Plan Review Details - Permit 11050203
Plan Review Stops For Permit 11050203
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-06-27 Cont ID  
Sent By shill Date 2011-06-27 Time 09:26 Rev Time 0.00
Received By shill Date 2011-06-27 Time 09:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-05-31 Cont ID  
Sent By shill Date 2011-05-31 Time 11:14 Rev Time 0.00
Received By shill Date 2011-05-31 Time 11:14 Sent To  
Notes
2011-05-31 11:20:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SPANS ARE NOT CORRECT. FOR INSTANCE, IF OPENING #1
 IS 108X48, WITH A 3" EDGE DISTANCE, SPAN SHOULD EQUAL
 BLADE LENGTH FOR ACCORDION SHUTTERS (ANCHOR TO ANCHOR
 FOR PANELS).
  
 2. SPANS NOT CLEAR, PRODUCT APPROVAL IS FOR ACCORDION
 SHUTTERS BUT INSTALLATION SCHEDULE STATES THE SHUTTERS
 WILL BE INSTALLED HORIZONTALLY. ACCORDION SHUTTERS ARE
 INSTALLED VERTICALLY. REVISE INSTALLATION SCHEDULE TO
 REFLECT JOB CONDITIONS SO CODE COMPLIANCE CAN BE
 DETERMINED. FBC R 301.
  
 3. REVISE INSTALLATION SHEDULE SO THE "SHUTTER
 CONNECTION MOUNTING TYPE" CLEARLY SHOWS CONSTRUCTION
 PROPOSED. FBC R301.
  
 FOR INSTANCE, OPENING #1 (AND OTHERS) STATE THAT "4" IS
 TO BE USED. SEE SHEET 7 OF THE PRODUCT APPROVAL. IN THE
 CONCRETE BLOCK SECTION, THE SECOND COLUMN IS FOR 1&2
 WITH 4. THE THIRD COLUMN IS 3&4 W/2+5. 9" SPACING
 PROPOSED. FOR 1&2 W/4, TAPCON NOT ALLOWED AS A FASTENER
 FOR 50PSF. 3&4 REQUIRES 7.5" SPACING. PLEASE REVISE
 INSTALLATION SCHEDULE TO COMPLLY WITH REQUIREMENTS OF
 PRODUCT APPROVAL. FBC R 301.
  
 ONE TIME ONLY - DUE TO THE LENGHT OF TIME FOR REVIEW,
 CONTRACTOR MAY RESUBMIT VIA EMAIL OR FAX.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-10 Cont ID  
Sent By shill Date 2011-05-10 Time 16:50 Rev Time 0.00
Received By shill Date 2011-05-10 Time 16:50 Sent To  
Notes
2011-05-10 16:53:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 THIS SHOULD CORRELATE WITH THE FLOORPLAN.
  
 2. APPLICATION STATES THAT THREE FIXED WINDOWS WILL BE
 INSTALLED. FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, 9N-3.
  
 3. PROVIDE A PLAN WHICH SHOWS PROPOSED WINDOW LOCATION
 AND SIZES. PROVIDE ROOM DESIGNATIONS, SEE FBC R310, FBC
 EB 604.1. IF INSTALLATION IS IN A BEDROOM, SHOW
 ALTERNATE EMERGENCY ESCAPE AND RESCUE OPENING.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-06-27 Cont ID  
Sent By shill Date 2011-06-27 Time 09:26 Rev Time 0.00
Received By shill Date 2011-06-26 Time 10:42 Sent To  
Notes
2011-06-26 10:44:04GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-31 Cont ID  
Sent By shill Date 2011-05-31 Time 11:20 Rev Time 0.00
Received By shill Date 2011-05-20 Time 16:44 Sent To  
Notes
2011-05-20 16:44:44SENT TO SAMANTHA'S DESK FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-10 Cont ID  
Sent By shill Date 2011-05-10 Time 16:53 Rev Time 0.00
Received By shill Date 2011-05-09 Time 14:16 Sent To  
Notes
2011-05-09 14:16:14TO MISC 1
  