Plan Review Details - Permit 11100370
Plan Review Stops For Permit 11100370
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-01-13 Cont ID  
Sent By jwitmer Date 2012-01-13 Time 13:26 Rev Time 0.55
Received By jwitmer Date 2012-01-13 Time 13:26 Sent To  
Notes
2012-01-13 13:30:26BUILDING PLAN REVIEW
 PERMIT: 11100370
 ADD: 215 CLEMATIS ST
 CONT: L B DEVELOPMENT
 TEL: (954)709-1926
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 01/13/2012
 3RD REVIEW
 ACTION: APPROVED
  
 1) PROVISO:THE MEZZANINE AND KITCHEN BELOW MUST
 MAINTAIN A FINISHED CEILING HEIGHT OF 7'-0" FBC-B
 1208.2 EXCEPTION # 3. SHEET A-3 STILL INDICATES A 6'-8"
 DIMENSION.
  
 2-4) COMPLIED.
  
  
  
 5) BUILDING PROVISO:
 MISSING PRODUCT APPROVALS FBC-B 1609 COMPONENTS &
 CLADDING, RULE 9N-3.
 5A-B) COMPLIED.
 5C) EXTERIER WALK IN COOLERS &/FREEZERS
  
 6-12) COMPLIED.
  
 13) PROVISO: A SEPERATE PREMIT IS REQUIRED. SHEET A-3 &
 A-4 INDICATE THE USE OF DRYWALL DROPED CEILING PANELS
 WITH LATTICE, A NOTE ON A-3 INDICATES METHOD OF
 ATTACHMENT, SUSPENSION BY OTHERS, THIS SYSTEM TO BE
 REVIEWED BY THE DESIGN PROFESSIONAL, IT CAN BE
 PERMITTED UNDER THIS PERMIT OR COME IN AS A STAND ALONE
 PERMIT. THE DROPPED CEILING WILL NEED TO SHOW
 COMPLIANCE WITH
 803.3 & 803.4.1 AND MEET THE FINISH REQUIREMENTS OF
 TABLE 803.5.
  
 14-15) COMPLIED.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-01-06 Cont ID  
Sent By jwitmer Date 2012-01-06 Time 09:45 Rev Time 2.35
Received By jwitmer Date 2012-01-05 Time 13:08 Sent To  
Notes
2012-01-06 09:51:34BUILDING PLAN REVIEW
 PERMIT: 11100370
 ADD: 215 CLEMATIS ST
 CONT: L B DEVELOPMENT
 TEL: (954)709-1926
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 01/06/2012
 2ND REVIEW
 ACTION: DENIED
  
 1) THE MEZZANINE AND KITCHEN BELOW MUST MAINTAIN A
 FINISHED CEILING HEIGHT OF 7'-0" FBC-B 1208.2 EXCEPTION
 # 3. SHEET A-3 STILL INDICATES A 6'-8" DIMENSION.
  
 2) NO FIRE SPRINKLER PLANS WERE SUBMITTED. THE LAST
 KNOWN USE OF THIS SPACE WAS A DRESS SHOP MAKING THIS A
 CHANGE OF OCCUPANCY. THE 2007/09 FBC EXISTING BUILDING
 CODE CHAPTER 9 CHANGE OF OCCUPANCY SECTION EXST BLDG
 COE 904.1 . FIRE PROTECTION REQUIREMENTS OF SECTION 912
 SHALL APPLY WHERE A BUILDING OR PORTIONS THEREOF
 UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION.
  
 EXST BLDG CODE 912.2 FIRE PROTECTION SYSTEMS. FIRE
 PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTIONS 912.2.1 AND 912.2.2.
  
 2A) EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE
 A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2007/09 FBC-B 903.2 WHERE REQUIRED. APPROVED AUTOMATIC
 SPRINKLER SYSTEMS IN NEW BUILDINGS AND STRUCTURES SHALL
 BE PROVIDED IN THE LOCATIONS DESCRIBED IN THIS SECTION.
 FBC-B 903.2.1.2 GROUP A-2. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED FOR GROUP A-2 OCCUPANCIES
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2).
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
 3. THE FIRE AREA IS LOCATED ON A FLOOR OTHER THAN THE
 LEVEL OF EXIT DISCHARGE.
 4. NIGHTCLUBS OR SIMILAR USAGE WHEN OCCUPANT LOAD IS
 100 OR MORE.
 903.3 INSTALLATION REQUIREMENTS. AUTOMATIC SPRINKLER
 SYSTEMS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH SECTIONS 903.3.1 THROUGH 903.3.7.
 903.4 SPRINKLER SYSTEM MONITORING AND ALARMS. ALL
 VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC
 SPRINKLER SYSTEMS, PUMPS, TANKS, WATER LEVELS AND
 TEMPERATURES, CRITICAL AIR PRESSURES AND WATER-FLOW
 SWITCHES ON ALL SPRINKLER SYSTEMS SHALL BE ELECTRICALLY
 SUPERVISED IN ACCORDANCE WITH NFPA 72.
 903.4.1 SIGNALS. ALARM, SUPERVISORY AND TROUBLE SIGNALS
 SHALL BE DISTINCTLY DIFFERENT AND AUTOMATICALLY
 TRANSMITTED TO AN APPROVED CENTRAL STATION, REMOTE
 SUPERVISING STATION OR PROPRIETARY SUPERVISING STATION
 AS DEFINED IN NFPA 72 OR, WHEN APPROVED BY THE FIRE
 CODE OFFICIAL, SHALL SOUND AN AUDIBLE SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION.
  
  
 2B) COMPLIED. FIRE ALAARM PLAANS WERE SUBMITTED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) MISSING PRODUCT APPROVALS FBC-B 1609 COMPONENTS &
 CLADDING, RULE 9N-3.
 5A-B) COMPLIED.
 5C) EXTERIER WALK IN COOLERS &/FREEZERS
  
 6-12) COMPLIED.
  
 13) PROVISO: A SEPERATE PREMIT IS REQUIRED. SHEET A-3 &
 A-4 INDICATE THE USE OF DRYWALL DROPED CEILING PANELS
 WITH LATTICE, A NOTE ON A-3 INDICATES METHOD OF
 ATTACHMENT, SUSPENSION BY OTHERS, THIS SYSTEM TO BE
 REVIEWED BY THE DESIGN PROFESSIONAL, IT CAN BE
 PERMITTED UNDER THIS PERMIT OR COME IN AS A STAND ALONE
 PERMIT. THE DROPPED CEILING WILL NEED TO SHOW
 COMPLIANCE WITH
 803.3 & 803.4.1 AND MEET THE FINISH REQUIREMENTS OF
 TABLE 803.5.
  
 14-15) COMPLIED.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-11-14 Cont ID  
Sent By jwitmer Date 2011-11-14 Time 16:04 Rev Time 1.11
Received By jwitmer Date 2011-11-14 Time 16:03 Sent To  
Notes
2011-11-14 16:55:55BUILDING PLAN REVIEW
 PERMIT: 11100370
 ADD: 215 CLEMATIS ST
 CONT: L B DEVELOPMENT
 TEL: (954)709-1926
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE MEZZANINE AND KITCHEN BELOW MUST MAINTAIN A
 FINISHED CEILING HEIGHT OF 7'-0" FBC-B 1208.2 EXCEPTION
 # 3.
  
 2) THE LAST KNOWN USE OF THIS SPACE WAS A DRESS SHOP
 MAKING THIS A CHANGE OF OCCUPANCY. THE 2007/09 FBC
 EXISTING BUILDING CODE CHAPTER 9 CHANGE OF OCCUPANCY
 SECTION EXST BLDG COE 904.1 . FIRE PROTECTION
 REQUIREMENTS OF SECTION 912 SHALL APPLY WHERE A
 BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE OF
 OCCUPANCY CLASSIFICATION.
  
 EXST BLDG CODE 912.2 FIRE PROTECTION SYSTEMS. FIRE
 PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTIONS 912.2.1 AND 912.2.2.
  
 2A) EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE
 A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2007/09 FBC-B 903.2 WHERE REQUIRED. APPROVED AUTOMATIC
 SPRINKLER SYSTEMS IN NEW BUILDINGS AND STRUCTURES SHALL
 BE PROVIDED IN THE LOCATIONS DESCRIBED IN THIS SECTION.
 FBC-B 903.2.1.2 GROUP A-2. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED FOR GROUP A-2 OCCUPANCIES
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2).
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
 3. THE FIRE AREA IS LOCATED ON A FLOOR OTHER THAN THE
 LEVEL OF EXIT DISCHARGE.
 4. NIGHTCLUBS OR SIMILAR USAGE WHEN OCCUPANT LOAD IS
 100 OR MORE.
 903.3 INSTALLATION REQUIREMENTS. AUTOMATIC SPRINKLER
 SYSTEMS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH SECTIONS 903.3.1 THROUGH 903.3.7.
 903.4 SPRINKLER SYSTEM MONITORING AND ALARMS. ALL
 VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC
 SPRINKLER SYSTEMS, PUMPS, TANKS, WATER LEVELS AND
 TEMPERATURES, CRITICAL AIR PRESSURES AND WATER-FLOW
 SWITCHES ON ALL SPRINKLER SYSTEMS SHALL BE ELECTRICALLY
 SUPERVISED IN ACCORDANCE WITH NFPA 72.
 903.4.1 SIGNALS. ALARM, SUPERVISORY AND TROUBLE SIGNALS
 SHALL BE DISTINCTLY DIFFERENT AND AUTOMATICALLY
 TRANSMITTED TO AN APPROVED CENTRAL STATION, REMOTE
 SUPERVISING STATION OR PROPRIETARY SUPERVISING STATION
 AS DEFINED IN NFPA 72 OR, WHEN APPROVED BY THE FIRE
 CODE OFFICIAL, SHALL SOUND AN AUDIBLE SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION.
  
  
 2B) EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING ,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
  
 3) PLEASE PROVIDE DOCUMENTATION FOR THE VERTICAL
 ACCESSIBILITY LIFT IN COMPLIANCE WITH FBC-B 11-4.11
 PLATFORM LIFTS MEETING THE REQUIREMENTS OF ASME A17.1.
  
 4) PLEASE PROVIDE A CURRENT SSURVEY, IT APPEARS THAT
 THE NEW BIFOLD FRONT ENTRY DOORS MAY CROSS THE PROPERTY
 LINE, NO DETERMINATION CAN BE MADE AT THIS TIME.
 2007/09 FBC-B 3202.2 DOORS AND WINDOWS SHALL NOT OPEN
 OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 5) MISSING PRODUCT APPROVALS FBC-B 1609 COMPONENTS &
 CLADDING, RULE 9N-3.
 5A) BI-FOLD DOOR SYSTEM, NOTE IS THIS SYSTEM
 ACCESSIBLE, BOTTOM TRACK?
 5B) FRONT SWING GLAZED ENTRY DOORS (PAIR)
 5C) EXTERIER WALK IN COOLERS &/FREEZERS
  
 6) WEST PALM BEACH ADMINISTRATIVE CODE (CHAPT 1).
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) THE COVER SHEET INDICATES THIS BUILDING TYPE TO BE
 CLASSIFIED AS A III-A STRUCTURE, FBC-B TABLE 601
 REQUIRES FIRE RATINGS FROM 1 HOUR OR MORE DEPENDING ON
 THE STRUCTURAL MEMBER, PLEASE ALSO REVIEW TABLE 602 FOR
 EXTERIOR WALL FIRE RATINGS AND ALLOWABLE OPENINGS TABLE
 704.8. THE BACK PROPERTY LINE IS AN UNKNOWN AT THIS
 TIME.
 PLEASE PROVIDE THE FIRE RATING OF THE STEEL BEAMS THAT
 ARE BEING SEATED WITHIN THE PROPERTY LINE WALL WHICH
 WOULD REQUIRE A 3 HR FIRE RATING WITHIN THE EXTERIOR
 WALL, SEE TABLE 602.
  
 8) PLEASE PROVIDE THE FLOOR LOADING DESIGN FOR LIVE
 LOADS FOR THE NEWLY RECONFIGURED AND FRAMED MEZZANINE
 LEVEL, NEW BALCONY AND STAIRWAY PER FBC-B TABLE 1607.1.
  
 9) NOTE THE PLANS INDICATE (COVERSHEET) THE MEZZANINE
 LEVEL TO HAVE AN OCCUPANT LOAD OF 39 PEOPLE, AND A
 TRAVEL DISTANCE LESS THAN 75 FEET WHICH WILL MEET THE
 EGRESS REQUIREMENTS OF OF FBC-B 505.3. NO OCCUPANT LOAD
 IS FIGURED FOR THE NEW BALCONY, IF FIGURED AS A DANCE
 FLOOR IT WILL PUT THE MEZZANINE LEVEL OVER 50 OCCUPANTS
 AND REQUIRE A SECOND MEANS OF EGRESS PER FBC-B TABLE
 1015.1.
  
 10) STAIRWAY CONSTRUCTION TO BE CONSTRUCTED OF THE SAME
 MATERIALS CONSISTANT WITH BUILDING TYPE. FBC-B 1009.5.
  
 11) SHEET A-2 NOTE 4 INDICATES THE USE OF WOOD DRODUCTS
 PLEASE BE AWARE OF FBC-B 602.3 EXTERIOR WALLS OF TYPE
 III ARE TO BE NONCOMBUSTIBLE, FIRE RETARDANT TREATED
 WOOD FRAMING COMPLYING WITH 2303.2 SHALL BE PERMITTED
 WITHIN EXTERIOR WALL ASSEMBLIES OF A 2 HOUR RATING OR
 LESS.
  
 12) SHEET A2 NOR THE STRUCTURAL SHEETS PROVIDE A
 DIMENSION OF THE CORRIDOR IN FRONT OF THE RESTROOMS.
 THE LADIES RESTROOM DOOR SWINGS OUT INTO THE CORRIDOR
 PLEASE PROVIDE DIMENSIONING OF THIS AREA AND IN
 COMPLIANCE WITH SECTION FBC-B 1008.1.8.8.
  
 13) SHEET A-3 & A-4 INDICATE THE USE OF DRYWALL DROPED
 CEILING PANELS WITH LATTICE, A NOTE ON A-3 INDICATES
 METHOD OF ATTACHMENT, SUSPENSION BY OTHERS, THIS SYSTEM
 TO BE REVIEWED BY THE DESIGN PROFESSIONAL, IT CAN BE
 PERMITTED UNDER THIS PERMIT OR COME IN AS A STAND ALONE
 PERMIT. THE DROPPED CEILING WILL NEED TO SHOW
 COMPLIANCE WITH
 803.3 & 803.4.1 AND MEET THE FINISH REQUIREMENTS OF
 TABLE 803.5.
  
 14) SHEET A5 NOTE INDICATEING WET AREAS TO HAVE MR
 BOARD, PLEASE REVIEW FBC-B WET AREAS 2509.1 SHALL
 CONFORM TO 1210.2 & 1210.3. PLEASE AALSO REVIEW 2509.2
 BASE FOR TILE.
  
 15) SHEET A-5 NOTES FOR CEILING INDICATE SEE R. C. P. ?
 ADDITIONAL INFORMATION REQUIRED. 106.1.2.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-27 Cont ID  
Sent By rlecky Date 2011-10-27 Time 14:04 Rev Time 0.00
Received By rlecky Date 2011-10-27 Time 11:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-01-11 Cont ID  
Sent By wjolin Date 2012-01-11 Time 12:52 Rev Time 0.00
Received By wjolin Date 2012-01-11 Time 11:44 Sent To  
Notes
2012-01-11 12:48:19215 CLEMATIS STREET
 PERMIT #11100370
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: SHEET A-2 (DOOR #2 AND #6): DURING ITS
 SWING, ANY DOOR IN A MEANS OF EGRESS SHALL PROJECT NOT
 MORE THAN 7-INCHES INTO THE REQUIRED WIDTH OF THE
 EGRESS PATH WHEN FULLY OPEN. WHEN FULLY OPEN THESE DOOR
 PROJECT MORE THAN 7-INCHES INTO THE CORRIDOR.
  
 REPEAT COMMENT: INTERIOR WALL FINISHES AND CEILING
 FINISHES SHALL MEET AT LEAST A CLASS C RATING FOR FLAME
 SPREAD AND SMOKE DEVELOPEMENT.
  
 PROVIDE DETAIL OR PRODUCT DATA FOR THE SUSPENDED WOOD
 TRELLIS. INDICATE IF ANY DECORATIONS, PLANTS, FABRICS,
 ETC. WILL BE USED TO DECORATE THE TRELLIS.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-20 Cont ID  
Sent By wjolin Date 2011-10-20 Time 13:01 Rev Time 0.00
Received By wjolin Date 2011-10-20 Time 11:22 Sent To  
Notes
2011-10-20 13:01:00215 CLEMATIS STREET
 PERMIT #11100370
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THIS IS A CHANGE OF OCCUPANCY FROM MERCANTILE TO
 ASSEMBLY.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 STRUCTURES WITH LIGHT FRAME FLOOR TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER "F" DESIGNATION
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 VERIFY NO OTHER LOCKS OR LATCHES ARE INSTALLED ON THE
 EXISTING EXIT DOORS WITH PANIC HARDWARE.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE STAIR AND HANDRAIL DETAILS.
  
 INTERIOR WALL AND CEILING FINISHES SHALL MEET AT LEAST
 A CLASS C RATING FOR FLAME SPREAD AND SMOKE
 DEVELOPEMENT.
  
 SHEET A-2: INDICATE THE LOCATIONS OF WHEELCHAIR
 SEATING.
  
 SHEET A-2 (DOOR #2 AND #6): DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL PROJECT NOT MORE THAN
 7-INCHES INTO THE REQUIRED WIDTH OF THE EGRESS PATH
 WHEN FULLY OPEN.
  
 SHEET A-4: HEADROOM SHALL BE NOT LESS THAN 7'-6" WITH
 PROJECTIONS FROM THE CEILING NOT LESS THAN 6'-8" ABOVE
 THE FLOOR. THE MINIMUM CEILING HEIGHT SHALL BE
 MAINTAINED FOR NOT LESS THAN TWO-THIRDS OF THE CEILING
 AREA OF ANY ROOM OR SPACE.
  
 SHEET FS-1.0: DEEP FAT FRYERS SHALL BE EQUIPPED WITH A
 SEPARATE HIGH-LIMIT CONTROL IN ADDITION TO THE
 ADJUSTABLE THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN
 THE FAT TEMPERATURE REACHES 475F DEGREES AT 1 INCH
 BELOW THE SURFACE.
  
 SHEET FS-1.0: PROVIDE AN 8? TALL STEEL BAFFLE OR
 PROVIDE 16? OF SPACE BETWEEN THE DEEP FAT FRYER AND
 SURFACE FLAMES OF THE ADJACENT EQUIPMENT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2011-11-01 Cont ID  
Sent By lwagner Date 2011-11-01 Time 09:59 Rev Time 0.00
Received By lwagner Date 2011-11-01 Time 09:49 Sent To  
Notes
2011-11-01 10:00:24SEPARATE GAS PERMIT REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-18 Cont ID  
Sent By jwitmer Date 2012-01-18 Time 11:42 Rev Time 0.00
Received By jwitmer Date 2011-12-29 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-11-16 Time 10:54 Rev Time 0.00
Received By shill Date 2011-10-19 Time 10:14 Sent To  
Notes
2011-10-19 10:15:03SENT TO C16 SHELF FOR REVIEW. (NO ROOM ON BOB BOARD).
 JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2012-01-18 Cont ID  
Sent By jwitmer Date 2012-01-18 Time 11:40 Rev Time 0.00
Received By jwitmer Date 2011-11-14 Time 16:04 Sent To  
Notes
2012-01-18 11:42:1101/18/2012 IMPACT FEE RECEIPT # 2012-0118-61
 FEES: $70.98
2011-11-14 16:04:57BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-01-13 Cont ID  
Sent By hmoser Date 2012-01-13 Time 10:24 Rev Time 0.00
Received By hmoser Date 2012-01-13 Time 08:40 Sent To  
Notes
2012-01-13 10:39:07PASS PROVISO
 1) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM 2007 FBC
 (M)
 2) REFER TO SECTION 606.3 INSTALLATION 2007 FBC (M)
 3) REFER TO SECTION 606.4.1 SUPERVISION 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER.
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-11-16 Cont ID  
Sent By hmoser Date 2011-11-16 Time 15:14 Rev Time 0.00
Received By hmoser Date 2011-11-16 Time 12:19 Sent To  
Notes
2011-11-16 15:11:15PLANS DENIED
 1) SEPARATE PLANS AND PERMIT REQUIRED FOR HOOD AND FIRE
 SUPPRESSION.
 2) REFER TO SECTION 304.10 GUARDS . IN REGARDS TO ROOF
 PLAN PAGE M2.1
 3) REFER TO SECTION 506.3.12.3 TERMINATION LOCATION. IN
 REGARDS TO GREASE DUCT
 ROOF PLAN PAGE M2.1
 4) AIR DISTRIBUTION SCHEDULE PAGE M6.1 DOES NOT MATCH
 THE PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-11-01 Cont ID  
Sent By lwagner Date 2011-11-01 Time 09:59 Rev Time 0.00
Received By lwagner Date 2011-10-31 Time 14:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-01-06 Cont ID  
Sent By aaponte Date 2012-01-06 Time 15:17 Rev Time 0.00
Received By aaponte Date 2012-01-06 Time 15:17 Sent To  
Notes
2012-01-06 15:21:33PROVISO: ANY NEW MECHANICAL EQUIPMENT LOCATED ON THE
 ROOF SHALL BE SCREENED FROM VIEW FROM THE STREET AND
 ALLEY LEVEL. A PERMIT FOR SCREENING, IF NECESSARY,
 SHALL BE SUBMITTED AND APPROVED BEFORE FINAL CO CAN BE
 ISSUED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-11-03 Cont ID  
Sent By aaponte Date 2011-11-03 Time 14:56 Rev Time 0.00
Received By aaponte Date 2011-11-03 Time 14:56 Sent To  
Notes
2011-11-03 14:56:101. REAR SETBACK IS 5 FEET. PLEASE INDICATE PROPERTY
 LINE ON THE DRAWINGS TO CONFIRM COMPLIANCE. NEW FREEZER
 MAY BE ENCROACHING INTO THE SETBACK.
 2.PLEASE INDICATE PROPERTY LINE ON DRAWINGS TO CONFIRM
 NEW FOLDING DOORS ARE NOT ENCROACHING INTO THE REQUIRED
 FRONT SETBACK.
 3. A SIDEWALK CAFE PERMTI WILL BE REQUIRED FOR THE
 TABLES ON THE SIDEWALK.
 4. BLANK WALLS ARE NOT PERMITTED. PLEASE PROVIDE REAR
 ELEVATION TO CONFIRM THE REMOVAL OF THE EXISTING
 OPENNINGS DO NOT MAKE THE REAR FACADE A BLANK WALL
 (SECTION 94-109 - BLANK WALL DEFINITION).L
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.