA PRODUCT APPROVAL FL1654-R9 |
| SUBMITTED INDICATES THE PROPOSED INSTALLATION SYSTEM NO |
| W-33. THIS SYSTEM ASSEMBLY IS GOOD FOR A DESIGN |
| PRESSURE OF -97.5 PSF. THIS IS A BONDED ROOF SYSTEM AND |
| IT DOESN'T ALLOW NAIL ENHANCING (SEE NOTE #9 ON |
| FL1654-R9). ACCORDING TO THE FLORIDA RESIDENTIAL CODE |
| 2009 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS |
| LOCATED ON EXPOSURE "C". THE DESIGN PRESSURES FOR |
| EXPOSURE C ARE HIGHER THAN -97.5PSF AT THE CORNER |
| AREAS. THEREFORE, THIS SYSTEM CAN'T BE USED. NEED TO |
| SELECT ANOTHER SYSTEM THAT MEETS THE DESIGN PRESSURES |
| FOR EXPOSURE C. |
| |
| ***NOTE: MECHANICALLY ATTACHED BASE SHEET SYSTEMS |
| ALLLOW NAIL ENHANCING CALCULATIONS. IF USING A |
| MACHANICALLY ATTACHED SYSTEM THEN PROVIDE SIGNED AND |
| SEALED RAS 117 CALCULATIONS AS REQUIRED BY NOTE #8 ON |
| FLORIDA PRODUCT APPROVAL FL1654-R9. |
| |