Plan Review Details - Permit 11060128
Plan Review Stops For Permit 11060128
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-07-12 Cont ID  
Sent By shill Date 2011-07-12 Time 15:03 Rev Time 0.00
Received By shill Date 2011-07-12 Time 15:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-07-07 Cont ID  
Sent By shill Date 2011-07-07 Time 08:57 Rev Time 0.00
Received By shill Date 2011-07-07 Time 08:57 Sent To  
Notes
2011-07-07 09:00:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. BOTTOM SUBSTRATE (PREVIOUSLY "BLOCK" ON THE
 INSTALLATION SCHEDULE) IS NOW CONCRETE. PLEASE ADVISE,
 ARE ALL OPENINGS SLIDING GLASS DOORS OR WINDOWS WHICH
 EXTEND TO THE FOUNDATION? WINDOWS IN CBS CONSTRUCTION
 TYPICALLY HAVE A BLOCK BOTTOM SUBSTRATE.
  
 AN ATTEMPT WAS MADE TO RESOLVE BY TELEPHONE. FOR THIS
 PERMIT, RESUBMITTAL CAN BE MADE VIA EMAIL. PLEASE FEEL
 FREE TO CONTACT ME TO DISCUSS. ALSO, AS DISCUSSED, FOR
 THE NEXT SHUTTER PERMIT APPLICATION CONTRACTOR CAN MAKE
 AN APPOINTMENT TO HAVE THE REVIEW DONE AS A TURNAROUND
 WITH THE CONTRACTOR (OR REP WHO IS FAMILIAR WITH BOTH
 JOB CONDITIONS AND TECHNICAL REQUIREMENTS) PRESENT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-06-23 Cont ID  
Sent By shill Date 2011-06-23 Time 12:19 Rev Time 0.00
Received By shill Date 2011-06-23 Time 12:19 Sent To  
Notes
2011-06-23 12:22:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE OPENINGS 1 & 2, 4.1" SPACING REQUIRED FOR BLOCK
 SUBSTRATE, TAPCON, C2 CONNECTION TYPE, 47PSF, SPAN
 BETWEEN 6-9', PLEASE REVISE INSTALLATION SCHEDULE, FBC
 R301.
  
 2. SEE OPENING 3, C4 CONNECTION NOT PERMITTED FOR
 TAPCON INTO BLOCK SUBSTRATE. PLEASE REVISE INSTALLATION
 SCHEDULE FBC R 301.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-09 Cont ID  
Sent By shill Date 2011-06-09 Time 09:03 Rev Time 0.00
Received By shill Date 2011-06-09 Time 09:03 Sent To  
Notes
2011-06-09 09:10:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. TWO COMPLETE SETS OF DOCUMENTS ARE REQUIRED FOR
 PERMIT ISSUANCE. FAILURE TO PROVIDE TWO SETS OF THE
 INSTALLATION SCHEDULE MAY RESULT IN PERMIT ISSUANCE
 DELAYS.
  
 2. SPANS ARE NOT CORRECT. FOR INSTANCE, SEE OPENING 1.
 OPENING IS W X H, VERTICAL INSTALLATION, SO SPAN SHOULD
 CORRELATE WITH OPENING HEIGHT, NOT WIDTH.
  
 3. 9" ANCHOR SPACING PROPOSED FOR BOTTOM CONNECTION
 DOES NOT COMPLY WITH THE CHART ON SHEET 10 OF THE
 PRODUCT APPROVAL. PLEASE REVISE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-07-07 Cont ID  
Sent By shill Date 2011-07-07 Time 09:00 Rev Time 0.00
Received By shill Date 2011-06-28 Time 13:30 Sent To  
Notes
2011-06-28 13:30:54SENT TO SAMANTHA'S DESK FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-23 Cont ID  
Sent By shill Date 2011-06-23 Time 12:23 Rev Time 0.00
Received By shill Date 2011-06-17 Time 10:26 Sent To  
Notes
2011-06-17 10:27:23INCOMING SENT TO SAMANTHA H DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-09 Cont ID  
Sent By shill Date 2011-06-09 Time 09:10 Rev Time 0.00
Received By shill Date 2011-06-06 Time 11:27 Sent To  
Notes
2011-06-06 11:27:28UNDER 5 K BUILDING