Plan Review Stops For Permit 11050497 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2011-08-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-08-08 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-08-05 |
Time |
10:30 |
Sent To |
|
|
Notes |
2011-08-08 09:41:23 | BUILDING PROVISO | | | | PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE NEW | | INSWING EXTERIOR DOOR AT THE LAUNDRY ROOM. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2011-07-12 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-07-12 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-07-12 |
Time |
06:47 |
Sent To |
E |
|
Notes |
2011-07-12 11:44:07 | 2007 FBC W/2009 REVISIONS | | | | 2ND REVIEW | | DENIED BY BUILDING | | | | 1) ADDRESSED. | | | | 2) ADDRESSED. | | | | 3) SPECIFY THE ONE HOUR FIRE-RESISTANCE RATED | | FLOOR/CEILING TESTED ASSEMBLY THAT WILL BE INSTALLED. | | PROVIDE A SECTION DETAIL OF THE TESTED ASSEMBLY WITH | | THE FILE OR LISTING NUMBER. FBC R 317. * THE SEPARATE | | DRAWING THAT WAS SUBMITTED (ASSEMBLY WS6-1.5) IS FOR A | | 2 X 6 WOOD WALL ASSEMBLY. THE PLANS SPECIFY 2 X 4 WALLS | | AND A ONE HOUR FIRE RATED 2 X 6 FLOOR/CEILING ASSEMBLY | | IS REQUIRED. | | | | 4) SHOW COMPLIANCE WITH FBC R317.1.1 SUPPORTING | | CONSTRUCTION WHICH REQUIRES THE WALLS SUPPORTING THE | | ONE HOUR FIRE-RESISTANCE RATED FLOOR/CEILING TO HAVE AN | | EQUAL OR GREATER FIRE-RESISTIVE RATING. PROVIDE A | | SECTION DETAIL OF THE TESTED ASSEMBLY WITH THE FILE OR | | LISTING NUMBER. * THE UL DESIGN SPECIFIED ON THE PLANS | | ( DESIGN NUMBER U 448 ) IS FOR A NON- BEARING STEEL | | STUD WALL. THE PLANS AND YOUR SPAN CALCULATIONS | | INDICATE TWO INTERIOR BEARING WOOD FRAME WALLS WITH 2 X | | 4 STUDS 24" O.C. | | | | 5) ADDRESSED. | | | | 6) SHOW COMPLIANCE WITH FBC R602.1.2 FOR THE FIRE | | BLOCKING THAT IS REQUIRED IN THE BALLOON FRAMED WALLS | | AT THE CEILING AND FLOOR LEVELS. * THE FIREBLOCKING IS | | REQUIRED AT THE CEILING OF THE FIRST FLOOR UNIT AND AT | | THE FLOOR OF THE SECOND FLOOR UNIT. | | | | 7) ADDRESSED. | | | | 8) ADDRESSED. PLANS AND CALCULATIONS INDICATE TWO | | INTERIOR BEARING WALLS. | | | | 9) THE STAIRWAYS AND HANDRAILS ARE REQUIRED TO COMPLY | | WITH FBC R311.5. THE PLANS SITE SBC 1608.2.1 AND 1007 | | WHICH NO LONGER APPLY. CORRECT SHEET A-3. NOT | | ADDRESSED. | | | | 10) ADDRESSED. | | | | 11) ADDRESSED. | | | | 12) THE PLANS INDICATE A NEW EXTERIOR DOOR INSTALLED ON | | THE LAUNDRY ROOM. SUBMIT TWO COPIES OF PRODUCT | | APPROVALS FOR THE DOOR AS REQUIRED BY DCA RULE 9N-3. * | | THE PRODUCT APPROVAL MIAMI-DADE NOA THAT WAS SUBMITED | | IS FOR AN OUTSWING DOOR AND THE FILE HAS BEEN CLOSED | | AND IS NO LONGER VALID. SUBMIT TWO COPIES OF A CURRENT | | PRODUCT APPROVAL FOR THE EXTERIOR INSWING DOOR | | SPECIFIED ON THE PLANS. | | | | 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | AMENDMENTS 106.3.3 * NEW DOOR PRODUCT APPROVALS WILL | | NEED TO BE REVIEWED AND APPROVED BY DESIGNER OF RECORD. | | | | 14) ADDRESSED. | | | | 15) ADDRESSED. | | | | 16) ADDRESSED. | | | | 17) SUBMIT A RESPONSE LETTER INDICATING HOW THE REVIEW | | COMMENTS HAVE BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2011-06-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-09 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-08 |
Time |
07:10 |
Sent To |
|
|
Notes |
2011-06-08 11:21:07 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) THE WRONG EXPOSURE CATEGORY IS SPECIFIED ON THE | | PLANS. THE CORRECT EXPOSURE IS 'C' PER FBC R | | 301.2.1.4.3. | | | | 2) THE STRUCTURE IS NOT A SINGLE FAMILY HOME BECAUSE IT | | HAS TWO SEPARATE DWELLING UNITS. IT IS A TWO-FAMILY | | DWELLING. FBCR CHAPTER 2. | | | | 3) SPECIFY THE ONE HOUR FIRE-RESISTANCE RATED | | FLOOR/CEILING TESTED ASSEMBLY THAT WILL BE INSTALLED. | | PROVIDE A SECTION DETAIL OF THE TESTED ASSEMBLY WITH | | THE FILE OR LISTING NUMBER. FBC R 317.1 | | | | 4) SHOW COMPLIANCE WITH FBC R317.1.1 SUPPORTING | | CONSTRUCTION WHICH REQUIRES THE WALLS SUPPORTING THE | | ONE HOUR FIRE-RESISTANCE RATED FLOOR/CEILING TO HAVE AN | | EQUAL OR GREATER FIRE-RESISTIVE RATING. PROVIDE A | | SECTION DETAIL OF THE TESTED ASSEMBLY WITH THE FILE OR | | LISTING NUMBER. | | | | 5) SHOW COMPLIANCE WITH FBC R317.3 WHICH REQUIRES | | PENETRATIONS OF FIRE-RESISTANCE RATED WALL OR | | FLOOR/CEILING ASSEMBLIES TO BE PROTECTED. | | | | 6) SHOW COMPLIANCE WITH FBC R602.1.2 FOR THE FIRE | | BLOCKING THAT IS REQUIRED IN THE BALLOON FRAMED WALLS | | AT THE CEILING AND FLOOR LEVELS. | | | | 7) THE BEARING WALL SUPPORTING THE FLOOR/CEILING | | ASSEMBLY IS NOT SHOWN AS BEING CONTINUOUS ON THE PLANS. | | PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE FLOOR | | JOISTS ARE BEING AT THE OPENING TO THE FIRST FLOOR | | KITCHEN. FBC R601.2 | | | | 8) THE PLANS SPECIFY 2 X 6 FLOOR JOISTS AT 16" OC | | SPANNING MORE THAN 13 FEET WITH A REQUIRED LIVE LOAD OF | | 40 PSF. THIS EXCEEDS THE ALLOWABLE JOIST SPANS OF FBCR | | TABLE R502.2.3(2). | | | | 9) THE STAIRWAYS AND HANDRAILS ARE REQUIRED TO COMPLY | | WITH FBC R311.5. THE PLANS SITE SBC 1608.2.1 AND 1007 | | WHICH NO LONGER APPLY. CORRECT SHEET A-3. | | | | 10) THE GUARDS ARE REQUIRED TO COMPLY WITH FBC R312. | | CORRECT SHEET A-3. | | | | 11) THE OPENINGS FOR THE GUARDS SHOWN ON A-2 OF THE | | PLANS, DO NOT COMPLY WITH FBC R312.2 GUARD OPENING | | LIMITATIONS. THE OPENINGS FOR GUARDS ON THE SIDES OF | | STAIR TREADS SHALL NOT ALLOW A 4-3/8" DIA. SPHERE TO | | PASS THROUGH. | | | | 12) THE PLANS INDICATE A NEW EXTERIOR DOOR INSTALLED ON | | THE LAUNDRY ROOM. SUBMIT TWO COPIES OF PRODUCT | | APPROVALS FOR THE DOOR AS REQUIRED BY DCA RULE 9N-3. | | | | 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | AMENDMENTS 106.3.3 | | | | 14) THE SCOPE OF WORK DOES NOT INDICATE THAT THE | | WINDOWS ARE BEING REPLACED, HOWEVER, A WINDOW LEGEND IS | | SPECIFIED ON SHEET A-1. IF THE WINDOWS ARE TO BE | | REPLACED PROVIDE THE APPROPRIATE PRODUCT APPROVALS AS | | REQUIRED BY DCA RULE 9N-3. | | | | 15) SPECIFY ON THE PLANS THE DWELLING UNITS THAT WILL | | HAVE USE OF THE LAUNDRY ROOM. FBC R101.2 | | | | 16) THE SHARED LAUNDRY ROOM WILL BE REQUIRED TO HAVE | | ONE HOUR FIRE-RESISTANCE RATED SEPARATION FROM BOTH | | UNITS. FBC R317.1 | | | | 17) SUBMIT A RESPONSE LETTER INDICATING HOW THE REVIEW | | COMMENTS HAVE BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2011-08-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-08-08 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-08-08 |
Time |
09:30 |
Sent To |
|
|
Notes |
2011-08-08 09:37:58 | ELECTRICAL PROVISO | | | | 1) PROVIDE A REVISED PANEL "C" SCHEDULE TO THE | | ELECTRICAL FIELD INSPECTOR. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2011-07-12 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-07-12 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2011-07-12 |
Time |
13:10 |
Sent To |
|
|
Notes |
2011-07-12 13:44:46 | PROVISO: | | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | GROUND. NEC 250.94 | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | INDIVIDUAL SERVICE WIRE SIZE MUST BE #3 FOR 100 | | AMPERES. NEC T 310.16 | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | R313 | | MAINTAIN REQUIRED SAFETY AND ACCESS CLEARANCES FOR | | ELECTRIC PANEL BOARDS. NEC 110.26 | | | | | | | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2011-06-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-09 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-09 |
Time |
07:01 |
Sent To |
|
|
Notes |
2011-06-09 08:42:55 | 2007 FBC W/2009 REVISIONS | | 2008 NEC | | | | DENIED BY ELECTRIC | | | | 1) SUBMIT LOAD CALCULATIONS FOR THE SERVICE TO VERIFY | | THAT THE #1 WIRE SIZE IS ADEQUATE. ART. 215.5 & 220.40 | | | | 2) MATCH PANELS TO SERVICE RISER. THE RISER SHOWS THREE | | METER CANS LABELED 'D', 'C', 'E' AND THE ELECTRICAL | | FLOOR PLAN SHOWS 2 METERS AND DISCONNECTS AND THREE | | PANELS LABELED 'A', 'B', 'C'. ART. 110.22(A) | | | | 3) PROVIDE A PANEL SCHEDULE ON THE PLANS FOR THE 60 AMP | | PANEL OFF OF METER 'E'. ART408.4 | | | | 4) ALL OUTLETS ARE REQUIRED TO BE TAMPER RESISTANT. | | ART. 406.11 | | | | 5) ALL 15 AND 20 AMP BRANCH CIRCUITS ARE REQUIRED TO BE | | ARC FAULT PROTECTED EXCEPT THE KITCHEN, BATH ROOM AND | | OUTSIDE. ART. 210.12 | | | | 6) AT LEAST ONE GFCI RECEPTACLE OUTLET IS REQUIRED AT | | THE FRONT AND BACK OF THE DWELLING. ART. 210.52(E)(1) | | | | 7) PLEASE CLARIFY THAT THIS SERVICE IS ONLY FOR THE TWO | | STORY RESIDENCE IDENTIFIED ON THE SITE PLAN AS 423-A. | | IS THERE A SEPARATE SERVICE FOR THE OTHER TWO STORY | | RESIDENCE IDENTIFIED AS #423 ON THE SITE PLAN. ART. | | 215.5 | | | | 8) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2011-08-09 |
|
|
Cont ID |
|
Sent By |
jpapa |
Date |
2011-08-09 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
jpapa |
Date |
2011-08-09 |
Time |
14:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2011-06-09 |
|
|
Cont ID |
|
Sent By |
jpapa |
Date |
2011-06-08 |
Time |
16:49 |
Rev Time |
0.25 |
Received By |
jpapa |
Date |
2011-06-09 |
Time |
10:19 |
Sent To |
|
|
Notes |
2011-06-08 16:50:47 | PROVISO | | | | 1. THE PROPOSED WINDOW AND DOOR PRODUCTS (NOAS) MUST BE | | REVIEWED AND APPROVED PRIOR TO ISTALLATION. VINYL | | PRODUCTS SHALL NOT BE PERMITTED. | | | | FOR MORE INFORMATION, PLEASE CONTACT JILLIAN PAPA, | | HISTORIC PRESERVATION PLANNER, 561-822-1454. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2011-08-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-08-08 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-08-04 |
Time |
11:30 |
Sent To |
|
|
Notes |
2011-08-04 11:37:33 | SENT TO R2 SHELF FOR BUILDING, ELECTRICAL AND PLUMBING | | REVIEW. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2011-07-14 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2011-07-12 |
Time |
13:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-07-08 |
Time |
11:12 |
Sent To |
|
|
Notes |
2011-07-08 11:12:55 | TO RM DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2011-06-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-09 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-05-18 |
Time |
09:16 |
Sent To |
|
|
Notes |
2011-05-18 09:19:13 | INCOMING SENT TO R-15 BOX. JW |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2011-06-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-08 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-08 |
Time |
07:21 |
Sent To |
|
|
Notes |
2011-06-08 07:22:29 | NO MECHICANICAL PERMIT WAS APPLIED FOR AND NO | | MECHANICAL PLANS WERE SUBMITTED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2011-08-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-08-05 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-08-05 |
Time |
09:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2011-07-12 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-07-12 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-07-12 |
Time |
12:06 |
Sent To |
|
|
Notes |
2011-07-11 15:40:25 | 2007 FBC W/2009 REVISIONS | | | | 2ND REVIEW | | DENIED BY PLUMBING | | | | 1) THE SECOND FLOOR BATH ROOM IS NOT VENTED CORECTLY. | | FBC R3108.2 ONLY ALLOWS ONE WET-VENTED FIXTURE DRAIN TO | | DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN | | CONNECTION. * STILL INCORRECT. THE LAVATORY DRAIN AND | | VENT NEEDS TO TIE INTO BUILDING DRAIN BETWEEN THE TUB | | AND WATER CLOSET. | | | | 2) ADDRESSED. | | | | 3) ADDRESSED. | | | | 4) ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2011-06-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2011-06-07 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2011-06-07 |
Time |
14:24 |
Sent To |
|
|
Notes |
2011-06-07 15:08:14 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) THE SECOND FLOOR BATH ROOM IS NOT VENTED CORECTLY. | | FBC R3108.2 ONLY ALLOWS ONE WET-VENTED FIXTURE DRAIN TO | | DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN | | CONNECTION. | | | | 2) THE 2" WASHING MACHINE DRAIN IS REQUIRED TO CONNECT | | TO A MINIMUM 3" DIAMETER BRANCH DRAIN OR DRAINAGE STACK | | PER FBC P 406.3. | | | | 3) IS THE LAUNDRY ROOM FOR THE USE OF THE TWO UNITS IN | | THIS BUILDING ONLY? SPECIFY THE NUMBER OF UNITS THAT | | WILL BE USING THE LAUNDRY ROOM ON THE PLANS. FBC P412.4 | | | | 4) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2011-08-09 |
|
|
Cont ID |
|
Sent By |
jpapa |
Date |
2011-08-09 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
jpapa |
Date |
2011-08-09 |
Time |
14:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2011-06-08 |
|
|
Cont ID |
|
Sent By |
jpapa |
Date |
2011-06-08 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
jpapa |
Date |
2011-06-08 |
Time |
16:47 |
Sent To |
|
|
Notes |
2011-06-08 16:49:06 | THE VALUE OF THE PROPOSED SCOPE OF WORK DOES NOT EXCEED | | 50% OF THE ASSESSED VALUE AT THIS TIME. | | | | JILLIAN PAPA | | HISTORIC PRESERVATION PLANNER | | 561-822-1454 |
|
|