Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-09-27 Cont ID  
Sent By wjolin Date 2011-09-27 Time 10:48 Rev Time 0.00
Received By wjolin Date 2011-09-27 Time 09:59 Sent To M
Notes
2011-09-27 10:44:362223 PALM BEACH LAKES BOULEVARD - SUITE #103
 PERMIT #11080365
 MASTER #11040096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 REPEAT COMMENT: THE SPRINKLERS LOCATED IN THE PREP ROOM
 AND SMALL STORAGE ROOM SHOW S X L DIMENSIONS THAT
 RESULTS IN SPRINKLER COVERAGES IN EXCESS OF 130 SQUARE
 FEET PER SPRINKLER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-17 Cont ID  
Sent By wjolin Date 2011-08-17 Time 09:46 Rev Time 0.00
Received By wjolin Date 2011-08-17 Time 08:52 Sent To M
Notes
2011-08-17 09:46:412223 PALM BEACH LAKES BOULEVARD - SUITE #103
 PERMIT #11080365
 MASTER #11040096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ADDRESS ON PLANS DOES NOT MATCH THE ADDRESS ON THE
 PERMIT APPLICATION.
  
 THE JOB VALUE ON THE PERMIT APPLICATION APPEARS TO BE
 UNDERVALUED AT $31.25 PER SPRINKLER. JOB VALUE SHALL
 INCLUDE ALL MATERIALS AND LABOR. SUBMIT A COPY OF THE
 SIGNED CONTRACT.
  
 FLORIDA STATUES REQUIRE THE SPRINKLER DESIGN TO BE
 SIGNED AND SEALED BY A PROFESSIONAL ENGINEER WHEN THE
 SPRINKLER INSTALLATION/MODIFICATION EFFECTS MORE THAN
 49 SPRINKLERS.
  
 THE PLANS INDICATE THE DESIGN IS LIGHT HAZARD; HOWEVER,
 THE MASTER PERMIT (#11040096) INDICATES THIS SPACE WILL
 BE A FURNITURE STORE WHICH WOULD HAVE A FUEL LOAD
 EXCEEDING WHAT WOULD BE EXPECTED FOR A LIGHT HAZARD
 OCCUPANCY. THE PLANS INDICATE STANDARD RESPONSE
 SPRINKLERS; IF THIS SPACE IS NOT A FURNITURE STORE, AND
 THE HAZARD IS ACTUALLY LIGHT HAZARD, THEN
 QUICK-RESPONSE TYPE SPRINKLERS WOULD BE APPROPRIATE.
 VERIFY THE INTENDED USE OF THIS SPACE.
  
 NO WATER SUPPLY OR HYDRANT FLOW TEST INFORMATION
 PROVIDED ON THE PLANS.
  
 NO SPRINKLER PROTECTION PROVIDED IN SMALL CLOSET NEAR
 REAR OF BUILDING.
  
 THE SPRINKLER IN THE EXISTING STORAGE ROOM IS LOCATED
 MORE THAN 7'-6" FROM THE WALL.
  
 THE SPRINKLER IN THE MEN'S RESTROOM IS LOCATED MORE
 THAN 9 FEET FROM THE WALL.
  
 THE SPRINKLERS LOCATED IN THE PREP ROOM AND STORAGE
 ROOMS ARE INDICATED AS NOT BEING IN THE CONTRACT. THESE
 SPRINKLERS ARE PROTECTING MORE THAN 130 SQUARE FEET AND
 SHOULD BE CORRECTED.
  
 THE SPRINKLERS TO THE LEFT OF THE EXISTING PREP ROOM
 ARE LOCATED MORE THAN 7'-6" FROM THE WALL.
  
 ONLY ONE SYMBOL IS PROVIDED SPRINKLER SCHEDULE; TWO
 SYMBOLS APPEAR ON THE PLAN.
  
 THE SPRINKLER CUT SHEET SUBMITTED DOES NOT MATCH THE
 SPRINKLER SCHEDULE INFORMATION (TY-FRB/TY-B).
  
 THE WOMEN'S BATHROOM IS PART OF THE MASTER PERMIT SCOPE
 OF WORK, BUT THE SPRINKLER PLAN INDICATES THIS IS NOT
 IN THE SCOPE OF SPRINKLER WORK. VERIFY.
  
 ANY PARTIAL HEIGHT WALLS WITH CEILINGS WILL REQUIRE
 SPRINKLERS TO BE LOCATED AT THE STRUCTURE. VERIFY ALL
 EXPOSED STRUCTURE TO BE PROTECTED BY SPRINKLERS WITHIN
 12-INCHES OF THE ROOF DECK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-03 Cont ID  
Sent By hmoser Date 2011-10-03 Time 12:26 Rev Time 0.00
Received By hmoser Date 2011-09-22 Time 16:21 Sent To  
Notes
2011-09-22 16:22:09TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-22 Cont ID  
Sent By hmoser Date 2011-08-22 Time 15:57 Rev Time 0.00
Received By hmoser Date 2011-08-15 Time 07:21 Sent To  
Notes
2011-08-15 07:22:04SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-10-03 Cont ID  
Sent By wjolin Date 2011-10-03 Time 10:50 Rev Time 0.00
Received By hmoser Date 2011-10-03 Time 12:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-08-22 Cont ID  
Sent By hmoser Date 2011-08-22 Time 15:57 Rev Time 0.00
Received By hmoser Date 2011-08-22 Time 15:45 Sent To  
Notes
2011-08-22 15:56:56PLANS DENIED
 CAN'T READ JOIST PIPE HANGER DETAIL OR
 TYPICAL HANGER DETAIL ON THE PLANS.
 ADDRESS ON THE PLANS DO NOT MATCH THE ADDRESS
 ON THE APPLICATION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]