Plan Review Details - Permit 11060421
Plan Review Stops For Permit 11060421
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-21 Cont ID  
Sent By rmcdouga Date 2011-06-21 Time 08:15 Rev Time 0.00
Received By rmcdouga Date 2011-06-17 Time 10:53 Sent To  
Notes
2011-06-17 10:53:27TO RM DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-21 Cont ID  
Sent By rmcdouga Date 2011-06-21 Time 08:15 Rev Time 0.00
Received By rmcdouga Date 2011-06-21 Time 08:15 Sent To  
Notes
2011-06-21 09:20:382007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF REVISED MECHANICAL PLAN SHEET
 M102 WITH AN EQUIPMENT SCHEDULE THAT INCLUDES THE NEW
 AIR HANDLERS AND CONDENSING UNITS.
  
 2) SHOW COMPLIANCE WITH FBC M1305.1.2 FOR ACCESS TO
 APPLIANCES IN ATTICS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714