Plan Review Details - Permit 11080473
Plan Review Stops For Permit 11080473
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-08-22 Cont ID  
Sent By jwitmer Date 2011-08-22 Time 15:20 Rev Time 0.77
Received By jwitmer Date 2011-08-22 Time 15:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-06 Cont ID  
Sent By rlecky Date 2011-09-06 Time 15:31 Rev Time 0.00
Received By rlecky Date 2011-09-06 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-19 Cont ID  
Sent By wjolin Date 2011-08-19 Time 12:46 Rev Time 0.00
Received By wjolin Date 2011-08-19 Time 12:23 Sent To  
Notes
2011-08-19 12:46:03525 OKEECHOBEE BOULEVARD - 8TH FLOOR
 PERMIT #11080473
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE SPRINKLERS AND FIRE ALARM NOTIFICATION APPLIANCES
 WILL NEED TO BE ADDED AND/OR RELOCATED TO ACCOUNT FOR
 THE NEW WALLS. SEPARATE PLANS AND PERMITS ARE REQUIRED
 FOR THE INSTALLATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM AND FIRE ALARM SYSTEM.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 EXIT SIGN LOCATIONS NOT INDICATED ON PLANS. FIELD
 INSPECTOR MAY REQUIRE ADDITIONAL EXIT SIGNS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-06 Cont ID  
Sent By rlecky Date 2011-09-06 Time 15:32 Rev Time 0.00
Received By rlecky Date 2011-08-18 Time 10:57 Sent To  
Notes
2011-08-18 10:59:10SENT TO B2 FOR ALL TRADES REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2011-09-06 Cont ID  
Sent By hmoser Date 2011-09-06 Time 14:28 Rev Time 0.00
Received By hmoser Date 2011-09-06 Time 14:22 Sent To  
Notes
2011-09-06 14:34:46NO MECHANICAL PLANS SUBMITTED . IF THERE IS MECHANICAL
 WORK HAVE THE MECHANICAL CONTRACTOR
 PROVIDE APPLICATION AND PLANS FOR PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2011-08-18 Cont ID  
Sent By eschneid Date 2011-08-18 Time 17:30 Rev Time 0.25
Received By eschneid Date 2011-08-18 Time 17:29 Sent To  
Notes
2011-08-18 17:30:32INTERIOR RENOVATION. CPD PLAN MEETS CURRENT LANDSCAPE
 STANDARDS.