Plan Review Details - Permit 11100438
Plan Review Stops For Permit 11100438
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-10-27 Cont ID  
Sent By rmcdouga Date 2011-10-27 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2011-10-27 Time 09:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-21 Cont ID  
Sent By rmcdouga Date 2011-10-21 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2011-10-20 Time 15:57 Sent To  
Notes
2011-10-21 16:27:172007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE C4 CONNECTION TYPE CIRCLED ON THE ANCHOR TABLE
 ON SHEET 9 REQUIRES 11" SPACING. THE INSTALLATION
 SCHEDULE THAT WAS SUBMITTED HAS 12" SPACING FOR EVERY
 OPENING. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-27 Cont ID  
Sent By rmcdouga Date 2011-10-27 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2011-10-26 Time 14:16 Sent To  
Notes
2011-10-26 14:17:30GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-21 Cont ID  
Sent By rmcdouga Date 2011-10-21 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2011-10-20 Time 11:11 Sent To  
Notes
2011-10-21 11:10:53SENT TO MISC 1 BOX