Plan Review Stops For Permit 11100235 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2011-11-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2011-11-04 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2011-11-04 |
Time |
13:01 |
Sent To |
E |
|
Notes |
2011-11-04 13:04:26 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. (NEW COMMENT, NEW SHEET) - SEE LS 1.00, NOT CLEAR | | HOW EXIT CAPACITY OF THE STAIR HAS BEEN DETERMINED. SEE | | FBC TABLE 1005.1. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2011-10-13 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2011-10-13 |
Time |
10:21 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2011-10-13 |
Time |
10:21 |
Sent To |
|
|
Notes |
2011-10-13 10:33:15 | BUILDING PLAN REVIEW | | PERMIT: 11100235 | | ADD: 777 S FLAGLER PENTHOUSE CLUB LEVEL EAST TOWER | | CONT: TBD | | TEL: (561)856-6655 | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) CONTRACTOR TO BE SIGNED ON WITH THE CORRECT | | LICENSURE BEFORE THE ISSUANCE OF THIS PERMIT. | | | | 2) THE PERMIT APPLICATION INDICATES INSTALL NEW | | RAILING? IS THIS A REPLACEMENT OF EXISTING BALCONY | | RAILING? NO DETAILS WERE SUBMITTED FOR HEIGHT NOR FOR | | ANCHORING OR | | COMPLIANCE WITH 1013.1 NOR 1607.7. | | | | 3) SHEET A-1.01 WIND DESIGN CRITERIA INDICATES +/- 850 | | F.S.P., PLANS DO NOT GIVE AN ABBREVIATION SHEET | | INDICATING WHAT F.S.P. STANDS FOR. ADDITIONAL | | INFORMATION REQUIRED. 106.1.2. | | | | 4) CONTRACTOR ONCE PICKED WILL NEED TO SUBMIT ARCH | | PRODUCT APPROVAL, CIRCLE THE GLAZING SYSTEM TO BE | | INSTALLED. COMPONENTS & CLADDING 1609. | | | | 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE | | REGULATED BY THE DCA RULE 9N-3 (OLD RULE 9B-72) SHALL | | BE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2011-11-04 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-11-04 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2011-11-04 |
Time |
16:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2011-10-13 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-10-13 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2011-10-13 |
Time |
17:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2011-11-03 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2011-11-03 |
Time |
12:18 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2011-11-03 |
Time |
11:55 |
Sent To |
B |
|
Notes |
2011-11-03 12:18:27 | 777 SOUTH FLAGLER DRIVE - EAST TOWER PENTHOUSE | | PERMIT #11100235 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE LIFE SAFETY PLAN INDICATES AN OCCUPANT LOAD OF 399 | | PERSONS. USING A CAPACITY FACTOR OF 0.2 INCHES OF WIDTH | | PER PERSON FOR LEVEL COMPONENTS, THE TWO EXIT STAIR | | DOORS WOULD NEED A TOTAL CLEAR WIDTH OF 80 INCHES (399 | | X 0.2 = 80). ONLY 69 INCHES OF EXIT STAIR WIDTH IS | | PROVIDED. | | | | INDICATE IF THE BALCONY DOORS WILL BE EQUIPPED WITH ANY | | LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A | | LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE | | RELEASED FROM THE EGRESS SIDE OF THE DOOR. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2011-10-19 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2011-10-19 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2011-10-19 |
Time |
11:41 |
Sent To |
|
|
Notes |
2011-10-19 13:21:43 | 777 SOUTH FLAGLER DRIVE - EAST TOWER PENTHOUSE | | PERMIT #11100235 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | NO ADDRESS PROVIDED ON DRAWINGS. | | | | PROVIDE A LIFE SAFETY PLAN SHOWING THE OCCUPANT LOADS, | | EXIT STAIR LOCATIONS, STAIR DOOR CAPACITY AND TRAVEL | | DISTANCES FOR THE ENTIRE FLOOR. THIS FLOOR APPEARS TO | | HAVE TWO EXIT STAIRS. ADDING A BALCONY ASSEMBLY AREA | | WITH 50+ OCCUPANTS MAY EXCEED THE CURRENT EXIT CAPACITY | | OF THIS FLOOR. | | | | INDICATE THE ADA SEATING LOCATIONS. | | | | THE WIDTH OF AISLES SERVING SEATING AT TABLES SHALL BE | | NOT LESS THAN 44-INCHES WHERE SERVING AN OCCUPANT LOAD | | EXCEEDING 50; OR 36-INCHES WHERE SERVING AN OCCUPANT | | LOAD OF 50 OR FEWER. | | | | DOORS SERVING 50 OR MORE PERSONS SHALL SWING IN THE | | DIRECTION OF EGRESS. | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | EXIT SIGNS. | | | | INDICATE THE DOOR HARDWARE. THE RELEASING MECHANISM ON | | ALL DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE | | RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE | | AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED | | UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE | | SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND | | SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR | | TWISTING OF THE WRIST TO OPERATE. | | | | INDICATE LOCATIONS OF NEAREST EXISTING PORTABLE FIRE | | EXTINGUISHERS. TRAVEL DISTANCE TO EXTINGUISHERS SHALL | | NOT EXCEED 75 FEET. | | | | TWO FIRE ALARM SPEAKER/STROBES WILL NOT ADEQUATELY | | COVER THE ENTIRE BALCONY AREA. | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | MODIFICATION OF THE FIRE ALARM SYSTEM. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2011-11-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2011-11-08 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2011-11-02 |
Time |
09:48 |
Sent To |
|
|
Notes |
2011-11-04 13:26:38 | TO RL DESK (NEW ELEC SHEET) | | | 2011-11-02 09:48:48 | **** EXPEDITED **** ROUND 2 | | 11/2 TO WJ DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2011-10-26 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2011-10-26 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2011-10-12 |
Time |
12:34 |
Sent To |
|
|
Notes |
2011-10-12 12:39:45 | *******************EXPEDITED********************* | | B--6 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2011-11-08 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2011-11-08 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2011-11-08 |
Time |
07:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2011-10-26 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2011-10-26 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2011-10-26 |
Time |
13:23 |
Sent To |
|
|
Notes |
|
|