2011-09-16 14:59:15BUILDING PLAN REVIEW
 PERMIT: 11090302
 ADD: 1450 CENTREPARK DR # 250
 CONT: FISHER CONTRACTING
 TEL: (561)691-4716
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
 SHEET A-2
 1) PLEASE SEE TRAINING ROOM # 108 WITH 52 SEATS AND A
 SINGLE EXIT. PLEASE REVIEW 2007/09 FBC-B TABLE 1015.1
 WHICH REQUIRES 2 EXIT DOORS WITH AN BUSINESS OCCUPANT
 LOAD GREATER THAN 49.
  
 2) THE TWO DOORS OF TRAINING ROOM # 108 WILL ALSO NEED
 TO SWING IN THE DIRECTION OF TRAVEL PER 2007/09 FBC-B
 SECTION 1008.1.2.
  
 3) THE EXIT DOOR AT COORIDOR DOOR # 106 WOULD ALSO NEED
 TO SWING INTHE DIRECTION OF TRAVEL. SECTION 1008.1.2.
  
 4) PLANS INDICATE THE USE OF CARD READERS PLEASE
 PROVIDE COMPLIANCE WITH SECTION 1008.1.8.6.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-10-05 Cont ID  
Sent By rlecky Date 2011-10-05 Time 08:51 Rev Time 0.00
Received By rlecky Date 2011-10-05 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-20 Cont ID  
Sent By rlecky Date 2011-09-20 Time 10:31 Rev Time 0.00
Received By rlecky Date 2011-09-19 Time 15:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-10-04 Cont ID  
Sent By wjolin Date 2011-10-04 Time 09:59 Rev Time 0.00
Received By wjolin Date 2011-10-04 Time 09:31 Sent To  
Notes
2011-10-04 09:59:201450 CENTREPARK DRIVE - SUITE #250
 PERMIT #11090302
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 SHEET A-2 INDICATES THE TENANT WILL PROVIDE CARD ACCESS
 DRAWINGS. PLEASE NOTE SEVERAL INTERIOR EXIT ACCESS
 DOORS ARE FITTED WITH CARD READERS THAT WOULD PROHIBIT
 OCCUPANTS FREE EGRESS THROUGHOUT THE TENANT SPACE. THE
 CURRENT CARD READER LOCATIONS WILL NOT BE APPROVED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-09-15 Cont ID  
Sent By wjolin Date 2011-09-15 Time 11:22 Rev Time 0.00
Received By wjolin Date 2011-09-15 Time 10:26 Sent To  
Notes
2011-09-15 11:12:311450 CENTREPARK DRIVE - SUITE #250
 PERMIT #11090302
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE. SEVERAL INTERIOR EXIT ACCESS DOORS ARE
 FITTED WITH CARD READERS THAT WOULD PROHIBIT OCCUPANTS
 FREE EGRESS THROUGHOUT THE TENANT SPACE.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 TRAINING ROOM #108 AND CORRIDOR #106 DOORS ARE REQUIRED
 TO SWING IN THE DIRECTION OF EGRESS TRAVEL FOR AN
 OCCUPANT LOAD OF 50 OR GREATER PERSONS PER SECTION
 7.2.1.4.2 OF THE FLORIDA FIRE PREVENTION CODE: NFPA 101
 - LIFE SAFETY CODE.
  
 TRAINING ROOM #108 HAS AN OCCUPANT LOAD EXCEEDING 50
 PERSONS AND THEREFORE WOULD BE CONSIDERED AN ASSEMBLY
 OCCUPANCY. A SECOND EXIT FROM THIS ROOM REQUIRED AS THE
 COMMON PATH OF TRAVEL EXCEEDS 20 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET E-1: AN ADDITIONAL FIRE ALARM NOTIFICATION
 APPLIANCE IS NEEDED IN CORRIDOR #106 AND OPEN OFFICE
 #116 AS THE EXISTING DEVICE WILL NOT COVER THIS ENTIRE
 SPACE. ALSO, IT WILL BE DIFFICULT TO MEET THE DB
 REQUIREMENT IN TRAINING ROOM #108 WITH A STROBE ONLY
 NOTIFICATION APPLIANCE.
  
 SHEET E-1: NO NOTIFICATION APPLIANCES LOCATED IN OTHER
 COMMON AREAS: COPY #112, MEETING ROOMS #102, #103 AND
 #115.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2011-11-01 Time   Rev Time 0.00
Received By shill Date 2011-09-30 Time 16:29 Sent To  
Notes
2011-09-30 16:29:22B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-26 Cont ID  
Sent By lmartine Date 2011-09-27 Time   Rev Time 0.00
Received By lmartine Date 2011-09-14 Time 13:32 Sent To  
Notes
2011-09-14 13:33:20B13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-01 Cont ID  
Sent By rregueir Date 2011-11-01 Time 14:09 Rev Time 0.00
Received By rregueir Date 2011-10-26 Time 13:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-09-27 Cont ID  
Sent By hmoser Date 2011-09-27 Time 09:20 Rev Time 0.00
Received By hmoser Date 2011-09-26 Time 15:09 Sent To  
Notes
2011-09-27 09:18:54PLANS DENIED
 PROVIDE DUCT SIZE AND GRILL SIZE FOR TRAINING ROOM #
 105
 AND BRAKE ROOM # 107 .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-09-20 Cont ID  
Sent By lwagner Date 2011-09-20 Time 14:42 Rev Time 0.00
Received By lwagner Date 2011-09-20 Time 14:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-10-03 Cont ID  
Sent By jroach Date 2011-10-03 Time 08:46 Rev Time 0.00
Received By jroach Date 2011-10-03 Time 08:46 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved