Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-07-29 Cont ID  
Sent By rbrown Date 2011-07-29 Time 16:32 Rev Time 0.00
Received By rbrown Date 2011-07-29 Time 16:31 Sent To  
Notes
2011-07-29 16:36:27POOL WALL IS 3'-6" FROM HOUSE FOUNDATION AND POOL BASE
 IS 1'-9" BELOW HOUSE FOUNDATION. THE HOUSE FOUNDATION
 WILL NOT EXERT LATERAL LOAD ON THE POOL WALL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-15 Cont ID  
Sent By rmcdouga Date 2011-07-15 Time 07:12 Rev Time 0.00
Received By rmcdouga Date 2011-07-15 Time 07:12 Sent To  
Notes
2011-07-15 11:52:022007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) DUE TO THE PROXIMITY OF THE PROPOSED POOL TO THE
 EXISTING DWELLING, IT WILL BE NECESSARY TO PROVIDE
 SHORING TO PROTECT THE EXISTING FOUNDATION DURING
 CONSTRUCTION. SUBMIT TWO COPIES OF A SHORING PLAN FROM
 FLORIDA LICENSED ENGINEER. FBC 3304.1 AND FBC R
 403.1.7.2
  
 2) SOME OF THE BEARING LOADS OF THE DWELLING FOOTINGS
 MAY BE TRANSFERED AS LATERAL LOADS TO THE POOL WALLS.
 THIS SHOULD BE CONSIDERED IN THE POOL DESIGN. FBC
 R301.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-07-15 Cont ID  
Sent By rmcdouga Date 2011-07-15 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2011-07-15 Time 10:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-15 Cont ID  
Sent By rmcdouga Date 2011-07-15 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2011-06-28 Time 16:26 Sent To  
Notes
2011-07-12 07:35:58SENT TO RES SWIMMING POOL.
2011-06-28 16:26:54SENT TO ZONING SHELF FOR REVIEW.

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-07-29 Cont ID  
Sent By rbrown Date 2011-07-29 Time 16:36 Rev Time 0.00
Received By rbrown Date 2011-07-29 Time 16:36 Sent To  
Notes
2011-07-29 16:40:19BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 SHEET 2 OF 2 - POOL SYSTEM FLOW RATE
 REVISION REQUIRED TO INCREASE 2" PRESSURE PIPE TO 2.5"
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-07-15 Cont ID  
Sent By rmcdouga Date 2011-07-15 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2011-07-15 Time 07:12 Sent To  
Notes
2011-07-15 08:47:012007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE TDH CALCULATIONS ON SHEET 2 OF THE PLANS INCLUDE
 A POOL HEATER AND THE APPLICATION SPECIFIES NO POOL
 HEATER. WHEN THE TDH OF 18 IS REMOVED FROM THE
 CALCULATIONS THE TOTAL TDH IS 28.8. USING THE PUMP
 CURVE FOR THE 1 HP PENTAIR WHISPERFLO POOL PUMP THE
 FLOW RATE IS 110 GPM WITH A TDH OF 28.8. THE VELOCITY
 IN THE 2.5 " SUCTION LINES WILL BE 7.18 FT/SEC, WHICH
 IS ACCEPTABLE. HOWEVER, THE VELOCITY IN THE 2" RETURN
 PIPING IS 11.23 FT/SEC, WHICH EXCEEDS THE 10 FT/SEC
 ALLOWED BY FBC R4101.6.3. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2011-07-11 Cont ID  
Sent By jroach Date 2011-07-11 Time 10:56 Rev Time 0.00
Received By jroach Date 2011-07-05 Time 16:03 Sent To E
Notes
***NONE***