Plan Review Stops For Permit 11090634
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-09-27 Cont ID  
Sent By wjolin Date 2011-09-27 Time 13:03 Rev Time 0.00
Received By wjolin Date 2011-09-27 Time 11:42 Sent To M
Notes
2011-09-27 11:56:44777 SOUTH FLAGLER DRIVE - SUITE #1600W
 PERMIT #11090634
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 PROVIDE SUITE NUMBER ON PLANS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT. MODIFY HANGER LOCATION DETAIL TO
 ACCOUNT FOR SYSTEM PRESSURES ABOVE 100 PSI.
  
 INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS
 FLOOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-30 Cont ID  
Sent By hmoser Date 2011-09-30 Time 10:35 Rev Time 0.00
Received By hmoser Date 2011-09-26 Time 10:27 Sent To  
Notes
2011-09-26 10:28:02IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-09-30 Cont ID  
Sent By hmoser Date 2011-09-30 Time 10:35 Rev Time 0.00
Received By hmoser Date 2011-09-30 Time 10:30 Sent To  
Notes
***NONE***