Plan Review Details - Permit 11070617
Plan Review Stops For Permit 11070617
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-03-05 Cont ID  
Sent By jwitmer Date 2012-03-05 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2012-03-05 Time 10:23 Sent To  
Notes
2012-03-02 16:30:54SEPERATE ROOFING PERMIT REQUIRED SEE UNKNOWNS BELOW
 IDENTIFIED AS (*******)
  
 ROOFING REPORTS SUBMITTED:
  
 BERRIDGE MANUFACTURING CO ZEE-LOCK PANEL W/ CONTINUOUS
 CLIP
 NOA 10-1018.02
 PAGE 5 OF 7 TABLE B FIELD -168.5 PERIMETERS & CORNER
 -176 PSF
  
  
 JOHN MANVILLE INSULATION BOARD
 NOA 09-0219.09
 SUBSYSTEM OR TRADE NAME OF SYSTEM NOT
 PROVIDED.**************************
  
  
 DUROLAST SINGLE PLY PVC ROOF SYSTEM OVER CONCRETE DECK
 NOA 07-1018.10
 PAGE 6 OF 14
 DECK TYPE 31
 SYSTEM A(2)
 MAX PRESSURE -247.5 LIMITATION #9.
  
 DURO-LAST SINGLE PLY PVC ROOF SYSTEM OVER WOOD DECK
 NOA 07-1018.14
 PAGE 6 OF 10
 DECK TYPE 1I
 SYSTEM C:
 MAXIMUM DESIN PRESSURES 45-60 PSF NOT IDENTIFIED
 LIMITATION # 7 **********************************
 *******************************************************
 ***************************************
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS
 PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S). REVISIONS REQUIRE ADDITIONAL REVIEWS WITH
 ASSOCIATED FEES.
  
 1) SHEET 1-A1.1 INDICATES A NEW MEZZANINE LEVEL AND
 HIGH RACK STORAGE SYSTEM. THE PLANS DON'T
 HAVE ANY DETAILS FOR THE STRUCTURAL COMPONENTS FOR
 EITHER SECTION. A REVISION WILL BE REQUIRED
 INDICATING CODE COMPLIANCE FOR BOTH OF THE AREAS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-02-01 Cont ID  
Sent By jwitmer Date 2012-02-01 Time 14:40 Rev Time 0.00
Received By jwitmer Date 2012-02-01 Time 13:31 Sent To  
Notes
2012-02-01 14:40:00BUILDING PLAN REVIEW
 PERMIT: 11070617
 ADD: 2301 OKEECHOBEE BLVD, BLDG# 1
 CONT: NORTH AMERICAN AUTOMOTIVE SERVICES
 TEL: (630)352-8126
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 2007 FLORIDA EXISTING BUILDING CODE W/ 2009 FBC
 SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 BLDG TYPE IB -NON SPRINKLERED
  
 3RD REVIEW
 ACTION: DENIED
  
 1) 2007 EXST BLD CODE 601.2 CONFORMANCE. AN EXISTING
 BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED SUCH
 THAT THE BUILDING BECOMES LESS SAFE OR ENERGY EFFICIENT
 THAN ITS EXISTING CONDITION. IF IN THE ALTERATION THE
 CURRENT LEVEL OF SAFETY OR SANITATION IS TO BE REDUCED,
 THE PORTION ALTERED SHALL CONFORM TO THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING .
  
 1A) SHEET 1-A1.0 THE PLANS APPEAR TO HAVE A OCCUPANCY
 SEPARATION WALL BETWEEN THE AUTOMOBILE REPAIR GARAGE
 AND PARTS STORAGE AND THE REPAIR GARAGE AND MERCANTILE
 OCCUPANCY. IT APPEARS TO BE A MASONRY OPENING NOT
 PROTECTED RIGHT OF DOOR # 1118?
  
 1B) THE ABOVE MENTIONED OCCUPANCY SEPARATION WALL IS
 THE ONLY OCCUPANCY SEPARATION WALL SHOWN ON THE PLANS,
 THERE WOULD APPEAR A OCCUPANCY SEPARATION WALL WOULD BE
 REQUIRED BETWEEN THE PARTS STORAGE AREA AND THE
 MERCANTILE OCCUPANCY. PLEASE PROVIDE THE FOLLOWING FOR
 A MIXED OCCUPANCY, IF THIS BUILDING IS TO BE CONSIDERED
 SEPARATED (FBC-B 508.3.1.3 OR NON-SEPARATED 508.3.2 OR
 IF MEETING THE REQUIREMENTS FOR ACCESSORY OCCUPANCIES
 508.3.1.
 PLEASE NOTE THAT BOTH THE FIRST FLOOR AND MEZZANINE
 SQUARE FOOT LEVELS ARE TO BE TOTALED TOGETHER FOR TOTAL
 SQ FT FOR THIS FIRE LOAD & OCCUPANCY IT APPEARS THE
 PARTS STORAGE AREA IS WELL OVER THE 10% OF THE TOTAL
 FLOOR AREA .
  
 1C) THE WALL BETWEEN THE PARTS AND SHOWROOM SHOULD ALSO
 BE A FIRE RATED WALL PER TABLE TABLE 508.3.3 FOOTNOTE B
 INDICATES AREA REQUIREMENTS REQUIRING SEPERATION AS
 WELL AS TABLE 508.2 INCIDENTAL USE AREAS FOR STORAGE
 ROOMS GREATER THAN 100 SQ FT IN UNSPRINKLERED
 BUILDINGS.
  
 2) THE SECOND ISSUE WITH THE PARTS STORAGE FIRE AREA
 WHICH INCLUDES APPROX. 4000 SQ FT (3789 SQ FT) FIRST
 FLOOR PLUS 3015 SQ FT ON THE PARTS MEZZANINE (VENDOR
 INSTALLED).
 SEE FBC-B 505.2 AREA LIMITATIONS FOR MEZZANINE
 ALLOWABLE FLOOR AREA.
  
 2A) THIS IS A STORAGE OCCUPANCY IN A BUILDING TYPE L-B.
 PLEASE REVIEW FBC-B MEZZANINE AREA LIMITATION 505.2
 EXCEPTION# 2. THE AGGREGATE AREA OF MEZZANINES IN
 BUILDINGS AND STRUCTURES OF TYPE I OR II CONSTRUCTION
 SHALL NOT EXCEED ONE-HALF OF THE FLOOR AREA OF THE ROOM
 IN BUILDINGS AND STRUCTURES EQUIPPED THROUGHOUT WITH AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 AND AN APPROVED EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM IN ACCORDANCE WITH SECTION
 907.2.12.2.
  
 THE MEZZANINE LEVEL WILL NEED TO BE REDUCED OR IT WILL
 BE REQUIRED TO BE CONSIDERED A SECOND FLOOR AND TO MEET
 ALL BUILDING & MEANS OF EGRESS OF A SECOND FLOOR.
  
 2B) THE COMMENT VENDOR INSTALLED, IS THIS A
 PRE-ENGINEERED SYSTEM? THE LIVE LOADS FOR ANY STORAGE
 AREA ABOVE THE GROUND FLOOR WILL NEED TO BE PROVIDED.
 2007/09 FBC-B T 1607.1
 LIGHT 125 PSF AND HEAVY 250 PSF. PLEASE PROVIDE
 ENGINEERING.
  
 2B)(1) 110.4.2 STORAGE & FACTORY- INDUSTRIAL
 OCCUPANCIES. IT SHALL BE THE RESPONSIBILITY OF THE
 OWNER, AGENT, PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE
 FLOOR LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
  
 2B)(2) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR
 PART OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR
 HAZARDOUS PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED
 ON PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM.
  
 2C) SHEET 1-A1.0 PLANS ARE DEFICIEENT IN AN OCCUPANCY
 SEPERATION WALL BETWEEN THE PARTS DEPARTMENT (STORAGE
 OCCUPANCY) AND OFFICE AREAS (BUSINESS OCCUPANCY).
  
 3) THE AREA OF CONCERN IS FOUND ON 1-A 1.0 &1-A1.1 A
 BUSINESS MEZZANINE, A TRUE SECOND FLOOR AREA WITH ONLY
 ONE MEANS OF EGRESS. PLEASE PROVIDE:
  
 3A) THE PLANS INDICATE A WALL TYPE N WHICH IS INDICATED
 ON 0-A1.0 AS A NON RATED WALL.
  
 3B) PLEASE PROVIDE THE SQUARE FOOTAGE OF MEZZANINE AND
 THE SQUARE FOOTAGE OF OPEN AREA
 THAT COMMUNICATES WITH THIS AREA. FBC-B 505.2 & 505.4.
 IF THIS IS NOT A TRUE MEZZANINE THEN ISSUES WILL ARISE
 FROM THE OPEN STAIR THAT SERVES THIS AREA. THIS AREA
 WAS DISCUSSED PREVIOUSLY AS HOW TO HANDLE THIS
 PRE-EXISTING CONDITION. ALSO DOOR # 1127A WAS RED LINED
 ON THE SEEET OF PLANS THAT WAS READY FOR ISSUANCE, IT
 SWINGS THE WRONG WAY FOR EGRESS FROM THE 2ND FLOOR
 LEVEL AND EGRESS PATERN FROM THE PARTS DEPARTMENT.
  
 4) SHEET 1-A8.1 DETAILS A & 1AND SHEET 1-A8.2 BOTH
 INDICATE THE USE OF ? INCH EXTERIOR GRADE PLYWOOD FOR
 SHEATHING, PLEASE REVIEW:
 FBC-B
  
  
  
 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL
 BE PERMITTED IN BUILDINGS OF TYPE I OR TYPE II
 CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN
 ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
  
 5) PLEASE REVIEW SHEET 1-A8.0 DETAIL # 1 INDICATES THE
 USE OF EXISTING WOOD TRUSSES, ARE THESE TRUSSES FIRE
 RETARDANT TREATED WOOD? THE PLANS DO NOT ADDRESS THE
 VERTICAL PLYWOOD, IF IT IS FIRE RETARDANT TREATED WOOD?
 TYPE I TYPE II BUILFINGS. FBC 603.1.
  
 6) SHEET 1-A8.1 WALL SECTION 1 ALSO HAS REFRENECE TO
 3/4 INCH PLYWOOD, NOT FIRE RETARDANT TREATED WOOD.
 603.1.
  
 7) THE ROOFING APPROVAL 07-1018.10 DURO-LAST SINGLE PLY
 PVC ROOFING SYSTEMS OVER CONCRETE DECKS THIS REPORT HAS
 SUBSYSTEM AND WILL NEED TO CIRCLE WHICH SUBSYSTEM WILL
 BE INSTALLED. PLEASE REVIEW THE DESIGN PRESSURES
 ASSOCIATED WITH EACH SUBSYSTEM AND IF LIMITATION 7 OR
 LIMITATION 9 ARE APPLICABLE. IF LIMITATION 7 IS
 INDICATED AND ENHANCED FASTENING IS REQUIRED IN ZONES 2
 & 3 PLEASE PROVIDE CALCULATIONS.
  
 8) THE ABOVE MENTIONED NOA 07-1018.10 IS FOR PVC ROOF
 SYSTEMS OVER CONCRETE DECKS.
 SHEET 1-A8.2 INDICATES NEW TOWER SECTIONS THAT WILL
 NEED A SEPARATE ROOFING PRODUCT APPROVAL FOR THIS TYPE
 OF ROOFING APPLICATION.
  
 9) DEPENDING ON THE SHEATHING FROM COMMENT #7 THE
 REYNOLDS REYNOBOND COMPOSITE PANEL NOA 10-1118.05 MAY
 NEED AN ENGINEERS ANALYSIS FOR THE TYPE OF SHEATHING TO
 BE INSTALLED SINCE THE PRESSURES ASSOCIATED WITH THIS
 REPORT ARE FROM 5/8 INCH PLYWOOD SHEATHING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-10-05 Cont ID  
Sent By jwitmer Date 2011-10-05 Time 11:20 Rev Time 1.20
Received By jwitmer Date 2011-10-05 Time 11:20 Sent To  
Notes
2011-10-05 11:20:59BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 BUILDING PLAN REVIEW
 PERMIT: 11070617
 ADD: 2301 OKEECHOBEE BLVD, BLDG# 1
 CONT: NORTH AMERICAN AUTOMOTIVE SERVICES
 TEL: (630)352-8126
  
 1A) PARTS MEZZANINE IS TO BE A PRE-ENGINEERED SYSTEM
 VENDOR INSTALLED, UNDER A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES.
  
 1B) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES.
 IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT,
 PROPRIETOR OR OCCUPANT OF GROUP S AND GROUP F
 OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR
 LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT. THE
 COMPUTATIONS & AFFIDAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
  
 1C) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART
 OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS
 PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE
 BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM.
  
 2) ROOFING APPROVALS:
  
 NOA: 07-1018.10
 DURO-LAST SINGLE PLY PVC ROOFING SYSTEM OVER CONCRETE
 DECK,
 PAGE 5, DECK TYPE 31 CONCRETE DECK INSULATED -217.5
 LIMITATION # 9
  
 NOA 09-0219.09
 JOHN MANVILLE ROOF INSULATION BOARD
 ROOF ASSEMBLIES ARE APPROVED UNDER SPECIFIC ROOF
 COVER?S PRODUCT NOA.
  
 NOA 07-1018.14
 DURO-LAST SINGLE PLY PVC ROOFING SYSTEM OVER WOOD DECK
 THE INDIVIDUAL SUB-SYSTEMS ARE NOT IDENTIFIED, ROOFING
 CONTRACTOR WILL NEED TO
 IDENTIFY SUB-SYSTEM AND IF LIMITATION # 7 APPLIES THEN
 ENHANCED FASTENING IN ZONES
 2 & 3 WILL NEED TO BE CALCULATED AND PREPARED BY EITHER
 A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-09 Cont ID  
Sent By jwitmer Date 2011-08-09 Time 14:34 Rev Time 6.50
Received By jwitmer Date 2011-08-03 Time 15:48 Sent To  
Notes
2011-08-09 14:35:15BUILDING PLAN REVIEW
 PERMIT: 11070617
 ADD: 2301 OKEECHOBEE BLVD, BLDG# 1
 CONT: NORTH AMERICAN AUTOMOTIVE SERVICES
 TEL: (630)352-8126
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 2007 FLORIDA EXISTING BUILDING CODE W/ 2009 FBC
 SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007 EXST BLD CODE 601.2 CONFORMANCE. AN EXISTING
 BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED SUCH
 THAT THE BUILDING BECOMES LESS SAFE OR ENERGY EFFICIENT
 THAN ITS EXISTING CONDITION. IF IN THE ALTERATION THE
 CURRENT LEVEL OF SAFETY OR SANITATION IS TO BE REDUCED,
 THE PORTION ALTERED SHALL CONFORM TO THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING .
  
 1A) SHEET 1-A1.0 THE PLANS APPEAR TO HAVE A OCCUPANCY
 SEPARATION WALL BETWEEN THE AUTOMOBILE REPAIR GARAGE
 AND PARTS STORAGE AND THE REPAIR GARAGE AND MERCANTILE
 OCCUPANCY. IT APPEARS TO BE A MASONRY OPENING NOT
 PROTECTED NEXT TO DOOR # 1118?
  
 1B) THE ABOVE MENTIONED OCCUPANCY SEPARATION WALL IS
 THE ONLY OCCUPANCY SEPARATION WALL SHOWN ON THE PLANS,
 THERE WOULD APPEAR A OCCUPANCY SEPARATION WALL WOULD BE
 REQUIRED BETWEEN THE PARTS STORAGE AREA AND THE
 MERCANTILE OCCUPANCY. PLEASE PROVIDE THE FOLLOWING FOR
 A MIXED OCCUPANCY, IF THIS BUILDING IS TO BE CONSIDERED
 SEPARATED (FBC-B 508.3.1.3 OR NON-SEPARATED 508.3.2 OR
 IF MEETING THE REQUIREMENTS FOR ACCESSORY OCCUPANCIES
 508.3.1.
 PLEASE NOTE THAT BOTH THE FIRST FLOOR AND MEZZANINE
 SQUARE FOOT LEVELS ARE TO BE TOTALED TOGETHER FOR TOTAL
 SQ FT FOR THIS FIRE LOAD & OCCUPANCY IT APPEARS THE
 PARTS STORAGE AREA IS WELL OVER THE 10% OF THE TOTAL
 FLOOR AREA .
  
 2) THE SECOND ISSUE WITH THE PARTS STORAGE FIRE AREA
 WHICH INCLUDES APPROX. 4000 SQ FT FIRST FLOOR PLUS 3015
 SQ FT ON THE PARTS MEZZANINE (VENDOR INSTALLED).
  
 2A) THIS IS A STORAGE OCCUPANCY IN A BUILDING TYPE L-B.
 PLEASE REVIEW FBC-B MEZZANINE AREA LIMITATION 505.2
 EXCEPTION# 2. THE AGGREGATE AREA OF MEZZANINES IN
 BUILDINGS AND STRUCTURES OF TYPE I OR II CONSTRUCTION
 SHALL NOT EXCEED ONE-HALF OF THE FLOOR AREA OF THE ROOM
 IN BUILDINGS AND STRUCTURES EQUIPPED THROUGHOUT WITH AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 AND AN APPROVED EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM IN ACCORDANCE WITH SECTION
 907.2.12.2.
  
 THE MEZZANINE LEVEL WILL NEED TO BE REDUCED OR IT WILL
 BE REQUIRED TO BE CONSIDERED A SECOND FLOOR AND TO MEET
 ALL BUILDING & MEANS OF EGRESS OF A SECOND FLOOR.
  
 2B) THE COMMENT VENDOR INSTALLED, IS THIS A
 PRE-ENGINEERED SYSTEM? THE LIVE LOADS FOR ANY STORAGE
 AREA ABOVE THE GROUND FLOOR WILL NEED TO BE PROVIDED.
 2007/09 FBC-B T 1607.1
 LIGHT 125 PSF AND HEAVY 250 PSF. PLEASE PROVIDE
 ENGINEERING.
  
 2B)(1) 110.4.2 STORAGE & FACTORY- INDUSTRIAL
 OCCUPANCIES. IT SHALL BE THE RESPONSIBILITY OF THE
 OWNER, AGENT, PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE
 FLOOR LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
  
 2B)(2) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR
 PART OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR
 HAZARDOUS PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED
 ON PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM.
  
 3) THE OTHER AREA OF CONCERN IS FOUND ON 1-A1.1 A
 BUSINESS MEZZANINE. PLEASE PROVIDE:
  
 3A) THE PLANS INDICATE A WALL TYPE M & N WHICH ARE NOT
 FOUND ON 0-A1.0.
  
 3B) PLEASE PROVIDE THE SQUARE FOOTAGE OF MEZZANINE AND
 THE SQUARE FOOTAGE OF OPEN AREA
 THAT COMMUNICATES WITH THIS AREA. FBC-B 505.2 & 505.4.
 IF THIS IS NOT A TRUE MEZZANINE THEN ISSUES WILL ARISE
 FROM THE OPEN STAIR THAT SERVES THIS AREA.
  
 4) BUSINESS MEZZANINE LEVEL WAS BUILT BEFORE THE ADA &
 FLORIDA ACCESSIBILITY CODE WERE IN ACTED. PLEASE
 PROVIDE COMPLIANCE WITH FBC-B 11-4.1.6(1)(K) III)
  NOTHING IN THIS SECTION SHALL BE CONSTRUED TO RELIEVE
 THE OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM
 THE DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE AND BELOW OCCUPIABLE GRADE LEVEL,
 REGARDLESS OF WHETHER THE CODE REQUIRES AN ELEVATOR TO
 BE INSTALLED IN SUCH BUILDING, STRUCTURE, OR FACILITY,
 EXCEPT FOR: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER, AS PROVIDED IN SECTION 553.509,
 FLORIDA STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES
 MUST, AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3(5) OF THIS
 CODE.
  
 5) SHEET 1-A1.0 DOES INDICATE THE USE OF A LIFT TO GAIN
 ACCESS TO THE RESTROOMS AND RETAIL AREAS, PLEASE
 PROVIDE COMPLIANCE WITH 11-4.1.6(1) (B) IF EXISTING
 ELEMENTS, SPACES, OR COMMON AREAS ARE ALTERED, THEN
 EACH SUCH ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 11-4.1.1 TO SECTION 11-4.1.3, MINIMUM REQUIREMENTS FOR
 NEW CONSTRUCTION. IF THE APPLICABLE PROVISION FOR NEW
 CONSTRUCTION REQUIRES THAT AN ELEMENT, SPACE, OR COMMON
 AREA BE ON AN ACCESSIBLE ROUTE, THE ALTERED ELEMENT,
 SPACE, OR COMMON AREA IS NOT REQUIRED TO BE ON AN
 ACCESSIBLE ROUTE EXCEPT AS PROVIDED IN SECTION
 11-4.1.6(2), ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION. PLEASE PROVIDE MANUFACTURERS
 SPECIFICATIONS.
  
 6) SHEET 1-A1.0 SERVICE AREA AND NEW FIVE FOOT WIDE
 CURB RAMP WILL NEED TO COMPLY WITH FBC-B 11-4.29
 DETECTABLE WARNINGS.
  
 7) SHEET 1-A8.1 DETAILS A & 1AND SHEET 1-A8.2 BOTH
 INDICATE THE USE OF ? INCH EXTERIOR GRADE PLYWOOD FOR
 SHEATHING, PLEASE REVIEW:
 FBC-B
  
 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL
 BE PERMITTED IN BUILDINGS OF TYPE I OR TYPE II
 CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN
 ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
  
 7) PLEASE SEE SHEET 1-A8.3 DETAIL A INDICATES THE USE
 OF ? INCH OF RIGID COVER BOARD AND 2 INCHES OF POLYISO
 INSULATION. THE NOA 10-1018.02 PAGE 4 INDICATES THE
 INSULATION TO HAVE CURRENT NOA?S.
  
 8) THE ROOFING APPROVAL 07-1018.10 DURO-LAST SINGLE PLY
 PVC ROOFING SYSTEMS OVER CONCRETE DECKS THIS REPORT HAS
 SUBSYSTEM AND WILL NEED TO CIRCLE WHICH SUBSYSTEM WILL
 BE INSTALLED. PLEASE REVIEW THE DESIGN PRESSURES
 ASSOCIATED WITH EACH SUBSYSTEM AND IF LIMITATION 7 OR
 LIMITATION 9 ARE APPLICABLE. IF LIMITATION 7 IS
 INDICATED AND ENHANCED FASTENING IS REQUIRED IN ZONES 2
 & 3 PLEASE PROVIDE CALCULATIONS.
  
 9) THE ABOVE MENTIONED NOA 07-1018.10 IS FOR PVC ROOF
 SYSTEMS OVER CONCRETE DECKS.
 SHEET 1-A8.2 INDICATES NEW TOWER SECTIONS THAT WILL
 NEED A SEPARATE ROOFING PRODUCT APPROVAL FOR THIS TYPE
 OF ROOFING APPLICATION.
  
 10) DEPENDING ON THE SHEATHING FROM COMMENT #7 THE
 REYNOLDS REYNOBOND COMPOSITE PANEL NOA 10-1118.05 MAY
 NEED AN ENGINEERS ANALYSIS FOR THE TYPE OF SHEATHING TO
 BE INSTALLED SINCE THE PRESSURES ASSOCIATED WITH THIS
 REPORT ARE FROM 5/8 INCH PLYWOOD SHEATHING.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2012-02-29 Cont ID  
Sent By rlecky Date 2012-02-29 Time 17:34 Rev Time 0.00
Received By rlecky Date 2012-02-29 Time 17:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2012-02-06 Cont ID  
Sent By rlecky Date 2012-02-06 Time 12:25 Rev Time 0.00
Received By rlecky Date 2012-02-03 Time 15:59 Sent To  
Notes
2012-02-06 12:27:3611070617
 2310 OKEECHOBEE BLVD.
 NAPLETON BLDG. 1
  
 THE ELECTRICAL EQUIPMENT ROOM REQUIRES TWO ENTRANCES.
 NEC 110.26(C)(2)
 PROVIDE DEDICATED WORKING SPACE AND SAFETY CLEARANCES
 FOR DISTRIBUTION PANELBOARD 1DPC. NEC 110.26
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOMS. NEC 110.22, 110.16
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-09-27 Cont ID  
Sent By rlecky Date 2011-09-27 Time 14:52 Rev Time 0.00
Received By rlecky Date 2011-09-27 Time 12:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-08-17 Cont ID  
Sent By rlecky Date 2011-08-17 Time 11:28 Rev Time 0.00
Received By rlecky Date 2011-08-10 Time 10:22 Sent To  
Notes
2011-08-17 10:44:57 
 BUILDING # 1
 RELOCATE THE MAIN BONDING JUMPER FOR BUILDING #1 TO THE
 MAIN DISCONNECTS. NEC 250.24(B)
 PROVIDE AN EQUIPMENT LAYOUT PLAN FOR THE COMPRESSOR
 ROOM SHOWING THE ELECTRIC CIRCUITRY WITH DISCONNECTS
 AND WORKING CLEARANCES. NEC 110.26, 215.5
 A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE SITE
 LIGHTING. THE PLAN SHOULD INCLUDE PHOTO METRICS, THE
 DESIGN WIND LOAD ENGINEERED FOR THE LIGHT POLES AND AN
 ELECTRIC POWER PLAN.
 A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE CAR WASH
 EQUIPMENT
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2012-05-30 Cont ID  
Sent By mgonzale Date 2012-05-30 Time   Rev Time 1.00
Received By mgonzale Date 2012-05-30 Time   Sent To  
Notes
2012-05-30 13:58:47PLANS ARE APPROVED WITH PROVISOS (RESPOND TO ALL
 COMMENTS IN WRITING IN ACKNOWLEDGEMENT)
  
 #1 RIGHT TURN ONLY EXIT CONCRETE APRON UNTO CONGRESS
 AVE NEEDS TO BE REVISED AND NARROWED TO AVOID CARS
 ENTERING SITE WHILE OTHERS ARE TRYING TO EXIT.
 (CONGRESS AVENUE IS A PALM BEACH COUNTY ROADWAY
 THEREFORE CONSULT WITH PBC ROAD ROW PERMIT WILL BE
 REQUIRED)
  
 #2 PROVIDE DETAILS AND/OR DESIGN SUMMARY FOR PROPOSED
 A.D.A. RAMP. (PLANS SUBMITTED DO NOT SHOW SLOPE,
 SPECIFIC DIMENSIONS (LENGTH, WIDTH, ETC.) AND DETAILS
 FOR A.D.A. HANDRAIL. (RAMP DETAILS MAY BE OBTAINED THRU
 WWW.ADA.ORG WEB SITE UNDER U.S. DEPARTMENT OF JUSTICE -
 ADA STANDARDS FOR ACCESSIBLE DESIGN. IF PERMIT FOR THIS
 ELEMENT HAS BEEN ISSUED UNDER ARCHITECTURE PLANS OR
 OTHER SOURCE PLEASE PROVIDE PERMIT NUMBER AND/OR
 INFORMATION.
  
 #3 PLAN IDENTIFIES TWO DUMPSTER AREAS; HOWEVER THESE
 AREAS ARE NOT LOCATED IN THE SAME VICINITY. PLEASE
 SPECIFY WHICH DUMPSTER WILL BE THE PRIMARY DUMPSTER FOR
 CITY OF WEST PALM BEACH SANITATION PICK-UP.
  
 #4 PLEASE VERIFY THAT THE 2" DOMESTIC METER (LOCATION:
 CONGRESS SIDEWALK 10 NORTH OF SOUTH DRIVE) HAS THE
 PROPER BACKFLOW PREVENTION DEVICE. INACTIVE 1" SERVICE
 (LOCATION: SIDEWALK 4' WEST OF OKEECHOBEE DRIVEWAY)
 COULD BE ACTIVATED AND DESIGNATED AS IRRIGATION. WITH
 CURRENT CONFIGURATION DOMESTIC WATER USED FOR
 IRRIGATION WILL BE CHARGED SEWAGE AGAINST IT.
  
 #5 ACCESS DRIVE EXITING TO 20FT WIDE ALLEY MUST BE AS
 PER CITY OF WEST PALM BEACH STANDARD DRIVEWAY APRON.
 20FT WIDE IS THE MAX + 3' FOOT FLARE + 3' CURB
 TRANSITION. APRON MUST BE 6" THICK CONCRETE AND 3000PSI
 MINIMUM. REFER TO:
 HTTP://WWW.WPB.ORG/ENGINEERING/PDF/STANDARDS/GC-6.PDF
  
 #6 IT IS HIGHLY SUGGESTIVE THAT CHAIN LINK FENCE
 SURROUNDING REAR LOT, BE PLACED AROUND DRY DETENTION
 AREAS. THIS WOULD ALLOW PROTECTION FOR PEDESTRIANS WHO
 COULD INADVERTENTLY WALK INTO THE SITE AND FALL.
  
 PLEASE FEEL FREE TO DIRECT ANY SPECIFIC QUESTION SHOULD
 YOU NEED CLARIFICATION ON ANY OF THE ABOVE MENTIONED
 ITEMS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2011-10-28 Cont ID  
Sent By mgonzale Date 2011-10-28 Time 14:46 Rev Time 0.25
Received By mgonzale Date 2011-10-28 Time 14:46 Sent To  
Notes
2011-10-28 15:14:50PASSED WITH PROVISOS - PLAN IS ACCEPTABLE FOR BUILDING
 RENOVATIONS.
 PLEASE SUPPLY SITE PERVIOUS AND IMPERVIOUS INFORMATION
 TO:
 THIS INFORMATION WILL BE UTILIZED TO UPDATE CITY'S
 STORMWATER ACCOUNT.
  
 BRIAN R MOREE
 ENGINEERING SERVICES CONSTRUCTION SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1098
 FAX: 494-1118
 E-MAIL: [email protected]
 SERVING SINCE NOV 12, 2000
 EMPLOYMENT CATEGORY: FR
  
 ************************************************
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING SERVICES
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-09-07 Cont ID  
Sent By mgonzale Date 2011-09-07 Time 09:45 Rev Time 0.00
Received By mgonzale Date 2011-09-07 Time 09:45 Sent To  
Notes
2011-09-07 09:47:14FAILED:
  
 #1 PLEASE ADDRESS COMMENTS IN WRITING ISSUED DURING
 PPRC.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2012-03-05 Cont ID  
Sent By wjolin Date 2012-03-05 Time 14:52 Rev Time 0.00
Received By wjolin Date 2012-03-05 Time 12:45 Sent To  
Notes
2012-03-05 12:58:042301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3
 PERMIT #11070617
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.1
 PARTS #2109 - OPEN GRATE AREA: STORAGE TO BE MAINTAINED
 AT OR BELOW 12'-0" TOTAL HEIGHT. PAINT STRIPE AROUND
 ROOM TO MARK ELEVATION OF MAXIMUM STORAGE, OTHERWISE
 FIRE SPRINKLERS ARE REQUIRED FOR HIGH-PILED STORAGE.
 SOLID FLOOR AREA: PROVIDE PERMANENT SIGNAGE READING
 STORAGE TO BE MAINTAINED 24" BELOW STRUCTURE.
  
 SHEET 1-A2.0
 PROVIDE MINIMUM CEILING HEIGHT OF 7'-6". SURFACE
 MOUNTED LIGHTING MAY IMPEDE UPON THIS HEADROOM.
  
 SHEET 3-A5.0
 INDICATE WHAT MATERIALS AND QUANTITIES OF MATERIALS
 WILL BE STORED IN DETAIL STORAGE #1311.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2012-02-07 Cont ID  
Sent By wjolin Date 2012-02-07 Time 11:00 Rev Time 0.00
Received By wjolin Date 2012-01-31 Time 12:02 Sent To  
Notes
2012-02-07 10:58:262301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3
 PERMIT #11070617
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET 1-A1.0
 PARTS #1128 - MEZZANINE STAIRS SHALL BE 36" WIDE
 MINIMUM.
  
 PROVIDE FIRE RATED SEPARATION BETWEEN PARTS (STORAGE)
 AND BUSINESS OCCUPANCY. PROTECT ALL OPENINGS AND
 PENETRATIONS.
 NOTE: THE RATED WALLS AND DOORS DO NOT AGREE BETWEEN
 PLAN SHEETS 1-A1.0 AND 1-A3.0.
  
 SHEET A1.1
 PARTS #2109 - THE MEZZANINE MAY BE REQUIRED TO BE
 LIMITED TO 1/3 OR 1/2 THE AREA OF THE FLOOR BELOW.
  
 SHEET 1-A2.0
 PROVIDE MINIMUM CEILING HEIGHT OF 7'-6". NEED VENDOR
 SHELVING LAYOUT TO COMPARE TO SURFACE MOUNTED CEILING
 LIGHT LOCATIONS.
  
 NEED AN ADDITIONAL EXIT SIGN TO LEAD TO SECONDARY EXIT
 IN PARTS #1128.
  
 CUSTOMER WAITING #1117 HAS EXIT SIGNS ROUTING OCCUPANTS
 TO A MORE HAZARDOUS OCCUPANCY.
  
 SHEET 1-A3.0
 RELOCATE TABLES AND CHAIRS (NEAR TWO SOUTH DOUBLE EXIT
 DOORS) TO KEEP DIRECT UNOBSTRUCTED PATH TO EXITS.
  
 PROVIDE EXIT SIGN FOR PARTS STORAGE EAST EXIT AND MINOR
 REPAIRS AREA NORTH EXIT.
 NOTE: THE RCP EXIT SIGN LOCATIONS DO NOT MATCH ON
 SHEETS 1-A2.0 AND 1-A3.0.
  
 SHEET 1-A3.1
 THE MAXIMUM OCCUPANT LOAD FOR THE BUSINESS MEZZANINE
 NEEDS TO BE SHOWN AS 10 PERSONS, OTHERWISE AN
 ADDITIONAL EXIT IS REQUIRED.
  
 SHEET 3-A5.0
 INDICATE WHAT MATERIALS AND QUANTITIES OF MATERIALS
 WILL BE STORED IN DETAIL STORAGE #1311.
  
 GENERAL
 PROVIDE GUARD RAIL FOR PARTS MEZZANINE.
  
 STORAGE NEEDS TO BE MAINTAINED AT 24" BELOW THE CEILING
 OR STRUCTURE IN THE PARTS MEZZANINE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-10-13 Cont ID  
Sent By wjolin Date 2011-10-13 Time 14:55 Rev Time 0.00
Received By wjolin Date 2011-10-13 Time 13:38 Sent To  
Notes
2011-10-13 14:55:182301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3
 PERMIT #11070617
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A DETAILED SITE PLAN INDICATING FIRE DEPARTMENT
 VEHICLE ACCESS WIDTHS, MARKED FIRE LANES, FIRE HYDRANT
 LOCATIONS, PERIMETER GATES/FENCES, CONSTRUCTION
 TRAILERS ETC.
  
 BUILDING #2: IF POSSIBLE, RELOCATE KNOXBOX AND FIRE
 ALARM ANUNCIATOR PANEL NEAR AN EAST ENTRY DOOR AS THIS
 WILL BE THE ACCESS SIDE FOR EMERGENCY RESPONDERS. THE
 WEST SIDE OF THE BUILDING ABUTTS THE FENCE AND PROPERTY
 LINE.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL OTHER PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-08 Cont ID  
Sent By wjolin Date 2011-08-08 Time 12:25 Rev Time 0.00
Received By wjolin Date 2011-08-08 Time 08:35 Sent To  
Notes
2011-08-08 12:25:202301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3
 PERMIT #11070617
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE 2007 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA EDITION
 OF NFPA 1 AND NFPA 101.
  
 PROVIDE A DETAILED SITE PLAN INDICATING FIRE DEPARTMENT
 VEHICLE ACCESS WIDTHS, MARKED FIRE LANES, FIRE HYDRANT
 LOCATIONS, PERIMETER GATES/FENCES, CONSTRUCTION
 TRAILERS ETC.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND DEBRIS TO BE REMOVED FROM THE
 SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDINGS DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING NUMBER AND BUILDING ADDRESS VISIBLE
 FROM THE STREET. NUMBERS SHALL BE AT LEAST SIX-INCHES
 IN HEIGHT AND SHALL CONTRAST THE BACKGROUND (REFERENCE:
 SECTION 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE -
 NFPA 1).
  
 PROVIDE A LIFE SAFETY PLAN CLEARLY INDICATING FIRE
 RATED WALLS, FIRE RATED DOORS, OCCUPANT LOADS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL, FIRE EXTINGUISHERS ETC.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2006. THE ONLY FIRE RATED
 SEPARATION APPEARS TO BE THE 2-HOUR FIRE BARRIER
 SEPARATING THE INTERIOR SERVICE BAYS FROM THE ADJACENT
 INTERIOR SPACE.
  
 THE SERVICE AREAS APPEAR TO BE FUNCTIONING MORE LIKE AN
 INDUSTRIAL/FACTORY OCCUPANCY THAN A STORAGE OCCUPANCY.
  
 INDICATE IF THE SERVICE AREAS AND BODY SHOP AREAS WILL
 BE FUNCTIONING AS A MAJOR OR MINOR REPAIR GARAGE AS PER
 SECTION 3.3.165.21.1 OF NFPA 1.
  
 NO SMOKING OR OPEN FLAME SIGNS TO BE POSTED IN ALL
 SERVICE AREAS, BODY SHOPS AND PAINT BOOTH AREAS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 THE BUSINESS OFFICES (#2101, #2104 ETC.) ARE INDICATED
 AS BEING LOCATED ON THE MEZZANINE; HOWEVER, THIS SPACE
 DOES NOT MEET THE DEFINITION OF A MEZZANINE (SECTION
 8.6.9 NFPA 101) WHEREBY THE MEZZANINE SPACE IS OPEN TO
 THE FLOOR BELOW UNLESS THE OCCUPANT LOAD OF THE
 AGGREGATE AREA OF THE ENCLOSED SPACE DOES NOT EXCEED
 10.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 HANDRAILS ARE REQUIRED TO BE INSTALLED ON BOTH SIDES OF
 STAIRS.
  
 SPRAYING OF FLAMMABLE LIQUIDS (PAINT) SHALL CONFORM TO
 THE REQUIMENTS OF NFPA 33.
  
 STORAGE AND HANDLING OF FLAMMABLE LIQUIDS SHALL CONFORM
 TO THE REQUIREMENTS OF NFPA 30.
  
 INDICATE THE QUANTITIES OF FLAMMABLE LIQUIDS TO BE
 HOUSED IN THE PAINT SHOP AND MIXING ROOM.
  
 PAINT SHOP #1304 TO BE PROVIDED WITH TWO EXITS WHEREBY
 ONE FIRE EVENT WILL NOT RESTRICT ACCESS TO BOTH EXITS.
  
 INDICATE THE AREAS THAT WILL BE PROTECTED BY A FIRE
 SUPPRESSION SYSTEM(S).
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 INSTALLATION OF FIRE SPRINKLERS, FIRE ALARMS, PAINT
 SPRAY BOOTHS AND ANY OTHER SPECIALTY TRADE.
  
 SHEET FA0.1 BOTH FIRE ALARM RISER DIAGRAMS INDICATED AS
 BUILDING #1.
  
 SHEET 1FA2.2 NOT SEALED BY ENGINEER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-03-23 Cont ID  
Sent By lmartine Date 2012-03-23 Time 15:54 Rev Time 0.00
Received By lmartine Date 2012-02-27 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-03-23 Cont ID  
Sent By lmartine Date 2012-02-07 Time 15:54 Rev Time 0.00
Received By lmartine Date 2012-01-19 Time 17:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-11-03 Time 14:30 Rev Time 0.00
Received By shill Date 2011-09-22 Time 16:17 Sent To  
Notes
2011-09-23 16:18:19C--27 & 28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-23 Cont ID  
Sent By lmartine Date 2011-09-07 Time 16:17 Rev Time 0.00
Received By lmartine Date 2011-07-27 Time 08:58 Sent To  
Notes
2011-07-27 08:58:21C-27

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2012-03-09 Cont ID  
Sent By hmoser Date 2012-03-09 Time 14:27 Rev Time 0.00
Received By hmoser Date 2012-03-09 Time 14:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2012-02-08 Cont ID  
Sent By hmoser Date 2012-02-08 Time 13:02 Rev Time 0.00
Received By hmoser Date 2012-02-07 Time 13:11 Sent To  
Notes
2012-02-08 13:02:17PLANS DENIED
 1) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M)
 MISSING FIRE DAMPERS PAGE 1-M2.1 AND 1-M2.2.
 OF THE PLANS.
 2) PLEASE INDICATE ON THE PLANS WHERE THE 21X14
 DUCT IS GOING AND TO WHAT UNIT PAGE 1-M2.1
 3) PLEASE INDICATE RATED WALLS ON THE MECHANICAL PLANS
 4) PROVIDE A PIPING ISOMETRIC ON MECHANICAL PLANS FOR
 THE AIR COMPRESSOR, MO LINES WO LINES AND ATF LINES.
 5) THERE IS NO SUPPLY AIR IN ROOMS 1141 THROUGH 1145 ON
 PAGE 1-M2.1 PLEASE EXPLAIN.
 6) INDICATE WHAT UNIT IS COOLING CAR RENTAL AREA ON
 PAGE 3-M2.1
 7) PROVIDE PRODUCT APPROVALS FOR OUT DOOR LOUVERS PER
 SECTION
 106.33 2007 FBC.
 8) PROVIDE EXHAUST FAN NUMBERS ON EXHAUST AIR
 CALCULATIONS.
 9) PROVIDE A DETAIL ON CONDENSER STAND AND CURB TO ROOF
 TIE DOWN PER SECTION 301.12 WIND RESISTANCE 2007 FBC
 (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-03 Cont ID  
Sent By hmoser Date 2011-11-03 Time 14:54 Rev Time 0.00
Received By hmoser Date 2011-11-02 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-08-30 Cont ID  
Sent By hmoser Date 2011-08-30 Time 13:07 Rev Time 0.00
Received By hmoser Date 2011-08-24 Time 13:41 Sent To  
Notes
2011-08-30 13:19:34PLANS DENIED
 PLEASE MARK THE RTU EQUIPMENT ON THE DUCT PLANS PAGE M
 2.1.
 SECTION 301.12 WIND RESISTANCE 2007 FBC (M) . THE USE
 OF WOOD SLEEPERS SHALL
 NOT BE PERMITTED . ROOF PIPING SUPPORT DETAIL PAGE M7.1
 PLAIN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2012-03-02 Cont ID  
Sent By lwagner Date 2012-03-02 Time 08:22 Rev Time 0.00
Received By lwagner Date 2012-03-01 Time 15:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-02-03 Cont ID  
Sent By lwagner Date 2012-02-03 Time 13:04 Rev Time 0.00
Received By lwagner Date 2012-01-30 Time 13:00 Sent To  
Notes
2012-02-03 12:45:07FBC PLUMBING 2007 REVIEW #1
  
 ***NOTE***
 SHEET 1A-1.0 SHOWS THREE EYE WASH STATIONS. IF THEY ARE
 NOT SELF CONTAINED PLEASE SHOW WATER PIPE ON PLUMBING
 DRAWINGS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-10-07 Cont ID  
Sent By lwagner Date 2011-10-07 Time 14:21 Rev Time 0.00
Received By lwagner Date 2011-10-07 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-08-15 Cont ID  
Sent By lwagner Date 2011-08-15 Time 14:28 Rev Time 0.00
Received By lwagner Date 2011-08-04 Time 14:45 Sent To  
Notes
2011-08-15 14:28:34FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEET P0.1 DETAIL SHOWS A SCHLER SIT-150-C OIL
 SEPARATOR DETAIL. SHEETS 1P-2.1 & 2P-2.1 CALL FOR A
 SEPARATOR WITH NO COLLECTION TANK.
  
 2. SHEET P7.2 THE SECTION OF PIPE LABELED 6,032 SHOULD
 BE 8" . THE SECTION OF PIPE LABELED 9,880 SHOULD BE 10"
 PIPE BASED ON 1/8" PER FOOT & 5" RAINFALL.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2012-03-23 Cont ID  
Sent By jroach Date 2012-03-23 Time 14:27 Rev Time 0.00
Received By jroach Date 2012-03-23 Time 14:27 Sent To  
Notes
2012-03-23 14:27:45ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.23.2012
 PERMIT NO.: 11070617 AND 11070619
 ADDRESS: 2301 AND 2321 OKEECHOBEE BOULEVARD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: RENOVATION TO EXISTING STRUCTURES/SITE
 FOR REESTABLISHMENT OF A CAR DEALERSHIP.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY:
  
 A. A REVISED TRAFFIC CONCURRENCY LETTER SHALL BE
 PROVIDED FROM THE PALM BEACH COUNTY DEPARTMENT OF
 ENGINEERING AND PUBLIC WORKS ? TRAFFIC ENGINEERING
 DIVISION INDICATING THEIR REVIEW AND APPROVAL OF THE
 REVISED BUILDING SQUARE FOOTAGE.
  
 B. THE ENTIRE SITE SHALL BE BROUGHT INTO COMPLIANCE
 WITH ARTICLE XIV (LANDSCAPING) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS) AS THE VALUE OF
 THE WORK EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE [THESE REQUIRED IMPROVEMENTS ARE REFLECTED IN
 THE CPD APPLICATION THAT IS IN PROCESS, AND REFERENCED
 ABOVE]. ALL APPLICABLE PLANS (I.E. SITE PLANS,
 LANDSCAPE PLANS, ETC) WILL NEED TO BE SUBMITTED UNDER
 SEPARATE PERMITS. PLEASE ENSURE THAT ALL PLANS MATCH
 THOSE THAT ARE A PART OF THE CPD. UPON SUBMITTAL OF
 PERMIT APPLICATIONS FOR THE SITE WORK, LANDSCAPING,
 ETC. PLEASE ENSURE THAT DETAILS ARE PROVIDED FOR ALL
 IMPROVEMENTS SUCH AS GATES, FENCES, DUMPSTER
 ENCLOSURES, PARKING STRIPING, ETC.
  
 C. BUILDING #3: - THE ROOF TOP MECHANICAL EQUIPMENT
 SHALL BE SCREENED FROM VIEW. UPON INSTALLATION OF THE
 EQUIPMENT, AND PRIOR TO FINAL INSPECTION, A SITE VISIT
 SHALL COORDINATE WITH THE PLANNING DIVISION. IF IT IS
 DETERMINED THAT THE MECHANICAL EQUIPMENT IS VISIBLE,
 APPROPRIATE SCREENING SHALL BE ADDED.
  
 2. ALL SITE LIGHTING SHALL BE SUBMITTED UNDER A
 SEPARATE PERMIT.
  
 A. A PHOTOMETRIC PLAN SHALL BE SUBMITTED TO THE CITY?S
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 INDICATING THAT ANY NEW SITE LIGHTING, OR UPGRADES TO
 EXISTING SITE LIGHTING, DO NOT EXCEED 1.0 FOOTCANDLES
 WHEN MEASURED AT THE BOUNDARY OF THE DEVELOPMENT.
  
 B. THE ELECTRICAL SITE PLAN DOES NOT MATCH THE SITE
 PLAN THAT IS PROPOSED AND RESULTS IN SEVERAL CONFLICTS
 BETWEEN LIGHTING LOCATION, PARKING, TREE INSTALLATION,
 ETC. PLEASE ENSURE THAT ALL PLANS ARE CONSISTENT.
  
 C. DETAILS NEED TO BE PROVIDED REGARDING PROPOSED LIGHT
 POLES, INCLUDING OVERALL HEIGHT.
  
 3. PLEASE NOTE THAT ALL SIGNAGE WILL NEED TO CONFORM TO
 THE REQUIREMENTS OF THE GENERAL COMMERCIAL (GC) ZONING
 DISTRICT AND WILL BE REVIEWED UPON SUBMITTAL....THIS
 WILL NOT HOLD UP ISSUANCE OF A PERMIT, BUT IS JUST A
 REMINDER WHEN CONSIDERING SIGNAGE FOR THE DEVELOPMENT
 AND SUBMITTAL OF SIGN PERMITS. PLEASE NOTE THAT WALL
 SIGNS ARE LIMITED TO ONE (1) SIGN PER BUSINESS, PLUS
 TWO (2) ADDITIONAL SIGNS, RESULTING IN ONLY THREE (3)
 TOTAL SIGNS PERMITTED FOR THE PROJECT.
  
 4. THE FENCING SURROUNDING THE OIL STORAGE PEN SHALL BE
 SOLID/OPAQUE, NOT CHAIN LINK.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 4 Status F Date 2012-03-12 Cont ID  
Sent By jroach Date 2012-03-12 Time 10:51 Rev Time 0.00
Received By jroach Date 2012-03-12 Time 10:51 Sent To  
Notes
2012-03-12 10:51:56ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.12.2012
 PERMIT NO.: 11070617 AND 11070619
 ADDRESS: 2301 OKEECHOBEE BOULEVARD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW:
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. AN APPLICATION FOR A UNITY OF TITLE SHALL BE
 SUBMITTED TO THE CITY?S ENGINEERING SERVICES
 DEPARTMENT. UPON APPROVAL OF THE APPLICATION, THE UNITY
 OF TITLE SHALL BE RECORDED IN THE PUBLIC RECORDS OF
 PALM BEACH COUNTY, AND A CERTIFIED COPY SHALL BE
 SUBMITTED TO THE CITY?S DEVELOPMENT SERVICES DEPARTMENT
 ? PLANNING DIVISION.
  
 2. A REVISED TRAFFIC CONCURRENCY LETTER SHALL BE
 PROVIDED FROM THE PALM BEACH COUNTY DEPARTMENT OF
 ENGINEERING AND PUBLIC WORKS ? TRAFFIC ENGINEERING
 DIVISION INDICATING THEIR REVIEW AND APPROVAL OF THE
 REVISED BUILDING SQUARE FOOTAGE.
  
 3. A PHOTOMETRIC PLAN SHALL BE SUBMITTED TO THE CITY?S
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 INDICATING THAT ANY NEW SITE LIGHTING, OR UPGRADES TO
 EXISTING SITE LIGHTING, DO NOT EXCEED 1.0 FOOTCANDLES
 WHEN MEASURED AT THE BOUNDARY OF THE DEVELOPMENT.
  
 4. A CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN
 SHALL BE SUBMITTED TO, AND APPROVED BY, THE CITY OF
 WEST PALM BEACH POLICE DEPARTMENT ? CRIME PREVENTION
 UNIT.
  
 5. THE ENTIRE SITE SHALL BE BROUGHT INTO COMPLIANCE
 WITH ARTICLE XIV (LANDSCAPING) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS) AS THE VALUE OF
 THE WORK EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE [THESE REQUIRED IMPROVEMENTS ARE REFLECTED IN
 THE CPD APPLICATION THAT IS IN PROCESS, AND REFERENCED
 ABOVE]. ALL APPLICABLE PLANS (I.E. SITE PLANS,
 LANDSCAPE PLANS, ETC) WILL NEED TO BE SUBMITTED UNDER
 SEPARATE PERMITS. PLEASE ENSURE THAT ALL PLANS MATCH
 THOSE THAT ARE A PART OF THE CPD. UPON SUBMITTAL OF
 PERMIT APPLICATIONS FOR THE SITE WORK, LANDSCAPING,
 ETC. PLEASE ENSURE THAT DETAILS ARE PROVIDED FOR ALL
 IMPROVEMENTS SUCH AS GATES, FENCES, DUMPSTER
 ENCLOSURES, PARKING STRIPING, ETC.
  
 6. PLEASE ENSURE THAT ALL FLOOR PLANS, ELEVATIONS, ETC.
 ARE CONSISTENT WITH THE PROPOSED SITE PLAN
 MODIFICATIONS.
  
 7. PLEASE NOTE THAT ALL SIGNAGE WILL NEED TO CONFORM TO
 THE REQUIREMENTS OF THE GENERAL COMMERCIAL (GC) ZONING
 DISTRICT AND WILL BE REVIEWED UPON SUBMITTAL....THIS
 WILL NOT HOLD UP ISSUANCE OF A PERMIT, BUT IS JUST A
 REMINDER WHEN CONSIDERING SIGNAGE FOR THE DEVELOPMENT
 AND SUBMITTAL OF SIGN PERMITS. PLEASE NOTE THAT WALL
 SIGNS ARE LIMITED TO ONE (1) SIGN PER BUSINESS, PLUS
 TWO (2) ADDITIONAL SIGNS, RESULTING IN ONLY THREE (3)
 TOTAL SIGNS PERMITTED FOR THE PROJECT.
  
 8. THE ELECTRICAL SITE PLAN DOES NOT MATCH THE SITE
 PLAN THAT IS PROPOSED AND RESULTS IN SEVERAL CONFLICTS
 BETWEEN LIGHTING LOCATION, PARKING, TREE INSTALLATION,
 ETC. PLEASE ENSURE THAT ALL PLANS ARE CONSISTENT.
  
 9. DETAILS NEED TO BE PROVIDED REGARDING PROPOSED LIGHT
 POLES, INCLUDING OVERALL HEIGHT.
  
 10. PLEASE NOTE THAT PARKING SPACES ADJACENT TO
 REQUIRED LANDSCAPE BUFFERS WILL NEED TO HAVE WHEEL
 STOPS (OR THE CURB LINE MOVED IN) TO KEEP VEHICLES FROM
 OVERHANGING INTO THE REQUIRED LANDSCAPE AREA. THE SITE
 PLAN PROPOSED AS PART OF THE CPD APPLICATION ADDRESSES
 THIS COMMENT.
  
 11. THE FENCING SURROUNDING THE OIL STORAGE PEN SHALL
 BE SOLID/OPAQUE, NOT CHAIN LINK.
  
 12. BUILDING #1:
  
 A. THE STAIRS ON THE SOUTH SIDE OF BUILDING #1 ARE
 INCONSISTENT WITH THE PROPOSED SITE PLAN AND ENCROACH
 INTO THE PROPOSED PARKING SPACES.
  
 13. BUILDING #3:
  
 A. PLEASE PROVIDE INFORMATION REGARDING THE ROOF-TOP
 MECHANICAL EQUIPMENT ON TOP OF BUILDING #3. IT APPEARS
 THAT THERE IS NO PARAPET, AND THE MECHANICAL EQUIPMENT
 SHALL BE SCREENED FROM VIEW.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 3 Status F Date 2012-02-10 Cont ID  
Sent By jroach Date 2012-02-10 Time 10:45 Rev Time 0.00
Received By jroach Date 2012-02-07 Time 16:20 Sent To  
Notes
2012-02-10 10:46:06ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.10.2012
 PERMIT NO.: 11070617 AND 11070619
 ADDRESS: 2301 OKEECHOBEE BOULEVARD, #1 & #3
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: RENOVATIONS TO EXISTING CAR SALES
 FACILITY.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 GENERAL COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE
 COMMERCIAL PLANNED DEVELOPMENT (CPD) APPLICATION
 SUBMITTED TO THE CITY'S PLANNING AND ZONING DEPARTMENT
 SHALL BE APPROVED BY THE CITY COMMISSION.
  
 2. THE ENTIRE SITE SHALL BE BROUGHT INTO COMPLIANCE
 WITH ARTICLE XIV (LANDSCAPING) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS) AS THE VALUE OF
 THE WORK EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE [THESE REQUIRED IMPROVEMENTS ARE REFLECTED IN
 THE CPD APPLICATION THAT IS IN PROCESS, AND REFERENCED
 ABOVE]. ALL APPLICABLE PLANS (I.E. SITE PLANS,
 LANDSCAPE PLANS, ETC) WILL NEED TO BE SUBMITTED UNDER
 SEPARATE PERMITS. PLEASE NOTE THAT THE SITE PLAN
 SUBMITTED AS PART OF THIS PERMIT APPLICATION DOES NOT
 CORRESPOND WITH THE SITE PLAN THAT IS PROPOSED AS PART
 OF THE CPD APPLICATION. PLEASE ENSURE THAT ALL PLANS
 MATCH THOSE THAT ARE A PART OF THE CPD. UPON SUBMITTAL
 OF PERMIT APPLICATIONS FOR THE SITE WORK, LANDSCAPING,
 ETC. PLEASE ENSURE THAT DETAILS ARE PROVIDED FOR ALL
 IMPROVEMENTS SUCH AS GATES, FENCES, DUMPSTER
 ENCLOSURES, PARKING STRIPING, ETC.
  
 3. PLEASE ENSURE THAT ALL FLOOR PLANS, ELEVATIONS, ETC.
 ARE CONSISTENT WITH THE PROPOSED SITE PLAN
 MODIFICATIONS.
  
 4. PLEASE NOTE THAT ALL SIGNAGE WILL NEED TO CONFORM TO
 THE REQUIREMENTS OF THE GENERAL COMMERCIAL (GC) ZONING
 DISTRICT AND WILL BE REVIEWED UPON SUBMITTAL....THIS
 WILL NOT HOLD UP ISSUANCE OF A PERMIT, BUT IS JUST A
 REMINDER WHEN CONSIDERING SIGNAGE FOR THE DEVELOPMENT
 AND SUBMITTAL OF SIGN PERMITS. PLEASE NOTE THAT WALL
 SIGNS ARE LIMITED TO ONE (1) SIGN PER BUSINESS, PLUS
 TWO (2) ADDITIONAL SIGNS?RESULTING IN ONLY THREE (3)
 TOTAL SIGNS PERMITTED FOR THE PROJECT.
  
 5. THE ELECTRICAL SITE PLAN DOES NOT MATCH THE SITE
 PLAN THAT IS PROPOSED AND RESULTS IN SEVERAL CONFLICTS
 BETWEEN LIGHTING LOCATION, PARKING, TREE INSTALLATION,
 ETC. PLEASE ENSURE THAT ALL PLANS ARE CONSISTENT.
  
 6. A PHOTOMETRIC PLAN SHALL BE PROVIDED INDICATING
 NUMBER OF FOOTCANDLES AS MEASURED AT THE PROPERTY
 LINES. LIGHTING SHALL NOT EXCEED 1.0 FOOTCANDLES AT THE
 PROPERTY LINE.
  
 7. DETAILS NEED TO BE PROVIDED REGARDING PROPOSED LIGHT
 POLES, INCLUDING OVERALL HEIGHT.
  
 8. PLEASE NOTE THAT PARKING SPACES ADJACENT TO REQUIRED
 LANDSCAPE BUFFERS WILL NEED TO HAVE WHEEL STOPS (OR THE
 CURB LINE MOVED IN) TO KEEP VEHICLES FROM OVERHANGING
 INTO THE REQUIRED LANDSCAPE AREA. THE SITE PLAN
 PROPOSED AS PART OF THE CPD APPLICATION ADDRESSES THIS
 COMMENT.
  
 9. THE FENCING SURROUNDING THE OIL STORAGE PEN SHALL BE
 SOLID/OPAQUE, NOT CHAIN LINK.
  
 BUILDING #1:
  
 1. THE STAIRS ON THE SOUTH SIDE OF BUILDING #1 ARE
 INCONSISTENT WITH THE PROPOSED SITE PLAN AND ENCROACH
 INTO THE PROPOSED PARKING SPACES.
  
 BUILDING #3:
  
 1. PLEASE PROVIDE INFORMATION REGARDING THE ROOF-TOP
 MECHANICAL EQUIPMENT ON TOP OF BUILDING #3. IT APPEARS
 THAT THERE IS NO PARAPET?AND THE MECHANICAL EQUIPMENT
 SHALL BE SCREENED FROM VIEW.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 2 Status F Date 2011-10-06 Cont ID  
Sent By jroach Date 2011-10-06 Time 14:47 Rev Time 0.00
Received By jroach Date 2011-10-06 Time 14:47 Sent To  
Notes
2011-10-06 14:59:23ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.06.2011
 PERMIT NO.: 11070617, 11070618, AND 11070619
 ADDRESS: 2301 OKEECHOBEE BOULEVARD, #1-3
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: RENOVATIONS TO EXISTING CAR SALES
 FACILITY.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 GENERAL COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE
 COMMERCIAL PLANNED DEVELOPMENT (CPD) APPLICATION
 SUBMITTED TO THE CITY'S PLANNING AND ZONING DEPARTMENT
 SHALL BE APPROVED BY THE CITY COMMISSION.
  
 2. THE ENTIRE SITE SHALL BE BROUGHT INTO COMPLIANCE
 WITH ARTICLE XIV (LANDSCAPING) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS) AS THE VALUE OF
 THE WORK EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE [THESE REQUIRED IMPROVEMENTS ARE REFLECTED IN
 THE CPD APPLICATION THAT IS IN PROCESS, AND REFERENCED
 ABOVE]. ALL APPLICABLE PLANS (I.E. SITE PLANS,
 LANDSCAPE PLANS, ETC) WILL NEED TO BE SUBMITTED UNDER
 SEPARATE PERMITS.
  
