Plan Review Details - Permit 11100546
Plan Review Stops For Permit 11100546
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-11-16 Cont ID  
Sent By rlecky Date 2011-11-16 Time 10:07 Rev Time 0.00
Received By rlecky Date 2011-11-16 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-11-07 Cont ID  
Sent By rlecky Date 2011-11-07 Time 08:49 Rev Time 0.00
Received By rlecky Date 2011-11-07 Time 08:30 Sent To  
Notes
2011-11-07 08:51:3711100546
 429 BELEVEDERE RD
 ELECTRICAL SERVICE WORK
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE
 EQUIPMENT. NEC 110.9
 VERIFY THE EXISTING SERVICE RISER HAS ADEQUATE SIZE AND
 CLEARANCE. NEC 230.24
 INDICATE THE WIRE SIZE REQUIRED FOR THE SERVICE RISER.
 NEC 310.16
 VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN
 ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC
 230.72
 SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-10-26 Cont ID  
Sent By rlecky Date 2011-10-26 Time 10:14 Rev Time 0.00
Received By rlecky Date 2011-10-26 Time 10:14 Sent To  
Notes
2011-10-26 10:19:52PROVIDE ADDITIONAL INFORMATION ON THE NEW 200A
 ELECTRICAL PANEL. IS THIS NEW OR A CHANGE OUT? ADDING A
 NEW PANEL WILL REQUIRE A RISER PLAN FOR THE EXISTING
 SERVICE AND LOAD CALULATION. NEC 215.5.
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-16 Cont ID  
Sent By rlecky Date 2011-11-16 Time 10:07 Rev Time 0.00
Received By rlecky Date 2011-11-04 Time 13:56 Sent To  
Notes
2011-11-04 13:57:16GAVE TO LECKY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-04 Cont ID  
Sent By lmartine Date 2011-10-26 Time 13:56 Rev Time 0.00
Received By lmartine Date 2011-10-25 Time 12:39 Sent To  
Notes
2011-10-25 12:40:17UNDER 5 K ELECTRIC


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved