Plan Review Details - Permit 11080500
Plan Review Stops For Permit 11080500
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-10-20 Cont ID  
Sent By rmcdouga Date 2011-10-20 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2011-10-20 Time 11:20 Sent To  
Notes
2011-10-20 11:26:22REVISION REQUIRED
  
 THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE FIXED
 GLASS WINDOWS HAVE A MAXIMUM SIZE OF 48" X 96" AND THE
 PLANS SPECIFY 90" X 69" WINDOWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-23 Cont ID  
Sent By rmcdouga Date 2011-08-23 Time 09:13 Rev Time 0.00
Received By rmcdouga Date 2011-08-23 Time 06:54 Sent To  
Notes
2011-08-23 09:13:182007 FBC W/2009 REVISIONS
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 2) THE EXPOSURE CATEGORY SPECIFIED ON SHEET 1 IS
 INCORRECT. THE STRUCTURE IS LOCATED IN EXPOSURE 'C' PER
 FBC R301.2.1.4.2.
  
 3) REVISE THE DESIGN WIND PRESSURES FOR THE WINDOWS AND
 DOORS ON SHEET 1 TO CORRESPOND WITH EXPOSURE 'C'. FBC
 R301.2.1
  
 4) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 FLORIDA ROOM AS REQUIRED BY FBCR N1100. THE FORMS ARE
 REQUIRED TO BE SIGNED BY THE PREPARER AND THE
 OWNER/AGENT.
  
 5) SPECIFY THE WALL AND CEILING INSULATION FOR THE
 FLORIDA ROOM ON THE PLANS.
  
 6) PROVIDE DETAILS AND SECTIONS OF THE EXISTING FLORIDA
 ROOM INCLUDING THE EXISTING FOUNDATION, WALLS, CEILING
 HEIGHT, ROOF TO WALL CONNECTIONS AND ROOF STRUCTURE (
 INCLUDE OVERHANG, ROOF PITCH, ROOF COVERING, ATTIC
 VENTING, ETC.) FBC R301.1, R401, R601, R801 AND R901
  
 7) SHOW COMPLIANCE WITH FBC R403.1.4 FOR MINIMUM
 FOUNDATION DEPTH OF 12" BELOW GRADE.
  
 8) SHOW COMPLIANCE WITH FBC R404.1.6 WHICH REQUIRES THE
 CONCRETE FOUNDATION TO EXTEND 4" ABOVE GRADE.
  
 9) THE PRODUCT APPROVAL FOR THE PGT FIXED WINDOW
 (PW-701), NOA NO. 08-1112.10 HAS BEEN SUPERSEDED. THE
 CURRENT ONE IS NOA NO. 10-0504.05. SUBMIT THE CURRENT
 NOA THAT HAS BEEN REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD. THE CURRENT NOAS CAN BE FOUND
 AT THE FOLLOWING WEB SITE :
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
  
 10) THE INSTALLATION DRAWINGS FOR THE PGT SLIDING GLASS
 DOOR PRODUCT APPROVAL NOA ARE MISSING HALF OF EACH
 PAGE. THE COMPLETE DRAWINGS ARE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-10-18 Cont ID  
Sent By rlecky Date 2011-10-18 Time 09:42 Rev Time 0.00
Received By rlecky Date 2011-10-18 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-08-23 Cont ID  
Sent By rlecky Date 2011-08-23 Time 12:25 Rev Time 0.00
Received By rlecky Date 2011-08-23 Time 12:25 Sent To  
Notes
2011-08-23 13:37:3811080500
 1320 WILDERNESS DR
 FLORIDA ROOM RENOVATION
  
 PLEASE SUBMIT A PLAN SHOWING THE REQUIRED ELECTRICAL
 OUTLETS FOR THE NEW LIVING AREA.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52
 THE NEW LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR
 LIGHT AND A SWITCHED LIGHT AT OUTSIDE ENTRANCES. AT
 LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE. NEC 210.70
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-20 Cont ID  
Sent By rmcdouga Date 2011-10-20 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2011-10-06 Time 15:58 Sent To  
Notes
2011-10-06 15:58:44R--7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-06 Cont ID  
Sent By lmartine Date 2011-08-29 Time 15:58 Rev Time 0.00
Received By lmartine Date 2011-08-19 Time 10:07 Sent To  
Notes
2011-08-19 10:07:37R7
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-10-20 Cont ID  
Sent By rmcdouga Date 2011-10-20 Time 10:06 Rev Time 0.00
Received By rmcdouga Date 2011-10-20 Time 10:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-08-23 Cont ID  
Sent By rmcdouga Date 2011-08-23 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2011-08-23 Time 07:31 Sent To  
Notes
2011-08-23 07:43:062007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) NO MECHANICAL PLANS WERE SUBMITTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-10-17 Cont ID  
Sent By eschneid Date 2011-10-17 Time 16:39 Rev Time 0.25
Received By eschneid Date 2011-10-17 Time 16:39 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-08-29 Cont ID  
Sent By eschneid Date 2011-08-29 Time 18:28 Rev Time 0.50
Received By eschneid Date 2011-08-29 Time 18:28 Sent To  
Notes
2011-08-29 18:31:24FAILED
  
 1) PROVIDE A SURVEY OR SITE PLAN WHICH SHOWS THE NEW
 CONSTRUCTION AND THE SETBACKS OF THE NEW CONSTRUCTION
 TO THE PROPERTY LINES.
  
 2) PLEASE NOTE THAT THE FLOOR PLAN SHOWS A SIDE LOADED
 GARAGE, YET THE SURVEY SHOWS THIS AS A FRONT LOAD
 MODEL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.