Plan Review Details - Permit 11080116
Plan Review Stops For Permit 11080116
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-09-16 Cont ID  
Sent By jwitmer Date 2011-09-16 Time 08:34 Rev Time 0.50
Received By jwitmer Date 2011-09-16 Time 08:34 Sent To  
Notes
2011-09-16 08:35:03FITNESS CENTER/ TRUSS ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-07 Cont ID  
Sent By jwitmer Date 2011-09-07 Time 12:32 Rev Time 0.77
Received By jwitmer Date 2011-09-07 Time 12:32 Sent To  
Notes
2011-09-07 12:33:34REVISIONS DATED : 8/17/11 & 5 PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-08-17 Cont ID  
Sent By jwitmer Date 2011-08-17 Time 09:29 Rev Time 1.00
Received By jwitmer Date 2011-08-17 Time 09:29 Sent To  
Notes
2011-08-17 09:30:30BUILDING PLAN REVIEW
 PERMIT: 11080116
 ADD: 4200 N FLAGLER
 CONT: BENCHMARK III CORP.
 TEL: (561)722-5095
  
 2007 FLORIDA BUILDING CODE W/
 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1)THIS PROVISO WAS ATTACHED TO THE FOUNDATION PERMIT.
 INSPECTOR IS TO REVIEW AND BRING IN A SIGNED SEALED
 SOILS REPORT AT TIME OF FOUNDATION INSPECTION. THIS
 PLAN IS FOR A NEW BUILDING PLEASE PROVIDE SOILS REPORT
 FOR THE SAFE MINIMUM SOIL BEARING VALUES. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN
 THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS
 OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 2) THIS PROVISO WAS ATTACHED TO THE FOUNDATION PERMIT.
 THE NEW FOUNDATION PLANS DO SHOW WHAT FINISH SLAB
 ELEVATION 100 IS REFERENCED TOO IN NGVD. THIS BUILDING
 IS IN A A- 5 FLOOD ZONE. THE BASE FLOOD ELEVATION FOR
 FINISH FLOOR IS 7.5 NGVD. SHEET AS-101 INDICATES A
 FINISH FLOOR ELEVATION OF 100.00' BUT THERE IS NO
 REFERENCE TO WHAT 100.00' IS EQUAL TO?
  
 3A)FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 EXTERIOR DOORS GLAZED OR SOLID SINGLE AND DOUBLE
 WINDOWS W/ LARGE MISSILE IMPACT
 WALL LOUVERS
 ROOFING ASSEMBLIES, STANDING SEAM METAL ROOF, PLEASE
 NOTE PLANS INDICATE THE USE OF A SELF-ADHERED MEMBRANE,
 MUST COMPLY WITH PRODUCT APPROVAL IF A NAILABLE SUB
 SHEET IS
 REQUIRED.
  
 3B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) NO TRUSS ENGINEERING PACKAGE HAS BEEN SUBMITTED,
 CONTRACTOR IS WORKING AT OWN RISK, SINCE THE MAGNITUDE
 OF GRAVITY, UPLIFT OR LATERAL LOADS HAS NOT BEEN
 PROVIDED BY TRUSS ENGINEER, THE DESIGNER OF RECORD IS
 TO REVIEW & STAMP ENGINEERING BEFORE TRUSS ENGINEERING
 IS SUBMITTED TO THE BUILDING DEPARTMENT FOR REVIEW.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-09-06 Cont ID  
Sent By rlecky Date 2011-09-06 Time 12:20 Rev Time 0.00
Received By rlecky Date 2011-09-06 Time 12:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-08-22 Cont ID  
Sent By rlecky Date 2011-08-22 Time 14:53 Rev Time 0.00
Received By rlecky Date 2011-08-22 Time 09:43 Sent To  
Notes
2011-08-22 14:53:50FITNESS BUILDING #11080116
 4200 N. FLAGLER DR.
  
 PROVIDE A DEDICATED SPACE WITHIN THE ELECTRICAL
 EQUIPMENT ROOM FOR THE TRANSFORMER AND PANEL BOARDS.
 NEC110. 26 (E)
 GENERAL PURPOSE RECEPTACLES LOCATED OUTDOORS AND IN
 BATHROOMS REQUIRE GFCI PROTECTION. NEC 210.8
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-09-08 Cont ID  
Sent By wjolin Date 2011-09-08 Time 13:49 Rev Time 0.00
Received By wjolin Date 2011-09-08 Time 13:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-12 Cont ID  
Sent By wjolin Date 2011-08-12 Time 12:59 Rev Time 0.00
Received By wjolin Date 2011-08-12 Time 12:31 Sent To  
Notes
2011-08-12 12:38:174200 NORTH FLAGLER DRIVE - FITNESS BUILDING
 PERMIT #11080116
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: CIVIL SITE DRAWINGS TO BE SUBMITTED AS SEPARATE
 PACKAGE.
  
  
 NO ADDRESS PROVIDED IN TITLEBLOCK.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 DESIGN SHALL CONFORM TO THE 2007 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA EDITION
 OF NFPA 1 AND NFPA 101.
  
 SHEET G101 LIFE SAFETY PLAN NOT SUBMITTED.
  
 NO OCCUPANCY TYPE OR OCCUPANT LOAD INFORMATION
 PROVIDED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 NO FITNESS EQUIPMENT OR FURNITURE PLAN SUBMITTED.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. THE TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 ALL INTERIOR WALL AND CEILING FINISHES SHALL BE CLASS
 A, CLASS B OR CLASS C.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 SHEET A-101: DOOR #125A NOT PROVIDED WITH A FIRE
 RATING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2011-09-07 Time   Rev Time 0.00
Received By shill Date 2011-09-06 Time 11:00 Sent To  
Notes
2011-09-06 11:01:02C29
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-30 Cont ID  
Sent By hmoser Date 2011-08-30 Time 16:31 Rev Time 0.00
Received By hmoser Date 2011-08-04 Time 15:28 Sent To  
Notes
2011-08-04 15:28:29SENT TO C29 SHELF FOR ALL TRADES REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-09-08 Cont ID  
Sent By rbrown Date 2011-09-08 Time 18:53 Rev Time 0.00
Received By rbrown Date 2011-09-08 Time 18:53 Sent To  
Notes
2011-09-08 18:57:00SEE NOTES UNDER PERMIT # 11080115. IMPACT FEES WERE
 PAID FOR THIS FITNESS BUILDING TOGETHER WITH THE
 CAFETERIA BUILDING AND THE MAINTENANCE BUILDING ALL ON
 ONE RECEIPT # 2011-831-56 MU-2011-015450-0000 FOR
 $15,199.85

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-08-30 Cont ID  
Sent By hmoser Date 2011-08-30 Time 16:33 Rev Time 0.00
Received By hmoser Date 2011-08-17 Time 09:28 Sent To  
Notes
2011-08-17 09:29:11BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-09-07 Cont ID  
Sent By hmoser Date 2011-09-07 Time 13:49 Rev Time 0.00
Received By hmoser Date 2011-09-07 Time 13:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-30 Cont ID  
Sent By hmoser Date 2011-08-30 Time 16:31 Rev Time 0.00
Received By hmoser Date 2011-08-30 Time 15:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-09-07 Cont ID  
Sent By lwagner Date 2011-09-07 Time 09:48 Rev Time 0.00
Received By lwagner Date 2011-09-07 Time 09:48 Sent To  
Notes
2011-09-07 09:48:39RE-STAMP

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-08-22 Cont ID  
Sent By lwagner Date 2011-08-22 Time 12:21 Rev Time 0.00
Received By lwagner Date 2011-08-22 Time 10:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-08-26 Cont ID  
Sent By jroach Date 2011-08-26 Time 14:48 Rev Time 0.00
Received By jroach Date 2011-08-26 Time 14:48 Sent To  
Notes
2011-08-26 14:49:03ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.26.2011
 PERMIT NO.: 11080116
 ADDRESS: 3990 NORTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: JEFFREY L. SLADE
 TELEPHONE NO.: 954.764.6550
 SCOPE OF REVIEW: NEW MAINTENANCE BUILDING.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THIS PLAN REVIEW IS PASSED ONLY FOR AN AT RISK
 PERMIT. ALL DEVELOPMENT IS SUBJECT TO THE APPROVAL OF
 RESOLUTION NO. 191-11 BY THE CITY COMMISSION OF THE
 CITY OF WEST PALM BEACH. FAILURE TO OBTAIN SUCH
 APPROVAL WILL REQUIRE THAT ALL DEVELOPMENT CONSTRUCTED
 UNDER THIS PERMIT BE REMOVED AND THE SITE RETURNED TO
 ITS ?PRE-PERMIT? STATE.
  
 2. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 SEPARATE PERMITS SHALL BE OBTAINED FOR ALL SITE-RELATED
 WORK, INCLUDING LANDSCAPING, PAVEMENT, ETC.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved