Plan Review Details - Permit 11050074
Plan Review Stops For Permit 11050074
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-06 Cont ID  
Sent By shill Date 2011-05-06 Time 12:17 Rev Time 0.00
Received By shill Date 2011-05-06 Time 12:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-04 Cont ID  
Sent By jgomez Date 2011-05-04 Time 08:46 Rev Time 0.00
Received By jgomez Date 2011-05-04 Time 08:46 Sent To  
Notes
2011-05-04 09:17:07RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ENGINEER TO PROVIDE THE CALCULATED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA 10-1230.02 SUBMITTED.
  
 2- FASTENER SPACING CAN'T BE LESS THAN 4"O.C. SEE SEC.
 8.1 OF RAS 117 CALCULATIONS. ENGINEER SPECIFIED 3"O.C.
 FASTENER SPACING ON SECTION D FORM AND THE FLAT ROOF
 INFORMATION FORM SUBMITTED. REVISE AS REQUIRED. PLEASE
 DON'T USE THE PALM BEACH COUNTY FORMS. THOSE FORMS ARE
 NO PART OF THE CITY REQUIREMENTS FOR ROOFING PERMITS.
 PROVIDE REQUIRED INFORMATION ON SEPARATE SHEETS SIGNED
 AND SEALED BY THE ENGINEER AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
  
 3- FASTENER SPACING SHALL BE ROUNDED DOWN TO THE NEXT
 WHOLE NUMBER NOT ROUNDED UP. SEE SEC. 10.4.5 OF RAS
 117. IT LOOKS LIKE ENGINEER ROUNDED UP THE FASTENER
 SPACING FOR CORNER AREAS TO HAVE 2 ROWS IN THE CENTER
 OF THE SHEET. SEE SECTION D AND FLAT ROOF INFORMATION
 FORM SUBMITTED. REVISE AS REQUIRED. PLEASE DON'T USE
 PALM BEACH COUNTY FORMS.
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR THE POLYFOAM TO BE USED. NONE WAS
 SUBMITTED AT THIS TIME. PLEASE VISIT THE MIAMI-DADE
 WEBSITE TO DOWNLOAD CURRENT NOA.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-05-03 Cont ID  
Sent By fmittner Date 2011-05-03 Time 14:46 Rev Time 0.00
Received By fmittner Date 2011-05-03 Time 14:46 Sent To  
Notes
2011-05-03 14:47:13FHM APPROVED FOR FLAT TO FLAT AND BARREL TILE TO BARREL
 TILE. RETURNED PAPERWORK TO CUSTOMER 5-3-11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-03 Cont ID  
Sent By jgomez Date 2011-05-03 Time 15:24 Rev Time 0.00
Received By jgomez Date 2011-05-03 Time 15:24 Sent To  
Notes
***NONE***