Plan Review Details - Permit 11080351
Plan Review Stops For Permit 11080351
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-08-12 Cont ID  
Sent By rlecky Date 2011-08-12 Time 15:16 Rev Time 0.00
Received By rlecky Date 2011-08-12 Time 15:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-08-12 Cont ID  
Sent By rlecky Date 2011-08-12 Time 13:58 Rev Time 0.00
Received By rlecky Date 2011-08-12 Time 13:58 Sent To  
Notes
2011-08-12 14:11:58REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES A
 SWITCHED RECEPTACLE OR LIGHT. AT LEAST ONE GFCI
 PROTECTED RECEPTACLE IS REQUIRED AT FRONT AND REAR. NEC
 210.70
 PROVIDE A BRANCH CIRCUIT FOR THE BATHROOMS. NEC 210.11
 (C)(3)
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND A SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
 INDICATE THE LOCATION OF THE ELECTRIC SERVICE AND
 PANELBOARD ON THE PLAN. NEC 110.26
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2011-08-12 Cont ID  
Sent By rlecky Date 2011-08-12 Time 15:16 Rev Time 0.00
Received By rlecky Date 2011-08-12 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-12 Cont ID  
Sent By rlecky Date 2011-08-12 Time 14:12 Rev Time 0.00
Received By rlecky Date 2011-08-11 Time 17:38 Sent To  
Notes
2011-08-12 09:55:22TO ELECTRICAL
  
2011-08-11 17:38:11TO SEW FOR OWNER CHANGE
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved