Plan Review Details - Permit 11090174
Plan Review Stops For Permit 11090174
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-10-19 Cont ID  
Sent By rlecky Date 2011-10-19 Time 16:46 Rev Time 0.00
Received By rlecky Date 2011-10-19 Time 16:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-09-12 Cont ID  
Sent By rlecky Date 2011-09-12 Time 11:15 Rev Time 0.00
Received By rlecky Date 2011-09-12 Time 11:08 Sent To  
Notes
2011-09-12 11:38:1411090174
 1698 OLD OKEECHOBEE ROAD
 480 VOLT SERVICE
  
 PLEASE ADVISE HOW THIS INSTALLATION WILL COMPLY WITH
 THE FOLLOWING CODE SECTIONS:
  
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE. NEC 230.2
 EACH SERVICE DROP OR LATERAL SHALL SUPPLY ONLY ONE SET
 OF SERVICE ENTRANCE CONDUCTORS. NEC 230.40
 VERIFY THERE ARE NOT MORE THAN SIX SETS OF DISCONNECTS
 PER SERVICE GROUPED IN ANY ONE LOCATION. NEC 210.71
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-19 Cont ID  
Sent By rlecky Date 2011-10-19 Time 16:46 Rev Time 0.00
Received By rlecky Date 2011-10-18 Time 15:43 Sent To  
Notes
2011-10-18 15:43:30TO ELEC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-12 Cont ID  
Sent By rlecky Date 2011-09-12 Time 11:36 Rev Time 0.00
Received By rlecky Date 2011-09-09 Time 17:51 Sent To  
Notes
2011-09-09 17:51:31IN ELECTRIC BOX