Plan Review Stops For Permit 11090607 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2011-09-29 |
|
|
Cont ID |
|
Sent By |
ddaniels |
Date |
2011-09-28 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
ddaniels |
Date |
2011-09-28 |
Time |
11:40 |
Sent To |
M |
|
Notes |
2011-09-28 12:06:05 | 1500 NORTH FLORIDA MANGO ROAD | | PERMIT # 11090607 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1. FOR SYSTEM PRESSURES EXCEEDING 100 PSI, PENDENT | | SPRINKLERS SHALL BE PROTECTED FROM UPWARD MOVEMENT. | | HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF THE DROP | | ELBOW. INDICATE THE HANGER TYPE OR METHOD TO BE USED | | FOR RESTRAINING UPWARD MOVEMENT. | | | | 2.INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS | | FLOOR. | | | | DERRICK L. DANIELS, BATTALION CHIEF | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | (561) 805-6733 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2011-10-04 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2011-10-04 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2011-09-23 |
Time |
14:15 |
Sent To |
|
|
Notes |
2011-09-23 14:16:02 | SENT TO FIRE SHELF FOR REVIEW. JG. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2011-10-04 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2011-10-04 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2011-10-04 |
Time |
08:58 |
Sent To |
|
|
Notes |
|
|
|