Plan Review Details - Permit 11040608
Plan Review Stops For Permit 11040608
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-04-26 Cont ID  
Sent By wjolin Date 2011-04-26 Time 12:37 Rev Time 0.00
Received By wjolin Date 2011-04-26 Time 12:27 Sent To  
Notes
2011-04-26 12:37:271258 PALM BEACH LAKES BOULEVARD
 PERMIT #11040608
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A PLACARD INDICATING THE USE OF THE TYPE K
 EXTINGUISHER AS A SECONDARY MEANS TO THE AUTOMATIC FIRE
 EXTINGUISHING SYSTEM.
  
 VERIFY EXHAUST SYSTEM AUTOMATICALLY OPERATES WHENEVER
 COOKING EQUIPMENT IS TURNED ON.
  
 VERFIY DEEP FAT FRYERS ARE LOCATED AT LEAST 16 INCHES
 AWAY FROM SURFACE FLAMES OF ADJACENT EQUIPMENT OR
 PROVIDE AN 8 INCH TALL STEEL BAFFLE BETWEEN THE FRYER
 AND THE STOVE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-26 Cont ID  
Sent By wjolin Date 2011-04-26 Time 12:38 Rev Time 0.00
Received By wjolin Date 2011-04-25 Time 12:53 Sent To  
Notes
2011-04-25 12:54:08SENT TO FIRE BOX.