Plan Review Details - Permit 11060248
Plan Review Stops For Permit 11060248
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-31 Cont ID  
Sent By jwitmer Date 2011-08-31 Time 09:28 Rev Time 0.77
Received By jwitmer Date 2011-08-31 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-15 Cont ID  
Sent By jwitmer Date 2011-06-15 Time 12:05 Rev Time 3.33
Received By jwitmer Date 2011-06-15 Time 08:37 Sent To  
Notes
2011-06-15 12:39:30BUILDING PLAN REVIEW
 PERMIT: 11060248
 ADD: 3031 OKEECHOBEE BLVD
 CONT: POPPER & ASSOCIATES
 TEL: (561)719-7133
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-101-INT INDICATES A PARTS DEPARTMENT WHICH
 IS OVER 10% OF THE FIRST FLOOR AREA AND OVER 1,000 SQ
 FT. TABLE 508.3.3 REQUIRES A FIRE RATING BETWEEN THE
 PARTS DEPARTMENT AND BUSINESS/ MERCANTILE OCCUPANCIES.
 PLEASE REVIEW 2007/09 FBC-B TABLE 508.3.3. FOOTNOTE
 "B'. WILL ALSO NEED OPENING PROTECTIVE FOR DOOR
 OPENING. TABLE 715.4.
  
 2) IT ALSO APPEARS ON SHEET A-101-INT THERE IS TWO
 WINDOWS BETWEEN THIS BUILDING AND THE NEXT BUILDING (A
 MOTOR VEHICLE REPAIR GARAGE) THAT WOULD REQUIRE OPENING
 PROTECTIVES PER TABLE 715.4.
  
 3) SHEET A-101-INT NEW PARTITION BETWEEN PARTS AND
 RETAIL PARTS, PLEASE PROVIDE WALL DETAIL. 106.1.2
 ADDITIONAL INFORMATION.
  
 4) ACCESSIBILITY DISPROPORTIONATE COST: DUTY TO PROVIDE
 ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA: BREAKROOM
 IF SINK IS INSTALLED.
 (V) ACCESSIBLE DRINKING FOUNTAINS;
  
 4A) SHEET A-101-INT INDICATES A NEW BREAK ROOM, NO
 DETAILS PROVIDED OF ROOM, WILL THERE BE A SINK THAT
 WILL NEED TO MEET THE REQUIREMENTS OF
 11-4.24(1-7).
  
 4B) SHEET A-101-INT PLEASE INDICATE COMPLIANCE WITH
 11-4.15 DRINKING FOUNTAINS AND DRINKING COOLERS.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-09-07 Cont ID  
Sent By rlecky Date 2011-09-07 Time 07:19 Rev Time 0.00
Received By rlecky Date 2011-09-06 Time 16:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-06-20 Cont ID  
Sent By rlecky Date 2011-06-20 Time 09:36 Rev Time 0.00
Received By rlecky Date 2011-06-20 Time 09:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-08-30 Cont ID  
Sent By wjolin Date 2011-08-30 Time 10:41 Rev Time 0.00
Received By wjolin Date 2011-08-30 Time 10:13 Sent To  
Notes
2011-08-30 10:41:363031 OKEECHOBEE BOULEVARD
 PERMIT #11060248
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 VERIFY TRAVEL DISTANCE TO PORTABLE FIRE EXTINGUISHER
 DOES NOT EXCEED 75 FEET. SHEET A101-INT APPEARS TO SHOW
 ONLY ONE FIRE EXTINGUISHER .
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-06-14 Cont ID  
Sent By wjolin Date 2011-06-14 Time 13:25 Rev Time 0.00
Received By wjolin Date 2011-06-14 Time 10:31 Sent To  
Notes
2011-06-14 13:25:293031 OKEECHOBEE BOULEVARD
 PERMIT #11060248
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TRAVEL DISTANCE TO PORTABLE FIRE EXTINGUISHER EXCEEDS
 75 FEET.
  
 PROVIDE EXIT SIGN FOR NORTH OFFICE AREA.
  
 INDICATE WHERE NORTH OFFICE AREA HALL DOOR DISCHARGES
 TO.
  
 INDICATE IF THERE ARE EXISTING FIRE-RATED WALLS
 SEPARATING THE BUSINESS OCCUPANCY FROM THE PARTS
 (STORAGE) OCCUPANCY.
  
 NO NEW DOOR SCHEDULE PROVIDED.
  
 ROLL UP SECURITY GRILLS SHALL COMPLY WITH ALL FIVE
 REQUIREMENTS FOUND IN SECTION 7.2.1.4.1.4 OF NFPA 101 -
 LIFE SAFETY CODE FLORIDA EDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-09-07 Cont ID  
Sent By rlecky Date 2011-09-07 Time 07:19 Rev Time 0.00
Received By rlecky Date 2011-08-26 Time 14:37 Sent To  
Notes
2011-08-26 14:42:06SENT TO B13 FOR REVIEW BY ALL TRADES. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-14 Cont ID  
Sent By lmartine Date 2011-07-07 Time 08:41 Rev Time 0.00
Received By lmartine Date 2011-06-10 Time 16:43 Sent To  
Notes
2011-06-10 16:58:26B--13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-08-31 Cont ID  
Sent By jwitmer Date 2011-08-31 Time 09:34 Rev Time 0.50
Received By jwitmer Date 2011-08-31 Time 09:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-06-20 Cont ID  
Sent By hmoser Date 2011-06-20 Time 13:53 Rev Time 0.00
Received By hmoser Date 2011-06-20 Time 13:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-08-29 Cont ID  
Sent By lwagner Date 2011-08-29 Time 14:01 Rev Time 0.00
Received By lwagner Date 2011-08-29 Time 11:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-07-07 Cont ID  
Sent By lfranco Date 2011-07-07 Time 16:35 Rev Time 0.50
Received By lfranco Date 2011-07-07 Time 16:35 Sent To  
Notes
2011-07-07 16:49:59PLANNING AND ZONING: *** *ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ***