2011-11-30 15:48:43 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| FROM PREVIOUS LIST: |
| |
| 1. PROVIDE INFORMATION REGARDING THE LOCATION OF THE |
| ACCESSIBLE ENTRANCE(S), FBC11 4.3.2, FBC 11 4. |
| |
| 2. FBC 11 4.3.2, SHOW ACCESSIBLE ROUTE FROM THE PUBLIC |
| WAY TO THE ACCESSIBLE BUILDING ENTRANCE. |
| |
| 3. OK |
| |
| 4. FBC 11 4.6.2, ACCESSIBLE PARKING SPACES SERVING A |
| PARTICULAR BUILDING SHALL BE LOCATED ON THE SHORTEST |
| SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| TO AN ACCESSIBLE ENTRANCE. |
| |
| 2ND REVIEW, PLEASE SHOW THE ACCESSIBLE ENTRANCES. |
| PROXIMITY OF THE ACCESSIBLE SPACES TO THE ENTRANCE(S) |
| CANNOT BE DETERMINED. IF THERE IS MORE THAN ONE |
| ADJACENT PARKING AREA, ACCESSIBLE PARKING IS TO BE |
| DISPERSED. |
| |
| 5. ADVISORY ONLY, THE FOLLOWING WEBSITE MAY BE |
| INFORMATIVE: |
| HTTP://WWW.ADA.GOV/RESTRIPE.PDF |
| |
| PLEASE NOTE THAT ADA AND THE FLORIDA BUILDING CODE |
| CONSIDERS RESTRIPING "NEW CONSTRUCTION." |
| |
| 6. THE DESIGNER TAKING RESPONSIBILITY FOR THIS DESIGN |
| AND INFORMATION (AND CERTIFYING AS TO CODE COMPLIANCE) |
| IS TO PROVIDE HIS/HER NAME AND SIGNATURE ON THE PLAN. |
| |
| 2ND REVIEW, IT APPEARS THAT THE CONTRACTOR HAS REVISED |
| THE ENGINEER'S SEALED PLAN. IF THE CONTRACTOR IS TAKING |
| RESPONSIBILITY FOR THE DESIGN, PLEASE PROVIDE PRINTED |
| NAME, SIGNATURE, AND LICENSE NUMBER ON THE PLAN. |
| |
| 7. PLEASE REVISE PLAN TO INCLUDE TOTAL NUMBER OF |
| PARKING SPACES AND NUMBER OF ACCESSIBLE SPACES, FBC |
| 11-4. |
| |
| SEE FBC 11-4.1.2(5)(A), FOUR SPACES REQUIRED, THREE |
| SHOWN. |
| |
| PLEASE NOTE THAT THE ENGINEER IS IN CONVERSATIONS WITH |
| PLANS EXAMINER IN ORDER TO RESOLVE OUTSTANDING DESIGN |
| ISSUES. |
| |
| |
| |
| |