Plan Review Details - Permit 11060005
Plan Review Stops For Permit 11060005
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-06-10 Cont ID  
Sent By jleahy Date 2011-06-10 Time 07:41 Rev Time 0.00
Received By jleahy Date 2011-06-10 Time 07:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2011-06-23 Cont ID  
Sent By lwagner Date 2011-06-23 Time 08:58 Rev Time 0.00
Received By lwagner Date 2011-06-23 Time 08:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2011-06-13 Cont ID  
Sent By lwagner Date 2011-06-13 Time 09:35 Rev Time 0.00
Received By lwagner Date 2011-06-10 Time 13:14 Sent To  
Notes
2011-06-13 09:35:10FBC 2007 FUEL GAS REVISION # 1
 DENIED:
  
 LP TANK IS NOT SHOWN ON PLAN.
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-29 Cont ID  
Sent By lmartine Date 2011-06-29 Time 09:00 Rev Time 0.00
Received By lmartine Date 2011-06-24 Time 17:14 Sent To  
Notes
2011-06-24 17:14:55IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-13 Cont ID  
Sent By lwagner Date 2011-06-13 Time 14:18 Rev Time 0.00
Received By lwagner Date 2011-06-02 Time 07:53 Sent To  
Notes
2011-06-02 07:54:21SENT TO ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2011-06-28 Cont ID  
Sent By eschneid Date 2011-06-28 Time 16:40 Rev Time 0.25
Received By eschneid Date 2011-06-28 Time 14:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-06-08 Cont ID  
Sent By eschneid Date 2011-06-08 Time 08:33 Rev Time 0.75
Received By eschneid Date 2011-06-03 Time 13:08 Sent To E
Notes
2011-06-08 08:52:04FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE 2009 PROPERTY APPRAISER AERIAL OF THE SITE SHOWS
 A FENCE AND A TREE IN THE AREA OF THE PROPOSED
 GENERATOR. NEITHER OF THESE ARE SHOWN ON THE SUBMITTED
 SURVEY. PROVIDE A RECENT SURVEY, LESS THAN ONE YEAR
 OLD, WHICH SHOWS THE LOCATION OF THE FENCE AND THE
 LOCATION OF ANY TREES IN THE IMMEDIATE VICINITY OF THE
 PROPOSED GENERATOR.
  
 2) THE PROPOSED GENERATOR SHALL BE SHOWN ON THE NEW
 SURVEY.
  
 3) ANY TREES OR SHRUBS IMPACTED BY THE PROPOSED
 GENERATOR SHALL BE RELOCATED ON-SITE. THE RELOCATION OF
 A TREE WOULD REQUIRE THE ISSUANCE OF A TREE ALTERATION
 PERMIT BY THE PLANNING AND ZONING DEPARTMENT. IF NO
 TREES OR SHRUBS WILL BE IMPACTED, PLEASE PROVIDE A
 STATEMENT TO THAT EFFECT.
  
 4) WHERE WILL THE 500 GALLON FUEL TANK BE LOCATED? IF
 THIS TANK IS TO BE LOCATED ABOVE GROUND, THEN IT SHALL
 BE SCREENED FROM THE ADJACENT RIGHTS-OF-WAY AND THE
 NEIGHBORING PROPERTY. PROVIDE SCREENING DETAILS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.