Plan Review Details - Permit 11100639
Plan Review Stops For Permit 11100639
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-11-16 Cont ID  
Sent By wjolin Date 2011-11-16 Time 10:23 Rev Time 0.00
Received By wjolin Date 2011-11-16 Time 10:16 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-28 Cont ID  
Sent By wjolin Date 2011-10-28 Time 14:12 Rev Time 0.00
Received By wjolin Date 2011-10-28 Time 13:48 Sent To M
Notes
2011-10-28 14:03:33330 CLEMATIS STREET - SUITE #107
 PERMIT #11100639
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ADD SUITE NUMBER TO DRAWING ADDRESS TITLEBLOCK.
  
 SUBMIT PRODUCT DATA ON SPRINKLERS AND FLEXIBLE DROPS.
  
 PROVIDE DRY PENDENT SPRINKLERS IN COOLER.
  
 THE 9'-0" AFF SOFFIT ADJACENT TO THE RESTROOMS DO NOT
 APPEAR TO HAVE SPRINKLER PROTECTION.
  
 SUBMIT HYDRAULIC CALCULATIONS SUPPORTING THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THE FLEXIBLE DROPS.
  
 INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROPS TO BE
 USED.
  
 FLEXHEAD DETAIL: INDICATE THE MINIMUM BENDING RADIUS
 AND MAXIMUM NUMBER OF BENDS PER THE LISTING
 REQUIREMENTS.
  
 NOTE: PER LOCAL AHJ POLICY, ONLY BRAIDED FLEXIBLE DROPS
 ARE ACCEPTED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-19 Cont ID  
Sent By hmoser Date 2011-11-19 Time 10:17 Rev Time 0.00
Received By hmoser Date 2011-11-14 Time 15:24 Sent To  
Notes
2011-11-14 15:25:00TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-07 Cont ID  
Sent By hmoser Date 2011-11-07 Time 14:02 Rev Time 0.00
Received By hmoser Date 2011-10-28 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-19 Cont ID  
Sent By hmoser Date 2011-11-19 Time 10:17 Rev Time 0.00
Received By hmoser Date 2011-11-19 Time 10:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-11-07 Cont ID  
Sent By hmoser Date 2011-11-07 Time 13:57 Rev Time 0.00
Received By hmoser Date 2011-11-07 Time 13:14 Sent To  
Notes
2011-11-07 14:02:37PLEASE PROVIDE SUITE NUMBER ON THE PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved