Plan Review Details - Permit 11100267
Plan Review Stops For Permit 11100267
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-12-12 Cont ID  
Sent By shill Date 2011-12-12 Time 11:00 Rev Time 0.00
Received By shill Date 2011-12-12 Time 11:00 Sent To  
Notes
2011-12-12 11:01:13****PROVISOS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 *** 32" OPENING TO BE PROVIDED AT ALL EXITS PER
 CONTRACTOR AND ARCHITECT ***
  
 "PERIMETER" INSTALLATION TO INCLUDE TWO 32" OPENINGS
 PERPENDICULAR TO PROTECTED OPENINGS
  
 "ANGLED" INSTALLATION TO BE INSTALLED IN A MANNER WHICH
 ALLOWS DOORS TO OPEN WITH 32" EXITING CLEAR WIDTH
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-12-05 Cont ID  
Sent By shill Date 2011-12-05 Time 10:43 Rev Time 0.00
Received By shill Date 2011-12-05 Time 10:43 Sent To  
Notes
2011-12-05 10:46:31****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 PLEASE HAVE ENGINEER'S LETTER REVISED TO ADDRESS
 INSTALLATION METHOD PROPOSED WHICH IS UNIQUE TO THIS
 JOB; SPECIFICALLY THE ISSUE OF "PERIMETER"
 INSTALLATIONS WITH 32" OPENINGS.
  
  
 PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISO:
  
 PROVISO
  
 *** 32" OPENING TO BE PROVIDED AT ALL EXITS PER
 CONTRACTOR AND ARCHITECT ***
  
 "PERIMETER" INSTALLATION TO INCLUDE TWO 32" OPENINGS
 PERPENDICULAR TO PROTECTED OPENINGS
  
 "ANGLED" INSTALLATION TO BE INSTALLED IN A MANNER WHICH
 ALLOWS DOORS TO OPEN WITH 32" EXITING
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-20 Cont ID  
Sent By shill Date 2011-10-20 Time 16:06 Rev Time 0.00
Received By shill Date 2011-10-20 Time 16:06 Sent To  
Notes
2011-10-20 16:20:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE INFORMATION REGARDING OCCUPANCY
 CLASSIFICATION. PLEASE ALSO SEE THE FOLLOWING CODE
 SECTIONS:
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  
 NOTE THAT THERE IS NO PROVISION FOR BLOCKING EXITS WITH
 HURRICANE PROTECTION FOR ANY OCCUPANCY OTHER THAN GROUP
 R, SEE FBC 1008.1.3.6.
  
 PLEASE EITHER REMOVE ALL DOORS FROM SCOPE OF WORK OR
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC CHAPTER 10.
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS OR TO EMAIL
 ADDITIONAL INFORMATION.
  
 2. PLEASE INCLUDE SPANS IN THE INSTALLATION SCHEDULE.
 FOR INSTANCE, A 96" OPENING WITH A 3" TOP AND BOTTOM
 EDGE DISTANCE WOULD HAVE A SPAN OF 102". REVISE ANCHOR
 SPACING IF NECESSARY.
  
 3. PLEASE EITHER REVISE HORIZONTAL OPENINGS TO A BLOCK
 SUBSTRATE OR PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THE SIDES OF THE WINDOW OPENINGS ARE
 CONCRETE. CBS STRUCTURES TYPICALLY HAVE EITHER HOLLOW
 OR FILLED CELLS AT THE OPENINGS, NOT FORMED AND POURED
 COLUMNS. REVISE ANCHOR SPACING IF NECESSARY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-10 Cont ID  
Sent By wjolin Date 2012-04-10 Time 09:47 Rev Time 0.00
Received By wjolin Date 2012-04-10 Time 09:29 Sent To  
Notes
2012-04-10 09:47:364200 NORTH AUSTRALIAN AVENUE
 PERMIT #11100267
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A LETTER DATED MARCH 20, 2012 (FROM MR. JAMES
 ROHWELLER) WAS SENT TO THE WPB BUILDING DEPARMENT
 CONCERNING THE USE OF FABRIC "ARMOR SCREEN" HURRICANE
 SHUTTERS TO COVER EXIT DOORS OF THE BUILDING. BECAUSE
 THE LETTER INDICATES THAT THE BUILDING COULD BE
 OCCUPIED BY GOVERNMENT WORKERS AND THEIR FAMILIES
 DURING A STORM EVENT, THE SHUTTERS STILL NEED TO ALLOW
 OCCUPANTS UNIMPEDED EGRESS FROM THE BUILDING. WHILE THE
 HURRICANE SHUTTER ITSELF IS NOT A DOOR, OPERATING THE
 SHUTTER NEEDS TO MEET THE MINIMUM LIFE SAFETY CODE
 REQUIREMENTS FOR DOORS SUCH AS:
  
 1) THE DEVICE SHALL NOT REQUIRE A TOOL, SPECIAL
 KNOWLEDGE OR EFFORT TO OPERATE.
 2) THE RELEASING DEVICE SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS.
 3) THE RELEASING MECHANISM SHALL BE LOCATED BETWEEN
 34"-48" ABOVE THE FLOOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-05 Cont ID  
Sent By shill Date 2011-12-05 Time 10:46 Rev Time 0.00
Received By shill Date 2011-11-28 Time 16:29 Sent To  
Notes
2011-11-28 16:30:06TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-20 Cont ID  
Sent By shill Date 2011-10-20 Time 16:20 Rev Time 0.00
Received By shill Date 2011-10-12 Time 07:37 Sent To  
Notes
2011-10-13 07:38:07SENT TO MISC 1 BOX