Plan Review Details - Permit 11080581
Plan Review Stops For Permit 11080581
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-08-26 Cont ID  
Sent By wjolin Date 2011-08-26 Time 13:29 Rev Time 0.00
Received By wjolin Date 2011-08-26 Time 13:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-24 Cont ID  
Sent By wjolin Date 2011-08-24 Time 09:27 Rev Time 0.00
Received By wjolin Date 2011-08-24 Time 09:06 Sent To  
Notes
2011-08-24 09:27:531500 NORTH FLORIDA MANGO ROAD
 TRACKING #11080581
 PERMIT #11050147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TWO SPRINKLERS ARE SPACED 16 FEET APART IN THE
 NORTHWEST AREA OF THE LARGE OPEN OFFICE SPACE.
  
 SPRINKLER IS LOCATED MORE THAN 7'-6" FROM OFFICE WALL
 IN THE NORTHEAST CORNER OF THE BUILDING. SMALL ROOM
 RULE CANNOT APPLY AS SPACE IS LARGER THAN 800 SQUARE
 FEET.
  
 INADEQUATE SPRINKLER PROTECTION FOR AREA JUST OUTSIDE
 OF SMALL OFFICE ON THE EAST SIDE OF THE BUILDING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-26 Cont ID  
Sent By wjolin Date 2011-08-26 Time 13:29 Rev Time 0.00
Received By wjolin Date 2011-08-26 Time 13:22 Sent To  
Notes
2011-08-25 14:12:14*******************EXPEDITED******************
 2ND RUN
 GAVE TO WESLEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-24 Cont ID  
Sent By wjolin Date 2011-08-24 Time 09:28 Rev Time 0.00
Received By wjolin Date 2011-08-22 Time 08:19 Sent To  
Notes
2011-08-22 08:20:09****************EXPEDITED*******************
 PUT I N WESLEY'S POD