Plan Review Details - Permit 11100235
Plan Review Stops For Permit 11100235
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-11-04 Cont ID  
Sent By shill Date 2011-11-04 Time 13:01 Rev Time 0.00
Received By shill Date 2011-11-04 Time 13:01 Sent To E
Notes
2011-11-04 13:04:26****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. (NEW COMMENT, NEW SHEET) - SEE LS 1.00, NOT CLEAR
 HOW EXIT CAPACITY OF THE STAIR HAS BEEN DETERMINED. SEE
 FBC TABLE 1005.1.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-10-13 Cont ID  
Sent By jwitmer Date 2011-10-13 Time 10:21 Rev Time 0.77
Received By jwitmer Date 2011-10-13 Time 10:21 Sent To  
Notes
2011-10-13 10:33:15BUILDING PLAN REVIEW
 PERMIT: 11100235
 ADD: 777 S FLAGLER PENTHOUSE CLUB LEVEL EAST TOWER
 CONT: TBD
 TEL: (561)856-6655
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CONTRACTOR TO BE SIGNED ON WITH THE CORRECT
 LICENSURE BEFORE THE ISSUANCE OF THIS PERMIT.
  
 2) THE PERMIT APPLICATION INDICATES INSTALL NEW
 RAILING? IS THIS A REPLACEMENT OF EXISTING BALCONY
 RAILING? NO DETAILS WERE SUBMITTED FOR HEIGHT NOR FOR
 ANCHORING OR
 COMPLIANCE WITH 1013.1 NOR 1607.7.
  
 3) SHEET A-1.01 WIND DESIGN CRITERIA INDICATES +/- 850
 F.S.P., PLANS DO NOT GIVE AN ABBREVIATION SHEET
 INDICATING WHAT F.S.P. STANDS FOR. ADDITIONAL
 INFORMATION REQUIRED. 106.1.2.
  
 4) CONTRACTOR ONCE PICKED WILL NEED TO SUBMIT ARCH
 PRODUCT APPROVAL, CIRCLE THE GLAZING SYSTEM TO BE
 INSTALLED. COMPONENTS & CLADDING 1609.
  
 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-3 (OLD RULE 9B-72) SHALL
 BE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-11-04 Cont ID  
Sent By rlecky Date 2011-11-04 Time 16:28 Rev Time 0.00
Received By rlecky Date 2011-11-04 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-13 Cont ID  
Sent By rlecky Date 2011-10-13 Time 17:39 Rev Time 0.00
Received By rlecky Date 2011-10-13 Time 17:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-11-03 Cont ID  
Sent By wjolin Date 2011-11-03 Time 12:18 Rev Time 0.00
Received By wjolin Date 2011-11-03 Time 11:55 Sent To B
Notes
2011-11-03 12:18:27777 SOUTH FLAGLER DRIVE - EAST TOWER PENTHOUSE
 PERMIT #11100235
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE LIFE SAFETY PLAN INDICATES AN OCCUPANT LOAD OF 399
 PERSONS. USING A CAPACITY FACTOR OF 0.2 INCHES OF WIDTH
 PER PERSON FOR LEVEL COMPONENTS, THE TWO EXIT STAIR
 DOORS WOULD NEED A TOTAL CLEAR WIDTH OF 80 INCHES (399
 X 0.2 = 80). ONLY 69 INCHES OF EXIT STAIR WIDTH IS
 PROVIDED.
  
 INDICATE IF THE BALCONY DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-10-19 Cont ID  
Sent By wjolin Date 2011-10-19 Time 13:22 Rev Time 0.00
Received By wjolin Date 2011-10-19 Time 11:41 Sent To  
Notes
2011-10-19 13:21:43777 SOUTH FLAGLER DRIVE - EAST TOWER PENTHOUSE
 PERMIT #11100235
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED ON DRAWINGS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING THE OCCUPANT LOADS,
 EXIT STAIR LOCATIONS, STAIR DOOR CAPACITY AND TRAVEL
 DISTANCES FOR THE ENTIRE FLOOR. THIS FLOOR APPEARS TO
 HAVE TWO EXIT STAIRS. ADDING A BALCONY ASSEMBLY AREA
 WITH 50+ OCCUPANTS MAY EXCEED THE CURRENT EXIT CAPACITY
 OF THIS FLOOR.
  
 INDICATE THE ADA SEATING LOCATIONS.
  
 THE WIDTH OF AISLES SERVING SEATING AT TABLES SHALL BE
 NOT LESS THAN 44-INCHES WHERE SERVING AN OCCUPANT LOAD
 EXCEEDING 50; OR 36-INCHES WHERE SERVING AN OCCUPANT
 LOAD OF 50 OR FEWER.
  
 DOORS SERVING 50 OR MORE PERSONS SHALL SWING IN THE
 DIRECTION OF EGRESS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 INDICATE THE DOOR HARDWARE. THE RELEASING MECHANISM ON
 ALL DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE
 RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE
 AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 INDICATE LOCATIONS OF NEAREST EXISTING PORTABLE FIRE
 EXTINGUISHERS. TRAVEL DISTANCE TO EXTINGUISHERS SHALL
 NOT EXCEED 75 FEET.
  
 TWO FIRE ALARM SPEAKER/STROBES WILL NOT ADEQUATELY
 COVER THE ENTIRE BALCONY AREA.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-08 Cont ID  
Sent By shill Date 2011-11-08 Time 08:50 Rev Time 0.00
Received By shill Date 2011-11-02 Time 09:48 Sent To  
Notes
2011-11-04 13:26:38TO RL DESK (NEW ELEC SHEET)
  
2011-11-02 09:48:48**** EXPEDITED **** ROUND 2
 11/2 TO WJ DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-26 Cont ID  
Sent By lmartine Date 2011-10-26 Time 14:28 Rev Time 0.00
Received By lmartine Date 2011-10-12 Time 12:34 Sent To  
Notes
2011-10-12 12:39:45*******************EXPEDITED*********************
 B--6

Review Stop P PLUMBING
Rev No 1 Status N Date 2011-11-08 Cont ID  
Sent By lwagner Date 2011-11-08 Time 08:32 Rev Time 0.00
Received By lwagner Date 2011-11-08 Time 07:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-10-26 Cont ID  
Sent By aaponte Date 2011-10-26 Time 13:23 Rev Time 0.00
Received By aaponte Date 2011-10-26 Time 13:23 Sent To  
Notes
***NONE***