Plan Review Details - Permit 11100380
Plan Review Stops For Permit 11100380
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-01-23 Cont ID  
Sent By jwitmer Date 2012-01-23 Time 16:29 Rev Time 0.77
Received By jwitmer Date 2012-01-23 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-21 Cont ID  
Sent By jwitmer Date 2011-11-21 Time 16:34 Rev Time 0.77
Received By jwitmer Date 2011-11-21 Time 16:34 Sent To  
Notes
2011-11-21 16:38:26BUILDING PLAN REVIEW
 PERMIT: 11100380
 ADD: 2045 REGENTS BLVD
 CONT: GADSEN PROPERTY INVESTMENT INC
 TEL: (561)294-5339
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 SECTION A-A. PLEASE PROVIDE SOME
 CLARIFICATION, THE PLAN AAPPEARS TO HAVE TWO TYPES OF
 LEDGERS A 2X8 AND ALSO A 1X8 PLEASE PROVIDE WHICH IS
 THE LEDGER?
  
 2) SHEET A-1 INDICATE THE WIND DESIGN CRITERIA AS A "B"
 EXPOSURE THIS BACK YARD BACKS UP TO A GOLF COARSE WHICH
 WILL MAKE THIS AN "C" EXPOSURE PLEASE REVIEW ASSOCIATED
 PRESSURES. FBC-B 1609.4.3 EXPOSURE C. THIS EXPOSURE
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN
 EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN
 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF
 EXPOSURE C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET
 (182.9 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2012-01-03 Time 09:31 Sent To  
Notes
2012-01-03 09:31:52TO A STELLY DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-21 Cont ID  
Sent By jwitmer Date 2011-11-21 Time 16:34 Rev Time 0.00
Received By jwitmer Date 2011-10-18 Time 10:56 Sent To  
Notes
2011-10-18 10:57:09SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2012-01-23 Cont ID  
Sent By astelly Date 2012-01-23 Time 13:11 Rev Time 0.00
Received By astelly Date 2012-01-23 Time 13:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-11-02 Cont ID  
Sent By astelly Date 2011-11-02 Time 14:43 Rev Time 0.00
Received By astelly Date 2011-11-02 Time 14:43 Sent To  
Notes
2011-11-02 14:50:40AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 THE REAR SETBACK FOR THIS PROPERTY IS 15 FEET IN
 ACCORDANCE WITH ORDINANCE 2541-92 (ORD. 2238-88
 AMENDED). A CURSORY MEASUREMENT OF THE SETBACK AS
 PROPOSED INDICATES THAT IT IS APPROXIMATELY TEN (10)
 FEET. PLEASE ADJUST ACCORDINGLY OR APPLY FOR A VARIANCE
 FROM THE ZONING BOARD OF APPEALS TO MAINTAIN THE
 CURRENT PROPOSAL.