 3. PLEASE ENSURE THAT ALL FLOOR PLANS, ELEVATIONS, ETC.
 ARE CONSISTENT WITH THE PROPOSED SITE PLAN
 MODIFICATIONS. SEE MORE SPECIFIC COMMENTS BELOW.
  
 4. PLEASE NOTE THAT ALL SIGNAGE WILL NEED TO CONFORM TO
 THE REQUIREMENTS OF THE GENERAL COMMERCIAL (GC) ZONING
 DISTRICT AND WILL BE REVIEWED UPON SUBMITTAL....THIS
 WILL NOT HOLD UP ISSUANCE OF A PERMIT, BUT IS JUST A
 REMINDER WHEN CONSIDERING SIGNAGE FOR THE DEVELOPMENT
 AND SUBMITTAL OF SIGN PERMITS.
  
 5. THE ELECTRICAL SITE PLAN DOES NOT MATCH THE SITE
 PLAN THAT IS PROPOSED.
  
 6. THERE ARE SEVERAL LOCATIONS WHERE EXISTING LIGHT
 POLES CONFLICT WITH THE PROPOSED SITE PLAN. A) THERE IS
 A POLE TO THE NORTH OF BUILDING #3 THAT APPEARS THAT IT
 MAY BE LOCATED IN THE PARKING LOT DRIVE AISLE. PLEASE
 CONFIRM THAT IT WILL BE OUTSIDE OF THE MINIMUM 24 CLEAR
 WIDTH REQUIREMENT. B) THERE IS A POLE BETWEEN BUILDINGS
 #2 AND #3...THIS SPACE WILL NEED TO BE STRIPED AS "NO
 PARKING" OR THE POLE WILL NEED TO BE RELOCATED. C)
 THERE IS A POLE TO THE NORTH OF BUILDING #1...IT IS
 PREFERRED THAT THIS POLE BE RELOCATED, BUT AS LONG AS
 THIS IS MAINTAINED AS INVENTORY PARKING ONLY, IT MAY BE
 ABLE TO REMAIN. D) THERE IS ONE POLE SOUTH OF BUILDING
 #2 THAT IS LOCATED IN THE DRIVE AISLE.....THE CURB FOR
 THE LANDSCAPE ISLAND COULD BE EXTENDED OUT TO ENCOMPASS
 THIS POLE, SO LONG AS 20 MINIMUM WIDTH IS MAINTAINED
 BETWEEN THE ISLAND AND THE CURB TO THE WEST. E) THERE
 ARE 3 POLES AT THE HEAD OF PARKING SPACES SOUTH OF
 BUILDING #2...THESE WILL NEED TO BE STRIPED AS
 "COMPACT" SPACES AND THE WHEEL STOPS ADJUSTED TO
 PROVIDE THE 2-FOOT CLEAR OVERHANG.
  
 7. PLEASE NOTE THAT PARKING SPACES ADJACENT TO REQUIRED
 LANDSCAPE BUFFERS WILL NEED TO HAVE WHEEL STOPS (OR THE
 CURB LINE MOVED IN) TO KEEP VEHICLES FROM OVERHANGING
 INTO THE REQUIRED LANDSCAPE AREA.
  
 BUILDING #1:
  
 1. THE WESTERN-MOST STAIR ON THE SOUTH SIDE OF BUILDING
 #1 IS INCONSISTENT WITH THE PROPOSED SITE PLAN AND
 ENCROACHES INTO THE PROPOSED PARKING SPACES.
  
 BUILDING #2:
  
 1. THE STAIRWAYS AND HANDICAP RAMP ON THE SOUTH SIDE OF
 THE BUILDING APPEAR TO CONFLICT WITH THE PROPOSED
 PARKING LAYOUT....THE HC RAMP AND STAIRS WOULD ENCROACH
 INTO THE PROPOSED PARKING.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2011-08-14 Cont ID  
Sent By jroach Date 2011-08-14 Time 13:24 Rev Time 0.00
Received By jroach Date 2011-08-14 Time 13:24 Sent To  
Notes
2011-08-14 14:11:16ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.14.2011
 PERMIT NO.: 11070617, 11070618, AND 11070619
 ADDRESS: 2301 OKEECHOBEE BOULEVARD, #1-3
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: RENOVATIONS TO EXISTING CAR SALES
 FACILITY.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 GENERAL COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE
 COMMERCIAL PLANNED DEVELOPMENT (CPD) APPLICATION
 SUBMITTED TO THE CITY?S PLANNING AND ZONING DEPARTMENT
 SHALL BE APPROVED BY THE CITY COMMISSION.
  
 2. THE ENTIRE SITE SHALL BE BROUGHT INTO COMPLIANCE
 WITH ARTICLE XIV (LANDSCAPING) OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS) AS THE VALUE OF
 THE WORK EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE [THESE REQUIRED IMPROVEMENTS ARE REFLECTED IN
 THE CPD APPLICATION THAT IS IN PROCESS, AND REFERENCED
 ABOVE]. ALL APPLICABLE PLANS (I.E. SITE PLANS,
 LANDSCAPE PLANS, ETC) WILL NEED TO BE SUBMITTED.
  
 3. PLEASE ENSURE THAT ALL FLOOR PLANS, ELEVATIONS, ETC.
 ARE CONSISTENT WITH THE PROPOSED SITE PLAN
 MODIFICATIONS.
  
 4. THE TOTAL SQUARE FOOTAGES SHOWN ON THE COVER SHEET
 DO NOT MATCH THOSE THAT WERE SUBMITTED AS PART OF THE
 CPD APPLICATION REFERENCED ABOVE. PLEASE ENSURE THAT
 ALL PLANS ARE CONSISTENT.
  
 5. PLEASE NOTE THAT ALL SIGNAGE WILL NEED TO CONFORM TO
 THE REQUIREMENTS OF THE GENERAL COMMERCIAL (GC) ZONING
 DISTRICT AND WILL BE REVIEWED UPON SUBMITTAL.
  
 6. ALL MECHANICAL AND ELECTRICAL EQUIPMENT (I.E.
 TRANSFORMERS ON THE WEST SIDES OF BUILDINGS #1 AND #2),
 WILL NEED TO BE SCREENED.
  
 7. THE EXISTING LIGHT POLE SHOWN IN THE INVENTORY
 PARKING AREA CONFLICTS WITH THE DRIVE AISLE AND WILL
 NEED TO BE REMOVED OR RELOCATED.
  
 8. THE EXISTING LIGHT POLE SOUTH OF THE BODY SHOP
 CONFLICTS WITH A PARKING SPACE. THIS SPACE WILL NEED TO
 BE STRIPED AS ?NO PARKING? OR THE POLE WILL NEED TO BE
 REMOVED OR RELOCATED.
  
 BUILDING #1:
  
 1. THE TWO (2) STAIRWAYS ON THE SOUTH SIDE OF BUILDING
 1, FROM THE ELEVATED DISPLAY AREA, ENCROACH IN THE
 PARKING SPACES PROPOSED.
  
 2. THE FLOOR PLANS DO NOT MATCH THE ELEVATIONS. THE
 HANDICAP RAMP IS SHOWN GOING IN DIFFERENT DIRECTIONS.
  
 3. THE FLOOR PLAN SHOWS DOORWAYS EXISTING THE EAST
 FACADE OF THE BUILDING FROM THE DETAIL AND EXPRESS OIL
 OFFICES. A LANDSCAPE ISLAND IS BEING PROPOSED JUST EAST
 OF THESE DOORWAYS. THEREFORE, IT APPEARS THAT THE
 EXITING OF THESE OFFICES WILL CONFLICT WITH THE
 PROPOSED LANDSCAPING.
  
 BUILDING #2:
  
 1. THE STAIRWAYS AND HANDICAP RAMP ON THE SOUTH SIDE OF
 THE BUILDING APPEAR TO CONFLICT WITH THE PROPOSED
 PARKING LAYOUT.
  
 2. THE VEHICLE RAMP PROPOSED ON THE EAST SIDE OF THE
 BUILDING APPEARS TO ENCROACH INTO THE DRIVEWAY BETWEEN
 BUILDINGS #1 AND #2. THIS DRIVEWAY SHALL REMAIN 24 FEET
 IN CLEAR WIDTH. THIS WILL NEED TO BE VERIFIED ON THE
 SITE PLAN.
  
 BUILDING #3
  
 1. PLEASE NOTE THAT THE TITLE BLOCK ON SHEET 3-A4.0 AND
 SHEET 3-A5.0 INDICATE BUILDING #1, WHEN THEY SHOULD
 INDICATE BUILDING #3.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH