Plan Review Details - Permit 11070370
Plan Review Stops For Permit 11070370
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-13 Cont ID  
Sent By jwitmer Date 2011-09-13 Time 15:42 Rev Time 0.55
Received By jwitmer Date 2011-09-13 Time 15:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-04 Cont ID  
Sent By jwitmer Date 2011-08-04 Time 09:07 Rev Time 0.77
Received By jwitmer Date 2011-08-04 Time 08:37 Sent To  
Notes
2011-08-04 09:40:05BUILDING PLAN REVIEW
 PERMIT: 11070370
 ADD: 420 COLUMBIA # 111
 CONT: AUTOBUILDERS
 TEL: (561)622-3515
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW COVER SHEET CODE RESEARCH MEANS OF
 EGRESS WITH TRAVEL LESS THAN 75'-0". SHEET A-1.0 PLEASE
 TAKE THE TRAVEL DISTANCE FROM ONE FOOT OFF OF THE
 NORTH-EAST CORNER OF THE LOUNGE WALL, STAY 1'-0" OFF OF
 WALLS FOR TRAVEL DISTANCE UNTIL YOU REACH THE FRONT
 DOORS, THE LEAST AMOUNT OF TRAVEL DISTANCE THAT I
 MEASURED IS APPROXIMATELY 78'. IF YOU CAN ILLUSTRATE
 YOUR TRAVEL DISTANCE LESS THAN 75'-0" THEN ONLY ONE
 MEANS OF EGRESS IS REQUIRED. IT APPEARS THAT THE LOUNGE
 DOOR LEADING TO THE EXTERIOR (DOOR 107A) WILL BE
 REQUIRED AS A SECOND EXIT SINCE THIS IS A UNSPRINKERED
 BUILDING THE 100 FOOT EXCEPTION CAN NOT BE APPLIED.
 2007/09 FBC-B 1014.3, SEE COMMENTARY WHERE YOU CAN NOT
 TAKE DIAGONAL ROUTES ACROSS ROOMS. THE REASONING IS IF
 THE BUILDING IS FILLED WITH SMOKE YOU WILL NEED TO
 TOUCH THE WALLS TO FIND YOUR WAY TO AN EXIT, IF
 FURNITURE IS IN THE WAY YOU WILL ALSO NEED TO GO AROUND
 SUCH OBSTRUCTIONS.
  
 2) PLEASE REVIEW SHEET A-2.0 DETAILS 1 & 2 RECEPTION
 DESK MUSST MEET TTHE REQUIREMENTS OF 11-7.2 SERVICE
 COUNTERS AND OR INFORMATION COUNTERS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-09-21 Cont ID  
Sent By rlecky Date 2011-09-21 Time 11:28 Rev Time 0.00
Received By rlecky Date 2011-09-21 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-08-12 Cont ID  
Sent By rlecky Date 2011-08-12 Time 15:54 Rev Time 0.00
Received By rlecky Date 2011-08-12 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-09-19 Cont ID  
Sent By wjolin Date 2011-09-19 Time 10:13 Rev Time 0.00
Received By wjolin Date 2011-09-19 Time 09:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-15 Cont ID  
Sent By wjolin Date 2011-08-15 Time 11:52 Rev Time 0.00
Received By wjolin Date 2011-08-15 Time 11:33 Sent To  
Notes
2011-08-15 11:43:55400 COLUMBIA DRIVE - SUITE #111
 PERMIT #11070370
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REFER TO BUILDING DEPT COMMENT REGARDING 75 FEET OF
 TRAVEL FOR ONE EXIT IN A BUSINESS OCCUPANCY.
  
 RECOMMEND LOCATING PORTABLE FIRE EXTINGUISHER ALONG
 PATH OF EGRESS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-08-16 Time   Rev Time  
Received By   Date 2011-07-22 Time   Sent To  
Notes
2011-08-16 14:37:28**DIGITAL PLANS** SEE PROJECTDOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-16 Cont ID  
Sent By jwitmer Date 2011-08-16 Time 09:06 Rev Time 0.00
Received By rregueir Date 2011-08-16 Time 14:36 Sent To  
Notes
2011-08-04 09:07:51ENTERED IN WRONG REVIEW BOX. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-09-20 Cont ID  
Sent By lwagner Date 2011-09-20 Time 10:38 Rev Time 0.00
Received By lwagner Date 2011-09-20 Time 08:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-08-05 Cont ID  
Sent By lwagner Date 2011-08-05 Time 13:34 Rev Time 0.00
Received By lwagner Date 2011-08-05 Time 13:21 Sent To  
Notes
2011-08-05 13:33:21FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 PLEASE INCLUDE A PLUMBING RISER DIAGRAM.
 FBC 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 13. PLUMBING RISER
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-09-16 Cont ID  
Sent By rregueir Date 2011-09-16 Time 09:07 Rev Time 0.00
Received By rregueir Date 2011-09-16 Time 09:07 Sent To  
Notes
***NONE***