Plan Review Details - Permit 11070640
Plan Review Stops For Permit 11070640
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-08-04 Cont ID  
Sent By rlecky Date 2011-08-04 Time 10:45 Rev Time 0.00
Received By rlecky Date 2011-08-04 Time 10:45 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-03 Cont ID  
Sent By wjolin Date 2011-08-03 Time 14:40 Rev Time 0.00
Received By wjolin Date 2011-08-03 Time 14:13 Sent To E
Notes
2011-08-03 14:40:395101 GREENWOOD AVENUE
 PERMIT #11070640
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE BATTERY CALCULATIONS.
  
 INDICATE IF THE FIRE ALARM SYSTEM IS REQUIRED.
  
 ONLY TWO AUDIBLE DEVICES SHOWN FOR ENTIRE FLOOR PLAN.
 VERFIY THIS IS SUFFICIENT TO MEET THE AUDIBILITY
 REQUIREMENTS OF NFPA 72.
  
 VISUAL NOTIFICATION APPLIANCES NOT PROVIDED IN ALL
 COMMON ROOMS/SPACES SUCH AS RESTROOMS, CONFERENCE
 ROOMS, ETC.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2011-08-08 Cont ID  
Sent By hmoser Date 2011-08-08 Time 10:21 Rev Time 0.00
Received By hmoser Date 2011-07-26 Time 16:27 Sent To  
Notes
2011-07-26 16:27:33TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-08 Cont ID  
Sent By hmoser Date 2011-08-08 Time 10:21 Rev Time 0.00
Received By hmoser Date 2011-08-08 Time 10:21 Sent To  
Notes
***NONE***