Plan Review Details - Permit 11050304
Plan Review Stops For Permit 11050304
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-05-21 Cont ID  
Sent By jwitmer Date 2012-05-21 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2012-05-21 Time 10:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-12-27 Cont ID  
Sent By jwitmer Date 2011-12-27 Time 09:14 Rev Time 2.22
Received By jwitmer Date 2011-12-21 Time 13:32 Sent To  
Notes
2011-12-27 09:28:56BUILDING PLAN REVIEW
 PERMIT: 11050304
 ADD: 1225 PALM BEACH LAKES BLVD
 CONT: CILAS CONCRETE CONSTRUCTION
 TEL: (561)252-8429
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2009 FLORIDA EXISTING BUILDING CODE / 2009 SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SHEET A-1 INDICATES NEW PLAY AREA PLEASE PROVIDE THE
 FOLLOWING INFORMATION REQUIRED BY 2007 FBC-B
 106.3.5.1.1:
 2A)COMPLIED.
 2B) COMPLIED- BUILDING NOT SPRIVKLERED.
 2C) COMPLIED.
 2D) SEMI-COMPLIED. FLOOR PLAN/ LIFE SAFETY PLAN/ EGRESS
 INCLUDE; OCCUPANCY LOAD/GROSS/ NET/ EXIT ACCESS & EXITS
 PLEASE PROVIDE OCCUPANT LOADS FOR THE ROOMS AND
 INCIDENTAL USE AREAS INDICATED ON SHEET #1 AND TOTAL
 LOAD.
 12/27/2011 PLANS INDICATE AN OCCUPANT LOAD BASED ON 36
 SQ FT / OCCUPANT PLEASE REVIEW TABLE 1004.1.1 DAYCARE
 20/ NET
  
 3) SEMI COMPLIED. FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
  
 3A) NEW EXTERIOR DOOR. PLEASE REVIEW REQUIREMENTS FOR:
 1034.1 PANIC AND FIRE EXIT HARDWARE.
 1034.1.1 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE
 WHICH RELEASES WHEN A FORCE OF NO MORE THAN 15 POUNDS
 (67 N) IS APPLIED TO THE RELEASING DEVICES IN THE
 DIRECTION OF EXIT TRAVEL. SUCH RELEASING DEVICES MAY BE
 BARS OR PANELS EXTENDING NOT LESS THAN ONE-HALF THE
 WIDTH OF THE DOOR AND PLACED AT HEIGHTS SUITABLE FOR
 THE SERVICE REQUIRED, BUT NOT LESS THAN 34 INCHES (864
 MM) NOR MORE THAN 48 INCHES (1219 MM) ABOVE THE FLOOR.
 WHENEVER PANIC HARDWARE IS USED ON A LABELED FIRE DOOR,
 THE PANIC HARDWARE SHALL BE LABELED AS FIRE EXIT
 HARDWARE.
  
 3B) NEW- EGRESS WINDOWS
  
 4) SEMI COMPLIED WILL NEED TO REVIEW PANIC & FIRE
 HARDWARE FOR ALL EXTERIOR DOORS. 106.3.3 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 NEW COMMENTS NEW CHANGE OF OCCUPANCY PLANS AND SITE
 PLAN.
  
 5-9) COMPLIED.
  
 10) NO PRODUCT APPROVAL FOR THE NEW WINDOWS IN
 CLASSROOMS COMPLYING WITH :2007/09 FBC-B 1026.4.1 EVERY
 ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2 M2) IN
 EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR OTHER
 EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO STUDENT
 OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT OCCUPANCY, OTHER THAN BATHROOMS, IN GROUP D
 OCCUPANCIES SHALL HAVE NOT LESS THAN ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE THAT COMPLIES WITH THE FOLLOWING:
  
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
  
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 11) COMPLIED.
  
 12) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE
 SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 13) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
  
 14) NOT REQUIRED NO LAUNDRY!
  
 15) NORTHWEST CORRIDOR MARKED AS "NO EXIT WHICH CREATES
 A DEAD-END CORRIDOR OVER 20'-0" LONG. FBC-B 1017.3.
 DEAD END CORRIDOR CAN'T BE OVER 20'-0" IN LENGTH.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-10-25 Cont ID  
Sent By jwitmer Date 2011-10-25 Time 16:22 Rev Time 0.00
Received By jwitmer Date 2011-10-19 Time 10:00 Sent To  
Notes
2011-10-19 11:14:55BUILDING PLAN REVIEW
 PERMIT: 11050304
 ADD: 1225 PALM BEACH LAKES BLVD
 CONT: CILAS CONCRETE CONSTRUCTION
 TEL: (561)252-8429
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2009 FLORIDA EXISTING BUILDING CODE / 2009 SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION SCOPE OF WORK INDICATES THE
 INFILL OF PATIO NEW MASONRY AND WINDOWS, PLEASE
 INDICATE THIS IS A CHANGE IN OCCUPANCY!!!!
  
  
 2) SHEET A-1 INDICATES NEW PLAY AREA PLEASE PROVIDE THE
 FOLLOWING INFORMATION REQUIRED BY 2007 FBC-B
 106.3.5.1.1:
 2A)COMPLIED.
 2B) SEMI-COMPLIED. MINIMUM BLDG TYPE WILL BE REQUIRED
 SINCE THIS IS A CHANGE OF OCCUPANCY/ COMPLIED
 SPRINKLERED- YES.
 SHEET A-0 UNDER THE HEADING OCCUPANCY/ USE PLEASE
 CORRECT BUILDING TYPE AS III-B PROTECTED THE B
 DESIGNATION IS UNPROTECTED, A IS PROTECTED SEE TABLE
 601.
 2C) COMPLIED.
 2D) SEMI-COMPLIED. FLOOR PLAN/ LIFE SAFETY PLAN/ EGRESS
 INCLUDE; OCCUPANCY LOAD/GROSS/ NET/ EXIT ACCESS & EXITS
 PLEASE PROVIDE OCCUPANT LOADS FOR THE ROOMS AND
 INCIDENTAL USE AREAS INDICATED ON SHEET #1 AND TOTAL
 LOAD.
  
 3) SEMI COMPLIED. FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS: NEW EXTERIOR DOOR.
 PLEASE REVIEW REQUIREMENTS FOR:
 1034.1 PANIC AND FIRE EXIT HARDWARE.
 1034.1.1 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE
 WHICH RELEASES WHEN A FORCE OF NO MORE THAN 15 POUNDS
 (67 N) IS APPLIED TO THE RELEASING DEVICES IN THE
 DIRECTION OF EXIT TRAVEL. SUCH RELEASING DEVICES MAY BE
 BARS OR PANELS EXTENDING NOT LESS THAN ONE-HALF THE
 WIDTH OF THE DOOR AND PLACED AT HEIGHTS SUITABLE FOR
 THE SERVICE REQUIRED, BUT NOT LESS THAN 34 INCHES (864
 MM) NOR MORE THAN 48 INCHES (1219 MM) ABOVE THE FLOOR.
 WHENEVER PANIC HARDWARE IS USED ON A LABELED FIRE DOOR,
 THE PANIC HARDWARE SHALL BE LABELED AS FIRE EXIT
 HARDWARE.
  
 4) SEMI COMPLIED WILL NEED TO REVIEW PANIC & FIRE
 HARDWARE FOR ALL EXTERIOR DOORS. 106.3.3 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 NEW COMMENTS NEW CHANGE OF OCCUPANCY PLANS AND SITE
 PLAN.
  
 5) THE LANSCAPE AND SITE PLAN WILL PROBABLY BE A
 SEPERATE PERMIT, PLEASE NOTE ACCESSIBLE PARKING SPOTS
 (2) AND THE PLANS INDICATING ACCESS AISLE BEHIND THE
 ACCESSIBLE SPACE. FBC-B 11-4.6.2(1) (GRAY BOX FL
 SPECIFIC) ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE
 ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT
 USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
  
 6) IT APPEARS THIS BUILDING WILL BE A MIXED OCCUPANCY
 WITH DAY CARE (BABIES) AND EDUCATIONAL (KINDERGARDEN
 AND FIRST GRADE). THE DESIGNER WILL NEED TO INDICATE
 COMPLIANCE WITH EITHER FLC-B 508.313 OR 508.3.2 AND
 SHOW COMPLIANCE.
  
 7) DISCREPANCY IN CLASSROOM THAT IS 25'-0" WIDE (ALL
 CLASSROOMS NOT LABELED OR IDENTIFIED) PLEASE REVIEW
 DOOR SWING BY EXIT BY STORAGE AREA SHEET A1 VERSES LIFE
 SAFETY SHEET.
 ROOM NOT IDENTIFIED FOR WHAT AGE CHILDREN PLEASE REVIEW
 1028.3 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR
 SHALL BE RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR
 TRAFFIC; ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES
 (3.1 RAD) TO STOP AGAINST THE WALL. DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED CORRIDOR WIDTH
 BY MORE THAN ONE-HALF.
  
 8) SHEET A1 WALL LEGEND INDICATES WALL TYPE 3 TO BE A
 EXISTING 1 HOUR WALL WHERE AS DETAIL W3 INDICATES THE
 WALL STOPPING 6 INCHES ABOVE THE CEILING. PLEASE SEE
 WALL LEGEND
 W4 IS AN EXISTING INTERIOR WALL WHERE AS DETAIL W4
 INDICATES A 1-0 HOUR RATED WALL TO THE ROOF DECK ABOVE,
 DISCREPANCY PLEASE CORRECT.
  
 9) SHEET A1 INDICATES WHAT APEARS TO BE 1-0 RATED
 CORRIDOR BY THE WALL LEGEND BUT THERE IS A 1ST GRADE
 CLASS IN THE MIDDLE OF THIS CORRIDOR? PLEASE PROVIDE
 EXPLANATION.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 10) PLANS INDICATE BUILDING TO BE SPRINKLERED NOTE 5 ON
 LS SHEET, PLEASE PROVIDE SPRINKLER PLANS, PLEASE NOTE
 IF SPRINKLER SYSTEM IS SUPERVISED.
 2007/09 FBC-B 1026.4.1 EVERY ROOM OR SPACE GREATER THAN
 250 SQUARE FEET (23.2 M2) IN EDUCATIONAL OCCUPANCIES
 USED FOR CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR
 NORMALLY SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM OR
 SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN
 BATHROOMS, IN GROUP D OCCUPANCIES SHALL HAVE NOT LESS
 THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH THE FOLLOWING:
  
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
  
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 11) 36.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE
 SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE
 CLOSET.
  
 12) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE
 SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 13) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
  
 14) NOTE PLANS DO NOT INDICATE ANY AREA WHERE CLEANING
 SUPPLIES WILL BE KEPT IN A SAME ROOM NOR IF THERE IS A
 LAUNDRY ROOM. WATER HEATER IS ALSO MISSING FROM LS
 PLAN.
 436.6.2 THE FOLLOWING ROOMS OR SPACES SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING BY FIRE
 BARRIERS HAVING A FIRE RESISTANCE RATING OF NOT LESS
 THAN 1 HOUR AND SHALL BE PROTECTED BY AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM.
  
 1. LAUNDRIES.
  
 2. MAINTENANCE SHOPS, INCLUDING WOODWORKING AND
 PAINTING AREAS.
  
 3. ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE BUILDING
 OFFICIAL.
  
 4. ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
  
 EXCEPTION: FOOD PREPARATION FACILITIES PROTECTED IN
 ACCORDANCE WITH NFPA 96 SHALL NOT BE REQUIRED TO HAVE
 OPENINGS PROTECTED BETWEEN FOOD PREPARATION AREAS AND
 DINING AREAS. WHERE DOMESTIC COOKING EQUIPMENT IS USED
 FOR FOOD WARMING OR LIMITED COOKING, PROTECTION OR
 SEGREGATION OF FOOD PREPARATION FACILITIES SHALL NOT BE
 REQUIRED IF APPROVED BY THE BUILDING OFFICIAL.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-20 Cont ID  
Sent By jwitmer Date 2011-05-20 Time 09:38 Rev Time 2.22
Received By jwitmer Date 2011-05-17 Time 15:15 Sent To  
Notes
2011-05-17 15:16:27BUILDING PLAN REVIEW
 PERMIT: 11050304
 ADD: 1225 PALM BEACH LAKES BLVD
 CONT: CILAS CONCRETE CONSTRUCTION
 TEL: (561)252-8429
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2009 FLORIDA EXISTING BUILDING CODE / 2009 SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION SCOPE OF WORK INDICATES THE
 INFILL OF PATIO NEW MASONRY AND WINDOWS, PLEASE CONFIRM
 THE FOLLOWING:
  
 1A) IS THIS AN ADDITION? OR BLCOK WALL INFILL OF A
 EXISTING ROOFED OVER AREA?
  
 1B) THE LAST BUSINESS TAX REGISTRATION FOR THE CITY
 INDICATES THIS TO BE A RESTARAUNT, IS THIS A CHANGE OF
 OCCUPANCY SINCE THE DRAWINGS ARE LISTED UNDER THE
 HEADING OF KIDS KALEIDOSCOPE, PLAY AREA?
 IF SO THE REQUIREMENTS OF 901.3 2007/09 FL EXT BLDG
 CODE WILL BE ENACTED. 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902
 THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 2) SHEET A-1 INDICATES NEW PLAY AREA PLEASE PROVIDE THE
 FOLLOWING INFORMATION REQUIRED BY 2007 FBC-B
 106.3.5.1.1:
 2A)OCCUPANCY
 2B) MINIMUM BLDG TYPE/ SPRINKLERED?
 2C) BUILDING SQ FT
 2D) FLOOR PLAN/ LIFE SAFETY PLAN/ EGRESS
 INCLUDE; OCCUPANCY LOAD/GROSS/ NET/ EXIT ACCESS & EXITS
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS: WINDOWS
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-10-19 Cont ID  
Sent By rlecky Date 2011-10-19 Time 11:43 Rev Time 0.00
Received By rlecky Date 2011-10-19 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2012-05-10 Cont ID  
Sent By rferguso Date 2012-05-10 Time 15:54 Rev Time 0.00
Received By rferguso Date 2012-05-10 Time 15:53 Sent To B
Notes
2012-05-10 15:59:0505/10/2012 PLANS REVIEWED BY FIRE ****APPROVED****
  
 1. COMMENTS ADDRESSED
  
 RONALD E.FERGUSON ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE PREVENTION
 (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2011-12-02 Cont ID  
Sent By wjolin Date 2011-12-02 Time 12:49 Rev Time 0.00
Received By wjolin Date 2011-12-02 Time 11:32 Sent To  
Notes
2011-12-02 12:49:021225 PALM BEACH LAKES BOULEVARD
 PERMIT #11050304
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE OCCUPANT LOAD OF 94 ON SHEET A0 DOES NOT MATCH THE
 INDIVIDUAL ROOM OCCUPANT LOADS PROVIDED ON SHEET A1.
  
 EXIT ACCESS CORRIDORS SHALL PROVIDE DIRECT ACCESS TO
 EXITS WITHOUT PASSING THROUGH INTERVENING ROOMS.
  
 THE NORTHWEST CORRIDOR HAS A DEAD-END EXCEEDING 20 FEET
 OF TRAVEL.
  
 SHEET LS1 INDICATES A MIXED USE OCCUPANCY OF EDUCATION
 AND DAY CARE. EDUCATIONAL OCCUPANCIES REQUIRE 6 FEET
 WIDE EXIT ACCESS CORRIDORS.
  
 PROVIDE MECHANICAL PLAN SHOWING ALL DUCT SMOKE
 DETECTORS AND FIRE DAMPERS.
  
 FIRE ALARM CONSTRUCTION DOCUMENTS WERE NOT SUBMITTED
 WITH THE DESIGN DRAWINGS.
  
 A COMPLETE SMOKE DETECTION SYSTEM SHALL BE INTEGRATED
 WITH THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-10-25 Cont ID  
Sent By wjolin Date 2011-10-25 Time 13:26 Rev Time 0.00
Received By wjolin Date 2011-10-25 Time 12:00 Sent To  
Notes
2011-10-25 13:26:511225 PALM BEACH LAKES BOULEVARD
 PERMIT #11050304
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 DIRECTING OCCUPANTS TO EXIT THROUGH A STORAGE AREA IS
 NOT PERMITTED.
  
 WALL DETAIL THREE DOES NOT APPEAR TO PROVIDE A ONE-HOUR
 FIRE RATING.
  
 PROVIDE A DOOR AND HARDWARE SCHEDULE.
  
 EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN
 OPEN THE DOOR FROM INSIDE THE CLOSET.
  
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY STAFF
 MEMBERS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE CARBON MONOXIDE DETECTORS FOR GAS FUELED
 APPLIANCES/WATER HEATERS.
  
 ELECTRICAL RECEPTACLES SHALL BE PROVIDED WITH
 PROTECTIVE COVERS.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT (50 PERCENT IF FULLY
 SPRINKLERED) OF THE INDIVIDUAL WALL AREA.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 A SMOKE DETECTION SYSTEM IS REQUIRED IN DAY-CARE
 OCCUPANCIES. CARBON MONOXIDE DETECTORS WILL ALSO BE
 REQUIRED IN SLEEPING AREAS IF THE BUILDING USES GAS
 WATER HEATERS OR GAS APPLIANCES.
  
 SHEET LS1 INDICATES THE BUILDING IS PROTECTED BY
 EXISTING FIRE ALARM AND FIRE SPRINKLER SYSTEMS.
 CONSTRUCTION DOCUMENTS ARE REQUIRED TO SHOW THE SCOPE
 OF WORK AFFECTING THESE EXISTING SYSTEMS. FIRE ALARM
 SYSTEM SHALL BE CERTIFIED FOR CENTRAL STATION SERVICE.
  
 VERIFY FIRE SPRINKLER SYSTEM EXISTS AS THIS WILL AFFECT
 THE REQUIREMENT FOR RESCUE WINDOWS OR OTHER EXITS.
  
 SEPARATE PLANS AND SUB-PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-05-19 Cont ID  
Sent By mcarsill Date 2011-05-19 Time 13:02 Rev Time 0.00
Received By mcarsill Date 2011-05-19 Time 12:59 Sent To  
Notes
2011-05-19 13:02:371225 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 11050304
 "PATIO ENCLOSURE"
  
  
 1. PLEASE DECLARE OCCUPANCY TYPE FOR BUILDING.
 PREVIOUSLY THIS BUILDING WAS A RESTAURANT.
  
 2. PERMIT APPLICATION SEEMS TO SUGGEST THAT THE
 BUILDING IS USED FOR EARLY LEARNING.
  
 3. PLEASE PROVIDE FLOOR PLAN FOR BUILDING.
  
 4. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 5. PLEASE INDICATE EXISTING EXIT DOOR LOCATIONS FROM
 THE BUILDING.
  
 6. WHAT MATERIALS WILL BE STORED IN THE PLAY AREA.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-06-07 Cont ID  
Sent By jwitmer Date 2012-06-07 Time 08:58 Rev Time 0.00
Received By jwitmer Date 2012-05-10 Time 14:18 Sent To  
Notes
2012-05-10 14:18:22IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-01-19 Cont ID  
Sent By astelly Date 2012-01-19 Time 09:55 Rev Time 0.00
Received By astelly Date 2011-11-28 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-11-16 Time 11:14 Rev Time 0.00
Received By shill Date 2011-10-18 Time 13:11 Sent To  
Notes
2011-10-18 13:12:08SENT TO B11 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-12 Cont ID  
Sent By lmartine Date 2011-06-02 Time 15:17 Rev Time 0.00
Received By lmartine Date 2011-05-11 Time 08:32 Sent To  
Notes
2011-05-11 08:32:45B4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2012-06-07 Cont ID  
Sent By jwitmer Date 2012-06-07 Time 08:58 Rev Time 0.00
Received By jwitmer Date 2012-06-07 Time 08:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-05-21 Cont ID  
Sent By jwitmer Date 2012-05-21 Time 11:54 Rev Time 0.00
Received By jwitmer Date 2012-05-21 Time 11:54 Sent To  
Notes
2012-05-21 11:56:02ASSEMBLY TO DAYCARE, NO CHANGE IN EQUIPMENT OR DUCT
 WORK, FIRE DAMPERS ADDED FOR RATING OF CORRIDORS, WILL
 NEED FIRE DAMPER SPECS AT THE JOBSITE AT TIME OF
 INSPECTION. JW.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-11-16 Cont ID  
Sent By hmoser Date 2011-11-16 Time 13:56 Rev Time 0.00
Received By hmoser Date 2011-11-16 Time 13:49 Sent To  
Notes
2011-11-16 13:56:30PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO ROOF
 TIE DOWN AND THE UNIT TO CURB TIE DOWN AT 1ST.
 INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-11-03 Cont ID  
Sent By rregueir Date 2011-11-03 Time 10:23 Rev Time 0.00
Received By rregueir Date 2011-11-02 Time 15:49 Sent To  
Notes
2011-11-03 10:23:11REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE ENGINEERED DETAIL FOR ATTACMENT OF NEW
 ROOFTOP EQUIPMENT TO BUILDING STRUCTURE PER FBC-M
 301.12.
  
 2. PAGE M-1 OUTSIDE AIR CALCULATION: TABLE INDICATES
 CALCULATIONS ARE PER FBC-M 403.3 WHILE NOTE #2
 INDICATES ASHRAE 62.1 IS USED. WHICH IS CORRECT? ONE
 METHOD OR THE OTHER SHALL BE LECTED AND ADHERED TO.
  
 3. PAGE M-1 OUTSIDE AIR CALCULATION: IF ASHRAE 62.1 IS
 ELECTED, THE VENTILATION TOTALS LISTED ARE TO ALSO
 INCLUDE AN ADDITIONAL 0.18 CFM/SF OF FLOOR AREA IN THE
 SPACES BEING VENTILATED FOR DAYCARE OCCUPANCIES. SEE
 ASHRAE 62.1 TABLE 6-1 AND BREATHING ZONE OUTDOOR
 AIRFLOW EQUATION 6-1 IN SECTION 6.2.2.1.
  
 4. PLANS INDICATE HVAC SYSTEM DESIGN BY "K.O. ENERGY
 DESIGN, LLC." THIS DOES NOT APPEAR TO BE A PROFESSIONAL
 ENGINEER OR ENGINEERING BUSINESS. PLANS MUST BE
 DESIGNED BY AN ENGINEER IN ACCORDANCE WITH FBC-B
 105.3.1.2. SYSTEM MAY NOT BE DESIGNED BY A CONTRACTOR
 BECAUSE THE BUILDING OCCUPANT LOAD EXCEEDS 100 PERSONS.
 WHILE PAGE M-1 IS SIGNED AND SEALED BY AN ENGINEER, THE
 ENGINEER IS A "STRUCTURAL ENGINEER" AND NOT TAKING
 RESPONSIBILITY FOR THE MECHANICAL DESIGN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status N Date 2011-12-13 Cont ID  
Sent By lwagner Date 2011-12-13 Time 13:07 Rev Time 0.00
Received By lwagner Date 2011-12-12 Time 15:03 Sent To  
Notes
2011-12-13 13:00:14PLUMBING APPLICATION, DRAWING, FEES, AND PERMIT
 REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-11-16 Cont ID  
Sent By lwagner Date 2011-11-16 Time 12:19 Rev Time 0.00
Received By lwagner Date 2011-11-16 Time 10:57 Sent To  
Notes
2011-11-16 12:19:35OPENED IN ERROR

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-10-26 Cont ID  
Sent By lwagner Date 2011-10-26 Time 10:21 Rev Time 0.00
Received By lwagner Date 2011-10-26 Time 09:03 Sent To  
Notes
2011-10-26 10:20:16FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. 403.1 MINIMUM NUMBER OF FIXTURES. DAY CARE REQUIRES
 A SERVICE SINK. THE LOCATION OF THE PROVIDED DRINKING
 FOUNTAIN IS NOT SHOWN.
  
 ****NOTE****
 1. SHEET A-0 STATES - NO PLUMBING WORK ON THIS PROJECT.
 IS THE WATER HEATER BEING MOVED FROM IT'S EXISTING
 LOCATION?
  
 2. HAS THE EXISTING GREASE TRAP AND EXISTING GAS BEEN
 PROPERLY ABANDONED?
  
 3. THE HEALTH DEPARTMENT MAY HAVE OTHER FIXTURE
 REQUIREMENTS ABOVE WHAT IS REQUIRED IN THE PLUMBING
 CODE.
 HTTP://WWW.PBCHD.COM/ENV/CHILD_CARE/CHILD_CARE_FACILITI
 ES.HTML
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2012-01-19 Cont ID  
Sent By astelly Date 2012-01-19 Time 09:47 Rev Time 0.00
Received By astelly Date 2012-01-19 Time 09:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2011-11-15 Cont ID  
Sent By astelly Date 2011-11-15 Time 16:15 Rev Time 0.00
Received By astelly Date 2011-11-15 Time 16:15 Sent To  
Notes
2011-11-15 16:38:58AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE INDICATE WHETHER OR NOT THE SITE CURRENTLY HAS
 IRRIGATION. IF IT DOES, THE LOCATION OF THE SPRINKLERS
 MUST BE IDENTIFIED. IF NOT, IRRIGATION WILL HAVE TO BE
 INSTALLED UNDER A SEPARATE PERMIT.
 ONE 10'X25' LOADING SPACE IS REQUIRED FOR THIS PROJECT.
 PLEASE IDENTIFY THE LOCATION OF THE LOADING SPACE ON
 THE SITE PLAN.
 TWO BICYCLE PARKING SPACES ARE REQUIRED BASED ON THE
 NUMBER OF PARKING SPACES. PLEASE IDENTIFY THE LOCATION
 OF THE BICYCLE PARKING.
 A DROP-OFF AND PICK-UP AREA AREA MUST ALSO BE
 IDENTIFIED ON THE SITE PLAN.
 THE GATE AT THE REAR OF THE PROPERTY THAT PROVIDES
 ACCESS FOR EMERGENCY VEHICLES SWINGS INTO THE
 RIGHT-OF-WAY. PLEASE REVERSE THE SWING SO THAT THE GATE
 SWINGS INTO THE PROPERTY.
 BUILDING AND TRAFFIC CIRCULATION SIGNAGE WILL REQUIRE A
 SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-06-02 Cont ID  
Sent By astelly Date 2011-06-02 Time 08:38 Rev Time 0.00
Received By astelly Date 2011-06-02 Time 08:32 Sent To  
Notes
2011-06-02 09:04:03AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 THE DRAWINGS INDICATE THAT THE AREA FOR THE PROPOSED
 SCOPE OF WORK IS INDOOR PLAY AREA. AS A RESULT, THE
 ADDITION WILL INCREASE THE CAPACITY OF THE FACILITY.
 PLEASE INDICATE THE ENTIRE SQUARE FOOTAGE OF THE
 FACILITY SO THAT THE STUDENT CAPACITY OF THE FACILITY
 CAN BE CALCULATED. IN ADDITION, PLEASE INCLUDE A SITE
 PLAN WITH THE RESUBMISSION THAT INDICATES THE SQUARE
 FOOTAGE OF THE ENTIRE OUTDOOR PLAY AREA. LANDSCAPE
 BUFFERS CAN NOT BE COUNTED TOWARDS THE REQUIREMENT FOR
 OUTDOOR PLAY AREA.
  
 YOUR RESUBMISSION MAY GENERATE ADDITIONAL COMMENTS NOT
 REFLECTED IN THIS REVIEW.